Technical Guide

LX SERIES
SPLIT-SYSTEM
HEAT PUMPS

14 SEER - R-410A - 1 PHASE
1.5 THRU 5 NOMINAL TONS

MODELS: YHJD18 THRU 60

®

Due to continuous product improvement, specifications are sub-
ject to change without notice.

Visit us on the web at

www.upgnet.com

and

www.york.com

Additional rating information can be found at

www.ahridirectory.org

W

WAARRRRAANNTTYY SSUUM

MM

MAARRYY**

Standard 5-year limited parts warranty.
Standard 10-year limited compressor warranty.

Extended 10-year limited parts warranty

when product is

registered online within 90 days of purchase for replacement or
closing for new home construction.

*Does not apply to R-22 models, 3-Phase models, or internet sales.
See Limited Warranty certificate in User's Information Manual for details.

DESCRIPTION

The 14 SEER Series unit is the outdoor part of a versatile cli-
mate system. It is designed with a matching indoor coil compo-
nent from Johnson Controls Unitary Products. Available for
typical applications this climate system is supported with acces-
sories and documents to serve specific functions.

FEATURES

Small Footprint-

The compact footprint is a perfect fit for any

application.

Quality Condenser Coils-

The coil is constructed of copper

tubing and enhanced aluminum fins for increased
performance.

Coil Protection -

Coils are protected from damage by a slot-

ted, stamped steel coil guard.

Protected Compressor -

Compressors are protected inter-

nally by a high pressure relief valve and a temperature sen-
sor, and externally by the system high and low pressure
switches. A factory installed liquid line filter-drier further pro-
tects the compressor against moisture and debris.

Environmentally Friendly Refrigerant -

The next genera-

tion refrigerant R-410A delivers environmentally friendly per-
formance with zero ozone depletion.

Durable Finish -

The cabinet is made of G90-equivalent

galvanized steel, finished in a durable champagne colored
powdercoat. The coated steel wire fan guard and pre-treated,
galvanized steel chassis components resist corrosion and
rust creep.

Lower Installed Cost -

Installation time and costs are re-

duced by easy power and control wiring connections. The
unit is factory charged for a 15-foot lineset. The small base di-
mension means less space is required on the ground or roof.

Top Discharge -

Warm air from the top mounted fan is blown

up, away from the structure and any landscaping. This allows
compact location on multi-unit applications.

Low Operating Sound Level -

The upward air flow carries

the normal operating noise away from the living area. The rig-
id top panel effectively isolates any motor sound. Isolator
mounted compressor and the condenser coil muffle the nor-
mal fan motor and compressor operating sounds.

Low Maintenance -

Long life, permanently lubricated motor-

bearings need no annual servicing.

Easy Service Access -

Fully exposed refrigerant connec-

tions and a single panel covering the electrical controls make
for easy servicing of the unit.

Secured Service Valves -

Secured, re-usable service valves

are provided on both the liquid and vapor sweat connections
for ease of evacuating and charging.

Agency Listed -

Safety certified by CSA to UL 1995 / CSA

22.2. Performance certified to ANSI/AHRI Standard 210/240
in accordance with the Unitary Small Equipment certification
program.

571209-YTG-

F

-0

6

15

FOR INSTALLATION IN ALL US REGIONS AND CANADA

Installation Allowed

Summary of Contents for YHJD24S41S7

Page 1: ...nstalled liquid line filter drier further pro tects the compressor against moisture and debris Environmentally Friendly Refrigerant The next genera tion refrigerant R 410A delivers environmentally fri...

Page 2: ...ed 3 4 3 4 3 4 3 4 7 8 7 8 1 1 8 Unit Charge Lbs Oz 5 6 15 9 5 8 13 10 14 10 11 16 8 16 12 Charge Per Foot Oz 0 62 0 62 0 62 0 62 0 67 0 67 0 75 Operating Weight Lbs 172 194 206 218 218 285 290 These...

Page 3: ...pflow Downflow Horizontal Furnaces and Coils table FOOTNOTES 1 For applications requiring a TXV use S1 1TVM series kit 2 Approved orifice s shipped with outdoor unit 3 Systems matched with furnaces or...

Page 4: ...1010 30 0 21 8 14 00 12 00 YHJD30S41S7 MV12B 17 5 FC MC43B 1000 30 0 23 0 14 00 12 00 YHJD30S41S7 MV16C 21 0 FC MC35C 1070 30 0 23 0 14 00 12 00 YHJD30S41S7 MV16C 21 0 FC MC43C 1000 30 0 23 0 14 00 12...

Page 5: ...YHJD60S41S7 AHE60D 24 5 1835 57 0 42 5 14 00 12 00 YHJD60S41S7 AHV60D 24 5 1635 57 0 40 5 14 00 12 00 YHJD60S41S7 MV20D 24 5 FC MC62D 1855 57 0 42 5 14 00 12 00 YHJD60S41S7 MV20D 24 5 FC64D 1855 57 0...

Page 6: ...60B12MP11 17 5 FC MC PC35B 600 18 0 13 4 14 00 12 00 YHJD18S41S7 TM9E080B12MP11 17 5 FC MC PC24B 600 18 0 12 9 14 00 12 00 YHJD18S41S7 TM9E080B12MP11 17 5 FC MC PC30B 600 18 0 13 1 14 00 12 00 YHJD18S...

Page 7: ...8 0 14 00 12 00 YHJD24S41S7 Y 8 L C A12 14 5 FC MC PC37A 765 24 0 15 7 14 00 12 00 YHJD24S41S7 Y 8 L C B12 17 5 FC MC PC35B 630 23 0 15 6 14 00 12 00 YHJD24S41S7 Y 8 L C B12 17 5 FC MC PC43B 790 24 0...

Page 8: ...22 2 14 00 12 00 YHJD30S41S7 Y 8 L C C16 21 0 FC MC PC35C 985 30 0 23 0 14 00 12 00 YHJD30S41S7 Y 8 L C C16 21 0 FC MC PC43C 1035 30 0 22 2 14 00 12 00 YHJD30S41S7 Y 8 L C C20 21 0 FC MC PC35C 1035 30...

Page 9: ...C MC PC43C 1190 36 0 27 2 14 00 12 00 YHJD36S41S7 Y 8 L C C20 21 0 FC MC PC48C 1150 36 0 27 2 14 00 12 00 YHJD36S41S7 Y 9C C16 21 0 FC MC PC48C 1195 35 8 26 2 14 00 12 00 YHJD36S41S7 Y 9C C20 21 0 FC...

Page 10: ...445 41 0 31 6 14 00 11 50 YHJD42S41S7 Y 9C C20 21 0 FC MC PC48C 1430 41 0 31 4 14 00 11 75 YHJD42S41S7 Y 9C C20 21 0 FC MC PC48D 1430 41 0 31 2 14 00 11 75 YHJD42S41S7 Y 9C C20 21 0 FC PC60C 1445 41 5...

Page 11: ...0 57 0 40 0 14 00 12 00 YHJD60S41S7 TM9E120D20MP11 24 5 FC MC62D 1550 56 5 41 0 14 00 12 00 YHJD60S41S7 TM9E120D20MP11 24 5 FC64D 1525 57 0 39 0 14 00 12 00 YHJD60S41S7 TMLX100C20MP11 21 0 FC MC62D 15...

Page 12: ...86 2 16 13 6 2 30 1 73 8 20 YHJD30S41S7 MV12B FC MC43B 28 8 3 92 2 15 13 9 2 32 1 76 8 20 YHJD30S41S7 MV16C FC MC35C 28 4 3 94 2 11 13 7 2 34 1 72 8 20 YHJD30S41S7 MV16C FC MC43C 28 8 3 94 2 14 13 8 2...

