background image

5012886-YIM-B-0517

18

Johnson Controls Unitary Products

2.

Move the system switch on the thermostat to the AUTO or 
COOL position.

3.

Reduce the setting of the room thermostat to energize the 
compressor.

4.

Check the operation of the evaporator unit per the 
manufacturer’s recommendations.

5.

With an ammeter, check the compressor amps against the 
unit data plate.

6.

Check for refrigerant leaks.

7.

Check for any abnormal noises and/or vibrations, and 
make the necessary adjustments to correct fan blade(s) 
touching shroud, refrigerant lines hitting on sheet metal, 
etc.

8.

After the unit has been operating for several minutes, shut 
off the main power supply at the disconnect switch and 
inspect all factory wiring connections and bolted surfaces 
for tightness.

Operation

Unit Control Overview

This series of condenser units, comes factory equipped with 
Smart Equipment™ controls to monitor all unit functionality and 
safety controls. (2 Smart Equipment™ controls per system on 
30, 40 and 50 Ton condensers.)

Safety Controls

The Smart Equipment™ control board incorporates features to 
monitor safety circuits as well as minimize compressor wear 
and damage. An anti-short cycle delay (ASCD) is utilized to 
prevent operation of a compressor too soon after its previous 
run. Additionally, a minimum run time is imposed any time a 
compressor is energized to allow proper oil return to the 
compressor. The ASCD is initiated on unit start-up and on any 
compressor reset or lockout.

The Smart Equipment™ control board monitors the following 
inputs for each cooling system:

• A high-pressure switch is factory installed to protect 

against excessive discharge pressure due to a blocked 
condenser coil or a condenser fan motor failure. During 
cooling operation, if a high-pressure limit switch opens, 
the Smart Equipment™ control board will de-energize the 
associated compressors and initiate the 5-minute ASCD. 
If the call for cool is still present at the end of the ASCD, 
the control board will re-energize the halted compressor. If 
a high-pressure switch opens three times within two hours 
of operation, the Smart Equipment™ control board will 
lock out the associated system compressors and will 
display the fault on the on board LCD display.

• A low-pressure switch to protect the unit against 

excessively low suction pressure is standard on all 
condensing units. If the low-pressure switch opens during 
normal operation, the Smart Equipment™

 

control board 

will de-energize the compressor, initiate the ASCD, and 
shut down the condenser fans. On startup, if the low-

pressure switch opens, the Smart Equipment™ control 
board will monitor the low-pressure switch to make sure it 
closes within one minute. If it fails to close, the unit will 
shut down the associated compressor and begin an 
ASCD. If the call for cool is still present at the end of the 
anti-short cycle time delaying, the control board will re-
energize the halted compressor. If a low-pressure switch 
opens three times within two hours of operation, the 
Smart Equipment™ control board will lock out the 
associated system compressors and will display the fault 
on the on board LCD display.

• An ambient air sensor will lock out mechanical cooling at 

40

F. A field installed low ambient kit is available that 

allows the unit to operate down to 0°F.

The refrigerant systems are independently monitored and 
controlled. On any fault, only the associated system will be 
affected by any safety/preventive action. The other refrigerant 
system will continue to operate unless it is affected by the fault 
as well.

Pump Out

The "Pump-Out on Start-Up" function is a standard feature on 
the 30-50 ton matched split systems. These systems have dual 
circuit indoor evaporator refrigerant circuits. Each circuit 
includes 2 TXVs and 2 normally closed solenoid valves that are 
utilized for the "Pump-Out on Start-Up" sequence of operation. 
The pump-out sequence is designed to prevent liquid 
refrigerant flooding of the compressors during startup.

The pump-out circuit is activated each time the 

first stage

 (Y1 

of UCB 1) and/ or 

third stage

 (Y1 of UCB 2) compressors are 

called for from the thermostat. On initial startup, the pump-out 
circuitry does not allow the 

1LLS

 (Pump-Out Solenoid System 

1) or 

3LLS

 (Pump-Out Solenoid System 2) located in the liquid 

line just ahead of the TXVs to open, thus not allowing 
refrigerant flow, or liquid refrigerant to enter the evaporator 
during startup. 

The 

1LLS

 or 

3LLS

 remains closed and will not allow refrigerant 

flow through the system until the active refrigerant circuit's low 
pressure switch (

LPS

 1 on UCB 1) or (

LPS

 1 on UCB 2) opens. 

