FORM 150.26-EG1 (116)
JOHNSON CONTROLS
15
Design Parameters
DESIGN PARAMETERS - STANDARD EFFICIENCY (SE)
YCWL
MODEL
EVAPORATOR
FLOW GPM (L/S)
CONDENSER
FLOW GPM (L/S)
LEAVING EVAP.
WATER TEMP.
°F (°C)
ENT. COND.
WATER TEMP.
°F (°C)
LVG. COND.
WATER TEMP.
°F (°C)
EQUIPMENT
ROOM TEMP
°F (°C)
MIN MAX
MIN
MAX MIN1 MAX2
MIN
MAX
MIN
MAX
0056SE
60
(3.8)
285
(18)
90
(5.7)
360
(22.7)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0064SE
60
(3.8)
285
(18)
90
(5.7)
360
(22.7)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0074SE
60
(3.8)
285
(18)
90
(5.7)
360
(22.7)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0084SE
60
(3.8)
285
(18)
145
(9.1)
450
(28.4)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0094SE
100
(6.3)
355
(22.4)
145
(9.1)
450
(28.4)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0104SE
100
(6.3)
385
(24.3)
145
(9.1)
450
(28.4)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0118SE
100
(6.3)
385
(24.3)
145
(9.1)
450
(28.4)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0132SE
140
(8.8)
625
(39.4)
180
(11.4)
700
(44.2)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0157SE
150
(9.5)
625
(39.4)
225
(14.2)
700
(44.2)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0177SE
200
(12.6)
650
(41)
260
(16.4)
700
(44.2)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0198SE
200
(12.6)
650
(41)
260
(16.4)
700
(44.2)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
DESIGN PARAMETERS - HIGH EFFICIENCY (HE)
YCWL
MODEL
EVAPORATOR
FLOW GPM (L/S)
CONDENSER
FLOW GPM (L/S)
LEAVING EVAP.
WATER TEMP.
°F (°C)
ENT. COND.
WATER TEMP.
°F (°C)
LVG. COND.
WATER TEMP.
°F (°C)
EQUIPMENT
ROOM TEMP
°F (°C)
MIN MAX
MIN
MAX MIN1 MAX2
MIN
MAX
MIN
MAX
0064HE
100
(6.3)
355
(22.4)
145
(9.1)
450
(28.4)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0074HE
140
(8.8)
625
(39.4)
145
(9.1)
450
(28.4)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0084HE
140
(8.8)
625
(39.4)
145
(9.1)
450
(28.4)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0094HE
140
(8.8)
625
(39.4)
225
(14.2)
700
(44.2)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0096HE
150
(9.5)
625
(39.4)
225
(14.2)
700
(44.2)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0118HE
140
(8.8)
625
(39.4)
225
(14.2)
700
(44.2)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0127HE
200
(12.6)
650
(41)
225
(14.2)
700
(44.2)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
0157HE
200
(12.6)
650
(41)
260
(16.4)
700
(44.2)
40
(4.4)
50
(10)
65
(18)
130
(54)
40
(4.4)
115
(46)
NOTES
:
1. For leaving temperature below 40°F (4.4°C), optional brine chilling kit required. Minimum with kit is 15°F (-9.4°C).
2.
For leaving water temperature higher than 50°F (10°C), contact the nearest Johnson Controls Office for application guidelines.
Summary of Contents for YCWL 0056SE
Page 4: ...JOHNSON CONTROLS FORM 150 26 EG1 116 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 43: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 43 Unit Dimensions Four Compressor Cont d ...
Page 45: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 45 Unit Dimensions Five Six Compressor Cont d ...
Page 47: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 47 Unit Dimensions SI Four Compressor Cont d ...
Page 49: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 49 Unit Dimensions SI Five Six Compressor Cont d ...