Page 13: ...FC MC60D 46 0 3 60 3 74 24 0 2 46 2 86 8 20 YHJD48S41S7 MX20DN21 FC MC62D 45 0 3 42 3 86 24 4 2 52 2 84 8 20 YHJD60S41S7 AHE60D 57 0 3 76 4 44 37 8 2 50 4 43 8 20 YHJD60S41S7 AHV60D 57 0 3 64 4 59 37...

Page 14: ...24B 17 3 3 58 1 42 10 3 2 20 1 37 8 20 YHJD18S41S7 TM9E060B12MP11 FC MC PC30B 17 3 3 58 1 42 10 3 2 20 1 37 8 20 YHJD18S41S7 TM9E060B12MP11 FC MC PC35B 17 5 3 70 1 39 11 1 2 44 1 33 8 20 YHJD18S41S7 T...

Page 15: ...8 20 YHJD24S41S7 TMLX080B12MP11 FC MC PC43B 23 4 3 90 1 76 12 3 2 48 1 45 8 20 YHJD24S41S7 TMLX080C16MP11 FC MC PC43C 23 6 3 80 1 82 12 5 2 40 1 53 8 20 YHJD24S41S7 TMLX100C16MP11 FC MC PC43C 23 6 3 8...

Page 16: ...13 6 2 30 1 73 8 20 YHJD30S41S7 TMLX120C20MP11 FC MC PC43C 28 8 3 94 2 14 13 8 2 34 1 73 8 20 YHJD30S41S7 Y 8 L C A12 FC MC PC32A 28 4 3 64 2 29 13 1 2 26 1 70 8 20 YHJD30S41S7 Y 8 L C A12 FC MC PC37...

Page 17: ...8D 35 2 3 74 2 76 18 4 2 44 2 21 8 20 YHJD36S41S7 Y 8 L C B12 FC MC PC43B 34 2 3 60 2 78 18 0 2 40 2 20 8 20 YHJD36S41S7 Y 8 L C C16 FC MC PC43C 35 0 3 74 2 74 18 4 2 46 2 19 8 20 YHJD36S41S7 Y 8 L C...

Page 18: ...3 11 20 6 2 42 2 49 8 20 YHJD42S41S7 Y 8 L C C20 FC PC60C 39 5 3 92 2 95 22 4 2 64 2 49 8 20 YHJD42S41S7 Y 9C C16 FC MC PC48C 39 5 3 70 3 13 20 8 2 40 2 54 8 20 YHJD42S41S7 Y 9C C16 FC MC PC48D 39 5...

Page 19: ...2D 57 0 3 56 4 69 37 6 2 42 4 55 8 20 YHJD60S41S7 TM9E120D20MP11 FC64D 57 0 3 64 4 59 37 6 2 46 4 48 8 20 YHJD60S41S7 TMLX100C20MP11 FC MC62D 57 0 3 64 4 59 37 6 2 46 4 48 8 20 YHJD60S41S7 TMLX100C20M...

Page 20: ...nal staging of supplemental electric heat Low Ambient Pressure Switch Kit S1 2LA06700424 Al lows the use of air conditioning at low outdoor ambient temper atures down to 20 F 7 C For use with single s...

Page 21: ...OST CONTROL FIELD INSTALLED JUMPER DEHUMIDIFICATION CONTROL CONNECTION Humidistat Jumper must be removed GND SCREW CONTACTOR T2 T1 L2 L1 M R L or X Y O W G T2 E2 R R Y Y O O W2 W C C X L G W1 BK GND L...

Page 22: ...14 4 16 3 18 0 S C 12 5 12 6 10 5 10 7 8 6 14 2 14 3 12 7 12 8 9 8 15 9 15 9 14 4 14 9 11 0 KW 1 70 1 70 1 70 1 80 1 80 1 80 1 80 1 80 1 80 1 90 1 90 1 90 1 90 1 90 2 00 125 T C 11 5 11 4 11 6 13 4 1...