Once the low pressure switch opens or (5 minutes elapses), the 
SE board(s) energizes the 

PR1

 (Pump-Out Relay System 1) or 

PR2

 (Pump-Out Relay System 2), which then opens the 1LLS 

or 3LLS (Pump-Out Solenoids) and allows refrigerant to begin 
flowing through the active refrigerant circuit. The active 
systems' low pressure switch is ignored for approximately 1 
minute while the systems suction pressure rises above its cut in 
point of 71 psi. at which point the LPS closes again for normal 
operation and LPS function. The UCB - “CN-Fan” output 
controls the pump out relay function. “Pump Out” function is 
also possible with “Lead-Lag” enabled. Lead lag function should 
be turned off anytime Hot Gas Bypass (HGBP) is installed.

Sequence of Operation

NOTE: 

The timing intervals described in the following 
procedures are nominal. Some variations will naturally 
occur due to differences in individual components, or 
due to variations in ambient temperature or line/control 

Summary of Contents for YD480 Series

Page 1: ...Unit 9 6 Unit Dimensions Inches 14 7 Piping And Electrical Connection Sizes 30 40 50T Inches 16 8 Electrical Power Knockout Sizes Inches 16 9 Smart Equipment UCB Details 23 LIST OF FIGURES 1 Corner We...

Page 2: ...50 Ton C00 Cooling Only Product Options AA None TA Technicoat Condenser Coil Installation Options A None 2 208 230 3 60 4 460 3 60 5 575 3 60 Configured Split Condenser Model Number Nomenclature A St...

Page 3: ...n the carrier s freight bill A separate request for inspection by the carrier s agent should be made in writing Improper installation may create a condition where the operation of the product could ca...

Page 4: ...em Scroll Tandem Scroll Quantity 2 2 2 Cooling Nominal Capacity Tons System 1 15 20 25 System 2 15 20 25 Capacity Stages System 1 2 2 2 System 2 2 2 2 SYSTEM DATA No Refrigeration Circuits 2 2 2 Sucti...

Page 5: ...ngth to support the unit The condensing unit must be mounted on level supports The supports can be channel iron beams or wooden beams treated to reduce deterioration Minimums of two 2 beams are requir...

Page 6: ...on of vibration Holes are provided in the base rails for bolting the unit to its foundation For ground level installations precautions should be taken to protect the unit from tampering and unauthoriz...

Page 7: ...of the unit When preparing to move the unit always determine the center of gravity see Table 3 and Figure 1 of the unit in order to equally distribute the weight Slings connected to the compressor end...

Page 8: ...to compressor replacement repairing refrigerant leaks replacing refrigerant components such as filter drier pressure switch metering device or coil Units are shipped with compressor mountings which ar...

Page 9: ...3 60 1 1 2 4 2 9 63 5 70 575 3 60 4 9 0 14 78 575 3 60 1 1 2 4 2 2 47 1 50 YD480 208 230 3 60 4 30 1 47 225 208 230 3 60 1 1 2 4 5 8 151 1 175 460 3 60 4 16 7 26 114 460 3 60 1 1 2 4 2 9 82 6 90 575 3...

Page 10: ...emperatures must also be insulated Never solder suction and liquid lines together They can be taped together for convenience and support purposes but they must be completely insulated from each other...

Page 11: ...ctions of the main lines Connect the main liquid line to the liquid line connection on the evaporator unit while maintaining a flow of nitrogen Make the suction line connection at the evaporator and r...

Page 12: ...Line Solenoid Wiring NOTE For applications on airhandlers evaporator DX coils other than ND360 600 certified matchups liquid line solenoids may be required for proper operation and refrigerant system...

Page 13: ...On non ND models isolation relays must be installed to avoid overloading on 75 VA transformer on condensing unit Non ND units may not include any or all of the components required to wire the unit Use...

Page 14: ...4 Johnson Controls Unitary Products Figure 6 YD Unit Dimensions Table 6 Unit Dimensions Inches MODEL A B C D E F G H YD360 128 5 88 5 37 5 41 8 40 0 46 1 37 1 23 6 YD480 128 5 88 5 57 7 41 8 40 0 46 1...

Page 15: ...183 2 313 88 140 22 358 20 858 19 358 37 518 12 878 9 628 5012886 YIM B 0517 Johnson Controls Unitary Products 15 Figure 7 30 Ton Power And Control Wiring Connections Figure 8 40 50 Ton Power And Cont...

Page 16: ...NTRY SIZE SUCTION LINE SYS 1 1 5 8 OD LIQUID LINE SYS 1 7 8 OD SUCTION LINE SYS 2 1 5 8 OD LIQUID LINE SYS 2 7 8 OD POWER WIRING KNOCKOUT SEE TABLE 8 CONTROL WIRING 7 8 HOLE Table 8 Electrical Power K...

