Advanced trend setup screen
Figure 81: Advanced trend setup screen
The desired data collection start/stop triggers are setup on this screen. The trend data collection
can be set to start or stop based upon the status of up to two selected triggers. The triggers can
consist of digital events or analog parameters compared to thresholds. The triggers can be used
individually or in combination. The digital and analog parameters are selected from the Common
Slots Screen (or Master Slot Numbers List in this manual).
The parameter selected as the Primary Trigger is compared to a value selected as the Primary Test,
using the Primary Operator as a comparator. If it is evaluated as true, then the data collection is
started or stopped (after any selected trigger delay) per the selected Trigger Action.
A Secondary Trigger can be evaluated with the Primary Trigger to start/stop data collection. The
Primary to Secondary Operator is used to define the trigger combinations required to be true to
start/stop data collection. The Secondary Trigger is setup and evaluated the same as the Primary
Trigger.
Entry fields are as follows:
1. Primary Trigger
a. Primary Operator
b. Primary Test
2. Primary to Secondary Operator
3. Secondary Trigger
a. Secondary Operator
b. Secondary Test
4. Trigger Action
a. Delay of Trigger Delay
After the desired triggers are set, the START key on the TREND Screen must be manually pressed
before the triggers will be evaluated. While waiting for the triggers to start or stop data collection, a