Page 23: ...A 0 97 0 94 1 00 TM9E060B12MP11 FC MC PC24B 0 97 0 96 1 00 TM9E060B12MP11 FC MC PC30B 1 03 1 14 1 10 TM9E060B12MP11 FC MC PC35B 0 97 0 94 1 00 Furnaces Coils T C S C KW TM9E080B12MP11 FC MC PC24B 1 03...

Page 24: ...9 4 19 4 17 7 20 0 22 2 S C 16 3 16 1 13 4 13 5 10 8 17 7 17 6 15 4 15 5 11 9 19 2 19 2 17 5 17 5 13 0 KW 2 05 2 05 2 05 2 11 2 16 2 16 2 16 2 15 2 21 2 24 2 26 2 26 2 24 2 30 2 32 125 T C 15 3 14 8 1...

Page 25: ...C35B 1 01 1 08 1 08 TM9E060B12MP11 FC MC PC43B 1 07 0 94 1 12 TM9E080B12MP11 FC MC PC35B 1 01 0 93 1 08 TM9E080B12MP11 FC MC PC43B 1 07 1 07 1 12 Furnaces Coils T C S C KW TM9E080C16MP11 FC MC PC35C 1...

Page 26: ...2 21 9 18 7 19 0 15 0 23 7 23 6 20 9 21 0 16 0 25 2 25 2 23 1 23 0 17 0 KW 2 44 2 43 2 43 2 50 2 53 2 52 2 52 2 52 2 57 2 60 2 61 2 61 2 61 2 65 2 67 125 T C 20 8 19 9 20 0 23 5 26 2 22 2 22 1 20 7 2...

Page 27: ...C MC PC35B 1 02 0 99 1 17 TM9E080B12MP11 FC MC PC43B 1 02 0 96 1 17 TM9E080C16MP11 FC MC PC35C 1 02 0 99 1 17 TM9E080C16MP11 FC MC PC43C 1 02 0 99 1 17 Furnaces Coils T C S C KW TM9E100C16MP11 FC MC P...

Page 28: ...17 3 26 6 27 1 23 5 23 8 18 5 28 9 28 8 25 4 25 8 19 7 KW 2 96 2 95 2 93 3 10 3 20 3 07 3 05 3 04 3 20 3 29 3 18 3 15 3 16 3 30 3 39 125 T C 21 7 22 6 21 8 25 8 30 1 24 1 24 8 21 9 26 5 31 2 26 5 27 0...

Page 29: ...C MC PC48C 0 98 1 03 1 05 TM9E080C16MP11 FC MC PC48D 0 98 1 03 1 05 TM9E100C16MP11 FC MC PC43C 0 98 0 99 1 04 TM9E100C16MP11 FC MC PC48C 0 98 1 03 1 05 Furnaces Coils T C S C KW TM9E100C16MP11 FC MC P...

Page 30: ...9 33 9 36 9 32 9 32 8 31 3 34 4 37 4 S C 30 6 30 4 25 6 25 2 19 4 31 7 31 6 27 6 27 2 20 5 32 9 32 8 29 7 29 1 21 6 KW 3 90 3 89 3 90 3 93 3 97 3 99 3 99 3 98 4 02 4 06 4 08 4 08 4 06 4 10 4 14 125 T...

Page 31: ...C MC PC48D 1 04 1 07 1 10 TM9E100C16MP11 FC MC PC48C 1 04 1 08 1 10 TM9E100C16MP11 FC MC PC48D 1 04 1 07 1 10 TM9E100C20MP11 FC MC PC48C 1 05 1 08 1 06 Furnaces Coils T C S C KW TM9E100C20MP11 FC MC P...

Page 32: ...44 2 36 9 37 1 37 2 41 0 45 1 38 7 37 9 38 1 42 0 46 1 S C 34 6 32 9 27 7 27 4 21 8 36 3 35 1 29 9 29 5 22 9 38 0 37 3 32 0 31 6 24 1 KW 4 34 4 35 4 36 4 40 4 46 4 44 4 44 4 44 4 48 4 54 4 53 4 52 4...