Page 17: ...ent clearances been provided 2 Has all foreign matter been removed from the interior of the unit tools construction or shipping materials etc 3 Have the condenser fans been rotated manually to check f...

Page 18: ...minute If it fails to close the unit will shut down the associated compressor and begin an ASCD If the call for cool is still present at the end of the anti short cycle time delaying the control boar...

Page 19: ...of System 2 When the LPS of UCB 2 falls below its cut out point the PR2 relay brings on the 3LLS Solenoid allowing refrigerant in system 2 to return flow to the compressor for normal mechanical coolin...

Page 20: ...enance consists of changing or cleaning filters and general cleaning of the outdoor coil MOTORS Outdoor fan motors are permanently lubricated and require no maintenance OUTDOOR COIL Dirt should not be...

Page 21: ...cursor is on the top Status line hit the ENTER button This action steps the LCD display into the status mode Hit ENTER to view the status menu Press Enter Step 2 Scroll down to DVent Mode This is the...

Page 22: ...CANCEL JOY C PWR 7 7 77 Clg Engaged LeadLag Engaged Press Enter Joy Stick Down 2 Step 6 By toggling down twice the screen reaches the ClgOcc SP screen or Cooling Occupied Set Point ENTER CANCEL JOY C...

Page 23: ...mostat connection strip C and indoor blower VFD pin C 24V 24 VAC 75 VA transformer hot Powers the UCB microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for facto...

Page 24: ...hing in series Unit wiring harness jumper plug for factory shutdown accessories must be removed if the switching of field added external accessories for unit shutdown are wired between thermo stat con...

Page 25: ...ut from 10K 77 F Type III negative temperature coefficient thermistor Input required for 2 compressor heat pump units not required for 2 compressor A C units not active for 1 compressor units 3 625 VD...

Page 26: ...no input within 5 minutes from initiation of H1 output initiates an Ignition Failure alarm input for longer than 5 minutes without H1 output initiates a Gas Valve Mis wire alarm Pin Cooling and fan o...

Page 27: ...put is needed input must be present to allow FAN output and unit operation One FAN OVR trip lasting longer than 5 minutes or three FAN OVR trips in a two hour period cause a Fan Overload Lockout and u...

Page 28: ...munication circuit COM Common for the FC Field Connected BUS BACnet MSTP communication circuit Negative of the VDC FC bus BACnet MSTP communication circuit SHLD Shield for the FC Field Connected BUS B...

Page 29: ...with the TXV s left to the factory setting If the TXV s have been adjusted in the field the charging chart may no longer apply Outdoor Air Entering Condenser F 300 350 400 450 500 550 600 120 130 140...

Page 30: ...scharge Pressure psi Suction Pressure psi Charging Curves 50 Ton 115 105 95 85 65 1 Make sure that all condenser fans are running when charging 2 This chart is applicable to unit with the TXV s left t...

Page 31: ...5012886 YIM B 0517 Johnson Controls Unitary Products 31 Typical Wiring Diagrams Figure 17 Typical 208 230 Volt YD360 480 600 Condensing Unit Wiring Diagram...

Page 32: ...5012886 YIM B 0517 32 Johnson Controls Unitary Products Typical Wiring Diagrams Figure 18 Typical 460 575 Volt YD360 480 600 Condensing Unit Wiring Diagram...

Page 33: ...ocedures are followed and checks are made at initial start up This confidence is supported by the 30 day dealer protection coverage portion of our standard warranty policy which states that Johnson Co...

Page 34: ...he equipment If the system is a VAV system the CFM will be the airflow when the remote VAV boxes are in the full open position and the frequency drive is operating at 60 HZ Do not proceed with the equ...

Page 35: ...ystem 2 Is Condenser below Evaporator Yes No Yes No Total Line Length end to end _______ Ft _______ Ft Vertical Lift in Ft _______ Ft _______ Ft Vertical Fall in Ft _______ Ft _______ Ft Number of Elb...

Page 36: ...t or change required to obtain the correct airflow Was it necessary to increase of decrease the airflow to meet the design conditions If the motor pulley size was changed measure the outside diameters...

Page 37: ...hird if equipped Fourth if equipped Heat Pump 1st Stage Outside air temperature ________________ db F ________________ wb F ________________ RH Return Air Temperature ________________ db F ___________...

Page 38: ..._______________________________ ________________________________________________________________________________________________________ _______________________________________________________________...

Reviews: