FORM 150.75-NM2
63
YORK INTERNATIONAL
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SAFETY SHUTDOWN NUMBER 1
SHUTDOWN @ 5:18AM 1/02/97
CHILLER FAULT:
LOW AMBIENT TEMPERATURE SHUTDOWN
RETURN WATER TEMP 1
82.7 DEGF
RETURN WATER TEMP 2
83.7 DEGF
LEAVING WATER TEMP 1
60.1 DEGF
LEAVING WATER TEMP 2
73.5 DEGF
MIXED WATER TEMP
49.3 DEGF
LOW WATER CUTOUT
36.0 DEGF
SETPOINT TEMP
44.0 DEGF
OUTSIDE AIR TEMP
24.8 DEGF
LOW AMBIENT CUTOUT
25.0 DEGF
LOW PRESSURE CUTOUT
44 PSIG
LEAD SYSTEM
SYS 1
CONTROL TYPE
LCHWT
COOLING RANGE
44.0 TO 46.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
30 %FLA
SUCTION PRESSURE
46 PSIG
DISCHARGE PRESSURE
312 PSIG
OIL PRESSURE
92
PSID
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
STAGES OF LOADING
4
FORWARD FANS
1
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
65 %FLA
SUCTION PRESSURE
68 PSIG
DISCHARGE PRESSURE
334 PSIG
OIL PRESSURE
72
PSID
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
STAGES OF LOADING
4
FORWARD FANS
1
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 3 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
22 %FLA
SUCTION PRESSURE
59 PSIG
DISCHARGE PRESSURE
291 PSIG
OIL PRESSURE
95
PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
OFF
REVERSE FANS
OFF
SYSTEM 4 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
30 %FLA
SUCTION PRESSURE
623 PSIG
DISCHARGE PRESSURE
327 PSIG
OIL PRESSURE
83
PSID
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
STAGES OF LOADING
4
FORWARD FANS
2
REVERSE FANS
OFF
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SAFETY SHUTDOWN NUMBER 2
SHUTDOWN @ 4:58AM 1/02/97
SYS 1
LOW SUCTION PRESS SHUTDOWN
SYS 2
NO FAULTS
SYS 3
NO FAULTS
SYS 4
NO FAULTS
RETURN WATER TEMP 1
82.8 DEGF
RETURN WATER TEMP 2
83.6 DEGF
LEAVING WATER TEMP 1
60.1 DEGF
LEAVING WATER TEMP 2
73.5 DEGF
MIXED WATER TEMP
49.5 DEGF
LOW WATER CUTOUT
36.0 DEGF
SETPOINT TEMP
44.0 DEGF
OUTSIDE AIR TEMP
60.4 DEGF
LOW AMBIENT CUTOUT
25.0 DEGF
LOW PRESSURE CUTOUT
44 PSIG
LEAD SYSTEM
SYS 1
CONTROL TYPE
LCHWT
COOLING RANGE
44.0 TO 46.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
30 %FLA
SUCTION PRESSURE
21 PSIG
DISCHARGE PRESSURE
313 PSIG
OIL PRESSURE
117
PSID
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
STAGES OF LOADING
4
FORWARD FANS
2
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
65 %FLA
SUCTION PRESSURE
68 PSIG
DISCHARGE PRESSURE
334 PSIG
OIL PRESSURE
72
PSID
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
STAGES OF LOADING
4
FORWARD FANS
2
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 3 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
21 %FLA
SUCTION PRESSURE
59 PSIG
DISCHARGE PRESSURE
291 PSIG
OIL PRESSURE
95
PSID
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
STAGES OF LOADING
4
FORWARD FANS
2
REVERSE FANS
OFF
SYSTEM 4 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
30 %FLA
SUCTION PRESSURE
62 PSIG
DISCHARGE PRESSURE
353 PSIG
OIL PRESSURE
83
PSID
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
STAGES OF LOADING
4
FORWARD FANS
2
REVERSE FANS
OFF
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SAFETY SHUTDOWN NUMBER 2
SHUTDOWN @ 5:03AM 1/02/97
CHILLER FAULT:
115VAC UNDER VOLTAGE SHUTDOWN
RETURN WATER TEMP 1
82.8 DEGF
RETURN WATER TEMP 2
83.6 DEGF
LEAVING WATER TEMP 1
60.1 DEGF
LEAVING WATER TEMP 2
73.5 DEGF
MIXED WATER TEMP
49.5 DEGF
LOW WATER CUTOUT
36.0 DEGF
SETPOINT TEMP
44.0 DEGF
OUTSIDE AIR TEMP
60.4 DEGF
LOW AMBIENT CUTOUT
25.0 DEGF
LOW PRESSURE CUTOUT
44 PSIG
LEAD SYSTEM
SYS 1
CONTROL TYPE
LCHWT
COOLING RANGE
44.0 TO 46.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
30 %FLA
SUCTION PRESSURE
45 PSIG
DISCHARGE PRESSURE
312 PSIG
OIL PRESSURE
93
PSID
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
STAGES OF LOADING
4
FORWARD FANS
2
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
65 %FLA
SUCTION PRESSURE
68 PSIG
DISCHARGE PRESSURE
334 PSIG
OIL PRESSURE
72
PSID
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
STAGES OF LOADING
4
FORWARD FANS
2
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 3 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
21 %FLA
SUCTION PRESSURE
59 PSIG
DISCHARGE PRESSURE
291 PSIG
OIL PRESSURE
95
PSID
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
STAGES OF LOADING
4
FORWARD FANS
2
REVERSE FANS
OFF
SYSTEM 4 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
30 %FLA
SUCTION PRESSURE
62 PSIG
DISCHARGE PRESSURE
353 PSIG
OIL PRESSURE
83
PSID
LIQUID LINE SOLENOID
ON
RUN PERMISSIVE
ON
STAGES OF LOADING
4
FORWARD FANS
2
REVERSE FANS
OFF
NOTE:
In actual print-outs, this would be one continuous print-out.
FIG. 30
HISTORY PRINT OUT
ý
ý