Table 43: Programmable
Button
Access level
Description
Shutdown
(enabled/
disabled)
Operator
Allows the user to select whether the chiller will shutdown or continue to run when an
Excess Surge situation has been detected.
If this setpoint is Enabled and the EXTENDED RUN setpoint is Disabled, a safety
shutdown is performed when the SURGE WINDOW COUNT exceeds the COUNT LIMIT
setpoint.
If this setpoint is Enabled and the EXTENDED RUN setpoint is Enabled, a safety
shutdown is performed if the SURGE WINDOW COUNT exceeds the COUNT LIMIT
setpoint at the completion of the 10 minute Extended Run period.
“Surge Protection – Excess Surge” is displayed with either shutdown.
If this setpoint is Disabled, refer to operation in
Extended run
(enabled/
disabled)
Operator
Allows the user to select the surge correction/avoidance EXTENDED RUN mode.
This will be implemented when an Excess surge situation is detected as follows:
Anytime the SURGE WINDOW COUNT exceeds the COUNT LIMIT, the Pre-rotation
vanes are driven closed for the next 10 minutes. While this load inhibit is in effect,
“Warning – Surge Protection – Excess Surge Limit’ is displayed. When 10 minutes have
elapsed, the warning message and load inhibit are automatically cleared, provided the
SURGE WINDOW COUNT is less than or equal to the COUNT LIMIT. If the SHUTDOWN
setpoint is Enabled, and the SURGE WINDOW COUNT exceeds the COUNT LIMIT at the
completion of this period, a safety shutdown is performed and “Surge Protection –
Excess Surge” is displayed.
If the Hot Gas Bypass control is Enabled, the Hot gas Bypass Valve position must be
100% before the Extended Run mode is implemented.
Count window
Operator
Allows the user to define the period of time (1 to 5 minutes; default 3) in which the
number of surge events (SURGE WINDOW COUNT) are compared to the maximum
allowed (COUNT LIMIT), for the purpose of detecting an excess surge situation.
Count limit
Operator
Allows the user to define the maximum number of surge events (4 to 20; default 15)
that can occur within a defined period of time before an Excess Surge situation is
detected. If the SURGE WINDOW COUNT exceeds the COUNT LIMIT, an Excess Surge
situation has occurred.
When an Excess Surge is detected, the action depends upon the situation:
•
If both the SHUTDOWN and EXTENDED RUN setpoints are Disabled, the chiller
will continue to run, displaying the message “Warning – Excess Surge detected”.
•
If the SHUTDOWN setpoint is Enabled and the EXTENDED RUN setpoint
is Disabled, the chiller will perform a safety shutdown and display “Surge
Protection – Excess Surge”.
•
If the SHUTDOWN setpoint is Disabled and the EXTENDED RUN setpoint is
Enabled, the Pre-rotation Vanes are driven closed for 10 minutes and “Warning
– Surge Protection – Excess Surge Limit” is displayed. When the 10 minutes
have elapsed, if the SURGE WINDOW COUNT is less than or equal to the COUNT
LIMIT, this message and load inhibit are automatically cleared. Alternating with
this message is “Warning – Excess Surge Detected” that continues after the 10
minute period has elapsed until manually cleared with the Warning Reset key.
•
If both the SHUTDOWN and EXTENDED RUN setpoint are Enabled, the 10 minute
Extended RUN mode is invoked as described above. However, if the SURGE
WINDOW COUNT exceeds the COUNT LIMIT at the completion of the 10 minute
extended run period, a safety shutdown is performed and “Surge Protection –
Excess Surge” is displayed.
Surge sensitivity Service
Allows the user to define the surge detection sensitivity. Selectable over the range of
0.3 to 1.3; default 0.3. The smaller the number, the greater the sensitivity.
Clear surge count Admin
Allows user to set the Single Compressor Total Surge Count to zero.
Model YD Mod D with OptiView Control Center
58
Summary of Contents for YD Mod D
Page 2: ...2 Model YD Mod D with OptiView Control Center...
Page 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Page 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Page 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Page 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Page 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Page 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Page 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Page 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Page 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Page 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Page 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Page 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Page 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Page 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Page 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Page 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...