OPERATIONAL LIMITATIONS (ENGLISH)
TABLE 3 -
TEMPERATURES AND FLOWS
UNIT
DESIGNATION
TEMPERATURE
WATER FLOW
(GPM) MIN
WATER FLOW
(GPM) MAX
AIR ON CONDENSER (°F)
MIN
1
MAX
2
MIN
3
MAX
4
STANDARD EFFICIENCY
YLAA0070SE
40
55
60
325
0
125
YLAA0080SE
40
55
100
350
0
125
YLAA0089SE
40
55
100
400
0
125
YLAA0100SE
40
55
100
400
0
125
YLAA0120SE
40
55
150
625
0
125
YLAA0136SE
40
55
115
530
0
125
YLAA0155SE
40
55
150
625
0
125
YLAA0170SE
40
55
138
525
0
125
HIGH EFFICIENCY
YLAA0058HE
40
55
60
325
0
125
YLAA0065HE
40
55
60
325
0
125
YLAA0081HE
40
55
115
530
0
125
YLAA0092HE
40
55
100
400
0
125
YLAA0101HE
40
55
100
400
0
125
YLAA0125HE
40
55
100
400
0
125
YLAA0142HE
40
55
150
530
0
125
YLAA0156HE
40
55
138
525
0
125
YLAA0175HE
40
55
200
650
0
125
YLAA0200HE
40
55
230
625
0
125
YLAA0230HE
40
55
220
625
0
125
NOTES:
1. For leaving liquid temperature below 40°F (4°C) (to 10°F [-12°C]) optional low temperature glycol kit required. Contact your
nearest Johnson Controls Office for application requirements.
2. For leaving liquid temperature higher than 55°F (13°C), contact the nearest Johnson Controls Office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-29°C) with an electric heater as standard.
4. For operation at temperatures above 115°F (46°C), the optional High Ambient Kit will need to be installed on the system.
Excessive flow will cause damage to the
cooler. Do not exceed maximum cooler
flow. Special care should be taken when
multiple chillers are fed by a single pump.