Read this manual before installation and operation

Make sure that it is well kept for later reference

YKFE12BXEXBH-RX

YKFE(18-36)BXEXBH-RX

YKFE(36-55)BXOXBH-RX

YKFE(12-36)BYEXBHO-X

YKFE36BYOXBHO-X

YKFE48BYOXBHS-X

YKFE55BYOXBHS-X

S

INSTALLATION AND OWNER' ANUAL

M

Summary of Contents for YKFE12BXEXBH-RX

Page 1: ... installation and operation Make sure that it is well kept for later reference YKFE12BXEXBH RX YKFE 18 36 BXEXBH RX YKFE 36 55 BXOXBH RX YKFE 12 36 BYEXBHO X YKFE36BYOXBHO X YKFE48BYOXBHS X YKFE55BYOXBHS X S INSTALLATION AND OWNER ANUAL M ...

Page 2: ......

Page 3: ...ons 5 Installation Notice 6 Installation Place 7 General Installation Guideline 8 Preparation of Installing Parts and Tools 9 Installation Procedure 10 Piping Procedure 13 Installation of the Outdoor Unit 16 Install Outdoor Pipes and Cables 18 Connection of Outdoor Pipesand Cables 19 Electrical Wiring 20 Purge and Vacuum 21 Test Operation 22 Troubleshooting 23 ...

Page 4: ...ularly while the air conditioner is in use especially if there is also a gas appliance in use in this room Failure to follow these directions may result in a loss of oxygen in the room To prevent electric shock turn off the power or disconnect the power supply plug before beginning any cleaning or other routine maintenance Follow the directions for cleaning in the Owner s Manual Do not use liquid ...

Page 5: ...l shock can cause severe personal injury or death Only a qualified experienced electrician should attempt to wire this system Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked Highly dangerous electrical voltages are used in this system Carefully refer to the wiring diagram and these instructions when wiring Improper connections and inadequate gro...

Page 6: ...with high temp Malfunction may occur if infrared signal receiver on air conditioner is exposed to sunlight please shelter the signal receiver from sunlight with curtain Please remove the nearby electronic device for they may affect the performance of remote controller If necessary contact the local authorized service centre or technical support centre Do not put the used or different batteries int...

Page 7: ...PERATION MODE LOUVER SELECTION button TURBO QUIET button Mode is sequentially changed AUTO COOL DRY FAN Sequentially changed All 1 2 3 4 Functioning appears in lower angle TURBO provides a quicker cooling QUIET reduces airflow noise in cool mode Set the actual time hour and minute Pre set the on off time Indicate on off light for LCD panel display YCK3F10 15 18AAS W not available Lock the keypad T...

Page 8: ...le of up down swing 6 TURBO QUIET 1 Press TURBO QUIET the LCD displays TURBO Mode is set Press TURBO QUIET again the controller LCD displays the Quiet Mode is set Press TURBO QUIET again to exit the setting of TURBO QUIET Resume set air speed 2 This function is only enabled in Cool mode 7 TIMER Timer Timer On Press TIMER the ON blinking Press TIME TIME to select the desirable time Press SET to con...

Page 9: ...to avoid the noise or vibrations The noise near the air outlet of the outdoor unit may enter the air exit Locate the outdoor unit where noise emitted by it or hot air from its air outlet will not cause nuisance to your neighbours If the air conditioner sounds abnormal during operation contact the dealer where you purchased the air conditioner Wire To avoid the electric shock please link the air co...

Page 10: ...ore outdoor units are installed at the same zone there must be adequate space between units for avoiding short air cycle Cautions Location in the following places may cause malfunction of the machine If unavoidable please consult your local dealer a There exists petrolatum b There is salty air surrounding near the coast c There is caustic gas the sulfide for example existing in the air near a hot ...

Page 11: ...the flare nut indoor Connecting the pipings of the indoor unit 8 Check a gas leakage of the connecting part of the pipings 9 Air purging and vacuuming of the piping and indoor unit The air which contains moisture and which remains in the refrigeration cycle may cause a malfunction on the compressor 10 Open the liquid side and gas side valves 11 Form the pipings To prevent heat loss and sweat 12 Ch...

