![York Ylha plus 12 Installation Manual Download Page 17](http://html1.mh-extra.com/html/york/ylha-plus-12/ylha-plus-12_installation-manual_4247736017.webp)
Pressure drop in filters
1" filter
Water flow rate (l/h)
600
800
1000
1200
1400
1600
kPa
0,7
1,4
2,6
4,3
6,4
8,9
Water flow rate (l/h)
1800
2000
2200
2400
2600
kPa
11,8
15,1
18,8
22,8
27,1
1 1/4" filter
Water flow rate (l/h)
1500
2000
2500
3000
3500
kPa
0,9
1,5
2,6
3,9
5,6
Water flow rate (l/h)
4000
4500
5000
5500
6000
kPa
7,7
10,1
12,8
15,7
18,8
Data with water at 10°C.
In the case of using glycol, apply the correcting factors indicated in Section
Correcting factors for other
glycol concentrations
, see on page 12.