background image

13

DE - COMMISSIONING DISMANTLING & DISPOSAL

This product contains refrigerant under pressure, rotating parts, and electrical connections which

may be a danger and cause injury!

All work must only be carried out by competent persons using suitable protective clothing and safety precautions.

1. Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure that all points of electrical and gas

isolation are secured in the OFF position. The supply cables and gas pipework may then be disconnected and removed. For points of connection refer
to unit installation instructions.

2. Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then be

re-used, if appropriate, or returned to the manufacturer for disposal.

Under No circumstances should refrigerant be vented to atmosphere.

Where

appropriate, drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing
disposal of oily wastes.

3. Packaged unit can generally be removed in one piece after disconnection as above. Any fixing down bolts should be removed and then unit lifted from

position using the points provided and equipment of adequate lifting capacity. Reference MUST be made to the unit installation instructions for unit
weight and correct methods of lifting. Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above.

4. After removal from position the unit parts may be disposed of according to local laws and regulations.

d

e

ll

o

r

t

n

o

c

y

l

e

t

o

m

e

r

s

i

t

i

n

U

k

c

o

h

s

c

i

r

t

c

e

l

e

f

o

k

s

i

R

l

a

u

n

a

M

e

h

t

d

a

e

R

and may start without warning

ENGLISH

E-II-YDDN-0907

Summary of Contents for YDDN-22C(A/B)15A

Page 1: ...equipment Users should not install the air conditioner by themselves All pictures are only sketches If there is any difference between pictures in this manual and the actual shape of the air conditio...

Page 2: ...8 8 1 8 8 13 8 1 3 5...

Page 3: ...8 A 1 3 0 8 899 B 19 8 899...

Page 4: ...89 8 C 1 3 A D B 56E69...

Page 5: ...8 1 FG BH 0 8 1 A 5 299 B A 646...

Page 6: ...oad the inner frame Slide the knob release the buckle from the outside frame hole then unload the inner frame 2 Hang the outside frame on the main body with face down 4 places at 4 corners Note The si...

Page 7: ...ody and the outside frame with the x board of waist shape hole in two places Waist shaped hole xed board O utside frame Hook O utside frame Air inlet Inner frame Duct Tighten the other side of the boa...

Page 8: ...3 4 597 A A 819 B...

Page 9: ...15A M YDDN 22 140C A B 15A 15A 2 Indoor unit power supply The indoor unit power source should not be shared with the outdoor unit The indoor units that connect to the same outdoor unit should use the...

Page 10: ...11 B B 8 8 8 1 8 1 1 B 9 8 1 3 5 6 4 7 2 1199 9 2 85999 6 9 88199 5 9 999 3 1 2999 3 9 7899 1 6 6499 1 9 5699 8 6 3499 8 1 1299 8 9 53 5 55 9 9 9 86 84...

Page 11: ...la shes at 2 5Hz Condenser sensor check point is abnormal or outdoor temp sensor is abnormal Allthe indoor alarm lamps flash at 0 5Hz After the malfunctions disa ppea r it res tores automatically If t...

Page 12: ...or returned to the manufacturer for disposal Under No circumstances should refrigerant be vented to atmosphere Where appropriate drain the refrigerant oil from each system into a suitable container a...

Reviews: