![background image](http://html.mh-extra.com/html/york/yj-30/yj-30_technical-manual_913540009.webp)
628792-BTG-G-0418
Ducted Systems
9
Sound Performance
Outdoor Sound Power Levels (dB), 60 Hz
Model
Nominal
Tonnage
dB(A)
1
1
Rated in accordance with AHRI 270 Standard.
Electrical Data
Octave Bands (Hz)
63
125
250
500
1000
2000
4000
8000
YJ-30
30
92
90
93
91
89
87
83
79
74
YJ-40
40
92
90
93
91
89
87
84
80
75
YJ-50
50
93
91
94
92
90
87
84
80
75
YJ-30 thru -50 Electrical Data
Model
Compressors
Outdoor Fan Motor
Minimum
Circuit
Ampacity
Maximum
Fuse Size
(A)
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP
Qty
FLA
(each)
YJ-30
208/230-3-60
4
25.0
39
164
208/230-3-60
1 1/2
4
5.8
129.5
150
460-3-60
4
12.2
19
100
460-3-60
1 1/2
4
2.9
63.5
70
575-3-60
4
9.0
14
78
575-3-60
1 1/2
4
2.2
47.1
50
YJ-40
208/230-3-60
4
30.1
47
225
208/230-3-60
1 1/2
4
5.8
151.1
175
460-3-60
4
16.7
26
114
460-3-60
1 1/2
4
2.9
82.6
90
575-3-60
4
12.2
19
80
575-3-60
1 1/2
4
2.2
60.7
70
YJ-50
208/230-3-60
4
48.1
75
245
208/230-3-60
1 1/2
4
5.8
227.6
250
460-3-60
4
18.6
29
125
460-3-60
1 1/2
4
2.9
90.7
100
575-3-60
4
14.7
23
100
575-3-60
1 1/2
4
2.2
71.3
80