Page 33: ...MP11 FC PC60C 0 99 1 09 1 15 TM9E100C16MP11 FC MC PC60D 0 99 1 04 1 15 TM9E100C16MP11 FC MC62D 0 99 1 08 1 15 TM9E100C16MP11 FC PC60C 0 99 1 00 1 15 Furnaces Coils T C S C KW TM9E100C20MP11 FC MC PC60...

Page 34: ...KW 6 51 6 48 6 50 6 57 6 65 6 62 6 59 6 58 6 66 6 74 6 72 6 71 6 66 6 74 6 82 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT KW VALUES ARE FOR THE SYSTEM OUTDOOR INDOOR Green shaded cells are ACCA TVA co...

Page 35: ...2 2 1 24 9 5 2 3 1 22 80 8 6 1 8 1 39 8 9 1 9 1 37 9 3 2 0 1 34 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED KW VALUES ARE FOR THE SYSTEM OUT DOOR INDOOR Yellow shaded cells are A...

Page 36: ...A 0 95 0 92 1 03 TM9E060B12MP11 FC MC PC24B 0 96 0 92 1 03 TM9E060B12MP11 FC MC PC30B 0 96 0 92 1 03 TM9E060B12MP11 FC MC PC35B 0 97 0 95 1 01 Furnace Coil MBH COP KW TM9E080B12MP11 FC MC PC24B 0 96 0...

Page 37: ...1 64 12 4 2 2 1 64 12 7 2 3 1 64 80 10 7 1 8 1 78 11 1 1 8 1 79 11 4 1 9 1 79 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED KW VALUES ARE FOR THE SYSTEM OUT DOOR INDOOR Yellow sha...

Page 38: ...C35B 1 03 0 96 1 05 TM9E060B12MP11 FC MC PC43B 1 06 1 03 1 02 TM9E080B12MP11 FC MC PC35B 1 03 0 96 1 05 TM9E080B12MP11 FC MC PC43B 1 06 1 03 1 02 Furnace Coil MBH COP KW TM9E080C16MP11 FC MC PC35C 1 0...

Page 39: ...93 80 13 9 1 9 2 19 14 5 2 0 2 15 15 1 2 1 2 10 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED KW VALUES ARE FOR THE SYSTEM OUT DOOR INDOOR Yellow shaded cells are AHRI High Heatin...

Page 40: ...C MC PC35B 0 94 0 94 1 01 TM9E080B12MP11 FC MC PC43B 0 95 0 96 1 00 TM9E080C16MP11 FC MC PC35C 0 94 0 96 0 99 TM9E080C16MP11 FC MC PC43C 0 96 0 99 0 97 Furnace Coil MBH COP KW TM9E100C16MP11 FC MC PC3...

Page 41: ...2 11 2 36 80 15 0 1 95 2 26 15 1 1 90 2 33 15 2 1 85 2 40 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED KW VALUES ARE FOR THE SYSTEM OUT DOOR INDOOR Yellow shaded cells are AHRI Hi...

Page 42: ...C MC PC48C 1 00 1 04 0 96 TM9E080C16MP11 FC MC PC48D 1 00 1 04 0 96 TM9E100C16MP11 FC MC PC43C 0 99 1 03 0 96 TM9E100C16MP11 FC MC PC48C 1 00 1 04 0 96 Furnace Coil MBH COP KW TM9E100C16MP11 FC MC PC4...

Page 43: ...4 70 22 9 2 2 3 05 23 4 2 2 3 07 24 0 2 3 3 09 80 22 4 2 0 3 31 22 6 2 0 3 32 22 8 2 0 3 33 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED KW VALUES ARE FOR THE SYSTEM OUT DOOR INDO...