Page 12: ... Refrigerant R22 or R410A Gas charge Air purge Cleaning the pipe 12 Spanner To tighten the connecting parts of the pipings 13 Monkey spanner 14 Driver 15 Pliers 150mm Cutting the wires 16 Tapeline To measure the length 17 Core drill To make holes through the concrete wall and blocks 18 Voltmeter Ammeter Clamp meter To measure the current and voltage 19 Insulation resistance tester To measure the i...

Page 13: ...ts unit mm 535 Spacing of hanging screw 570 Indoor unit 570 Indoor unit 650 Ceiling opening 650 Ceiling opening 700 Trim panel 700 Trim panel YCK3F 10 18 AAS W 765 Spacing of hanging screw 765 Spacing of hanging screw 850 Indoor unit 850 Indoor unit 890 Ceiling opening 890 Ceiling opening 950 Trim panel 950 Trim panel YCK3F 20 60 AAS W 2 Hanging preparations Firmly fasten the hanging bolts Refer t...

Page 14: ...t its hooks onto the hanging bolt between the special nuts 3 Turn nut B to adjust the height of body 4 Leveling using a level to fine adjust the body for proper positioning Hook Fig 4 4 Panel Installation 1 Connect plugs of water pump and swing motor 2 Fix panel with screws Refrigerant pipe Indoor unit Drain pipe Housing 2 U shaped hooks Trim panel 4 Bolts M5 25 including gaskets Fig 5 Installatio...

Page 15: ...ay lead to water leaks and serious interior damage Note Install the drain pipe Install the drain pipe with downgrade gradient 1 50 to 1 100 and so there are no rises or traps in the pipe The bending angle of the drain pipe in the plastic bag should not exceed 45 glue cannot flow into the pipe Use general hard polyvinyl chloride pipe and connect it with adhesive so that there is no water leakage Ti...

Page 16: ...e a gas leakage 3 Flaring the pipes Insert the flare nuts mounted on the connection ports of both indoor and outdoor unit onto the copper pipes Some refrigerant gas may leak when the flare nuts are removed from the indoor unit as some gas is charged to prevent the inside of the pipe from rusting Fit the copper pipe end into the Bar of flare tool about 0 0 5mm higher See illustration Flare the pipe...

Page 17: ...r wall fix it on the wall by saddle or equivalent Tape the Piping and Connecting Cable from down to up In order to prevent water from entering the room tape the piping from a trap Fix the piping onto the wall with saddle or bracket In case the ourdoor unit is installed below position of the indoor unit In case the ourdoor unit is installed upper position of the indoor unit 1 1 2 2 3 3 Gas side pip...

Page 18: ...rrow on the wrench Pipe size Tighten torque A mm Flare shape ø6 35 1420 1720N cm 144 176kgf cm 8 3 8 7 R0 4 0 8 90 0 5 A 4 5 2 ø9 52 3270 3990N cm 333 407kgf cm 12 0 12 4 ø12 7 4950 6030N cm 490 500kgf cm 12 4 16 6 ø15 88 6180 7540N cm 630 770kgf cm 18 6 19 0 ø19 05 9720 11860N cm 990 1210kgf cm 22 9 23 3 If it is necessary locally purchased to bend or stretch the tubing use the spring which is at...

Page 19: ... is open the unit can not be installed there 2 When the front side air outlet is open and obstruction is lower than unit if we can keep the space as shown in the figure this position is still feasible even if there is obstruction in other three sides The top side is open 4 When there is obstruction at both front side and backside plaese don t choose the following location 6 While installing the ou...

Page 20: ...r unit unit mm Model Diameter Maximum length Maximum height between indoor and outdoor Additional weight Liquid side Gas side YSM3F10AAS YSM3F15AAS 6 35mm 12 7mm 20m 5m 30g m YSM3F18AAS YSM3F20AAS 6 35mm 15 88mm 20m 5m 30g m YSM3F22AAS YSM3F25AAS YSM3F28AAS YSM3F30AAS YSM3F35AAS 9 52mm 15 88mm 30m 10m 50g m YSM3F40AAS YSM3F50AAS YSM3F60AAS 9 52mm 19 05mm 50m 20m 50g m When connecting pipes are lon...

Page 21: ...already Keep the connecting pipe dry and do not let moisture in during installation The Procedure of Connecting Pipes Measure the necessary length of the connecting pipe and make it by the following way 1 Connect the indoor unit at first then the outdoor unit 2 The stop valve the outdoor unit should be closed absolutely as original state Every time you connect it first loosen the nuts at the part ...

Page 22: ...10AAS YSM3F15AAS Liquid pipe ø6 35mm 1 4 Gas pipe ø12 7mm 1 2 YSM3F18AAS YSM3F20AAS Liquid pipe ø6 35mm 1 4 Gas pipe ø15 88mm 5 8 YSM3F22AAS YSM3F25AAS YSM3F28AAS YSM3F30AAS YSM3F35AAS Liquid pipe ø9 52mm 3 8 Gas pipe ø15 88mm 5 8 YSM3F40AAS YSM3F50AAS YSM3F60AAS Liquid pipe ø9 52mm 3 8 Gas pipe ø19 05mm 3 4 1 2 1 Open the control board cover from the outdoor unit by removing the screws 2 Connect ...

Page 23: ...tors cables or relays use only the exact type size voltage and current rating of the component as furnished from the factory 7 While removing fixing supply cord loosen the top clamp of cord anchorage route the cord and fix the top clamp again Length of the earth conductor should be more than supply conductor for safety in case of cord slippage Field Wiring Diagrams YCK3F 10 18 ASS W YSM3F 10 18 AS...

Page 24: ...e In case of gas leakage tighten parts of piping joint If leakage stops then proceed step 6 If it does not stop gas leakage discharge whole refrigerants from the service port Repeat piping procedure and vacuumize 6 Detach the charge hose from the service port open liquid valve and gas valve Turn the valve rod anticlockwise until hitting lightly 7 To prevent the gas leakage close service port s cap...

Page 25: ... Test operation Set the air conditioner under the mode of COOLING with the remote controller and check the following points as per this Manual If there is any malfunction please resolve it through chapter Trouble Shooting in the Manual 1 The indoor unit a Whether the switch on the remote controller works well b Whether the buttons on the remote controller works well c Whether the air flow louver m...

Page 26: ...ne voltage Blocked condenser Defective run start capacitor overload start relay defective thermostat fault condenser fan motor or capacitor Obstructions in refrigerant system Reclaim refrigerant evacuate and recharge as on nameplate Replace compressor Call power distributor Determine cause and correct Replace fault component Locate obstructions and remove Compressor operates continuously Dirty air...

Page 27: ...Troubleshooting YSM3F 10 18 AAS LED flash times of signal receiver board Wired controller display Troubleshooting Possible reasons 10 E0 Malfunction of drain system Pump motor disconnected or at wrong position or the float switch broken down or the float switch disconnected or at wrong position 1 E1 Faulty ambient temperature sensor Sensor disconnected or broken or at wrong position or short circu...

Page 28: ... wired controller be disconnected faulty PCB F2 F2 EEPROM error Loss of data EEPROM FC FC Indoor coil temperature too high in cooling mode Refrigerant leakage or indoor coil sensor falling off or failure on 3 phases outdoor unit Optional equipment Outdoor toubleshooting LED flash times of outdoor control board Troubleshooting Possible reasons 4 Protection of discharging temp too high or sensor abn...

Page 29: ...26 ...

Page 30: ...27 ...

Page 31: ...28 ...

Page 32: ...Johnson Controls reserve the right to change product features without prior notice 2014 Johnson Controls Inc www johnsoncontrols com Doc No 160701 ...