9.1 Indoor Unit Error Display
Operation
lamp
Timer lamp
Display
LED STATUS
☆
1 time
X
E0
Indoor unit EEPROM parameter error
☆
2 times
X
E1
Indoor / outdoor units communication error
☆
4 times
X
E3
Indoor fan speed has been out of control
☆
5 times
X
E4
Indoor room temperature sensor T1 open circuit or short
circuit
☆
6 times
X
E5
Evaporator coil temperature sensor T2 open circuit or
short circuit
☆
7 times
X
EC
Refrigerant leakage detection
☆
1 times
O
F0
Overload current protection
☆
2 times
O
F1
Outdoor ambient temperature sensor T4 open circuit or
short circuit
☆
3 times
O
F2
Condenser coil temperature sensor T3 open circuit or
short circuit
☆
4 times
O
F3
Compressor discharge temperature sensor T5 open
circuit or short circuit
☆
5 times
O
F4
Outdoor unit EEPROM parameter error
☆
6 times
O
F5
Outdoor fan speed has been out of control
☆
1 times
☆
P0
IPM malfunction or IGBT over-strong current protection
☆
2 times
☆
P1
Over voltage or over low voltage protection
☆
3 times
☆
P2
High temperature protection of IPM module or
compressor top
☆
5 times
☆
P4
Inverter compressor drive error
O
(
light
)
X
(
off
)
☆(
flash
)
* Fault Symptom:
The display board shows a garbled code or a code that is not an error code found
in the service manual nor a temperature reading.
Trouble shooting:
Use the remote controller. If the unit does not respond to the remote, the indoor PCB needs to be
replaced; if the unit does respond, then the display board needs to be replaced.
Summary of Contents for YHKE09XEEAMH-RX
Page 8: ...6 For 7K INDOOR YHKE09XEEAMH RX For YHKE12XEEAMH RX For YHKE18XEEAMH RX...
Page 9: ...7 For YHKE24XEEAMH RX...
Page 13: ...11 For YHKE24YEEAMHO X MOCA30 24HFN1 QRC8GW...
Page 23: ...21 6 2 Outdoor Unit YHKE09YEEAMHO X YHKE12YEEAMHO X...
Page 24: ...22 YHKE18YEEAMHO X YHKE24YEEAMHO X...
Page 53: ...2016 Johnson Controls Inc www johnsoncontrols com Doc No M Pyrenees 160929...