Page 44: ...C MC PC48D 0 96 1 03 0 96 TM9E100C16MP11 FC MC PC48C 0 96 1 03 0 96 TM9E100C16MP11 FC MC PC48D 0 96 1 03 0 96 TM9E100C20MP11 FC MC PC48C 0 96 1 06 0 93 Furnace Coil MBH COP KW TM9E100C20MP11 FC MC PC4...

Page 45: ...2 3 57 26 8 2 2 3 57 70 25 2 1 9 3 89 24 8 2 0 3 63 24 3 2 0 3 56 80 23 6 1 8 3 84 22 8 1 8 3 71 21 9 1 8 3 56 NOTE ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED KW VALUES ARE FOR THE S...

Page 46: ...MP11 FC PC60C 1 02 1 12 0 91 TM9E100C16MP11 FC MC PC60D 1 02 1 12 0 91 TM9E100C16MP11 FC MC62D 1 00 1 14 0 90 TM9E100C16MP11 FC PC60C 1 02 1 12 0 91 Furnace Coil MBH COP KW TM9E100C20MP11 FC MC PC60D...

Page 47: ...ning the performance with other indoor sections Some of the combinations shown in these multiplier tables are not valid for use in the U S A Please see the Capacity Tables in the front of this Technic...

Page 48: ...13 00 11 00 YHJD30S41S7 FC MC PC35 17 5 21 0 800 1200 1000 29 4 22 0 13 00 11 00 YHJD30S41S7 FC MC PC37 14 5 800 1200 1000 29 4 22 4 13 00 11 00 YHJD30S41S7 FC MC PC43 17 5 21 0 800 1200 1000 29 4 22...

Page 49: ...2 6 13 25 11 50 YHJD30S41S7 TM9E100C20MP11 21 0 FC MC PC35C 1000 29 8 21 6 13 25 11 50 YHJD30S41S7 TM9E100C20MP11 21 0 FC MC PC43C 1000 30 0 22 4 13 75 11 50 YHJD30S41S7 TMLX060A12MP11 14 5 FC MC PC37...

Page 50: ...P11 24 5 FC MC PC60D 1325 46 0 33 2 13 50 11 50 YHJD48S41S7 TMLX080C16MP11 21 0 FC MC PC60D 1375 46 0 34 0 13 75 11 75 YHJD48S41S7 TMLX080C16MP11 21 0 FC PC60C 1350 46 0 33 0 13 75 11 75 YHJD48S41S7 T...

Page 51: ...0 YHJD36S41S7 FC MC PC37 35 4 3 70 2 80 18 7 2 42 2 26 7 70 YHJD36S41S7 FC MC PC43 35 4 3 70 2 80 18 7 2 42 2 26 7 70 YHJD36S41S7 FC MC PC48 35 4 3 70 2 80 18 7 2 42 2 26 7 70 YHJD42S41S7 FC MC PC48 3...

Page 52: ...3 2 20 1 90 8 00 YHJD30S41S7 TM9E100C20MP11 FC MC PC35C 28 6 3 70 2 26 13 9 2 20 1 85 8 00 YHJD30S41S7 TM9E100C20MP11 FC MC PC43C 29 0 3 80 2 24 14 2 2 24 1 86 8 00 YHJD30S41S7 TMLX060A12MP11 FC MC P...

Page 53: ...00 YHJD48S41S7 TMLX100C16MP11 FC MC PC60D 46 0 3 60 3 74 24 4 2 40 2 98 8 00 YHJD48S41S7 TMLX100C16MP11 FC PC60C 46 0 3 60 3 74 24 4 2 40 2 98 8 00 YHJD48S41S7 TMLX100C20MP11 FC PC60C 46 0 3 60 3 74 2...

Page 54: ...to change without notice Published in U S A Copyright 2015 by Johnson Controls Inc All rights reserved 571209 YTG F 0615 Supersedes 571209 YTG E 0315 York International Corp 5005 York Drive Norman OK...

Reviews: