FORM 150.26-EG1 (116)
JOHNSON CONTROLS
29
NOTES:
1. KWo = Unit kW Cooling Capacity Output
2. KWi = Compressor kW Input
3. KW = Condenser Heat Rejection
4. COP = Coefficient of Performance
5. LCWT = Leaving Chilled Water Temperature
6. Ratings based on 0.047 l/s cooler water per kW.
MODEL: YCWL0127HE
IPLV= 24.8
ENTERING CONDENSER WATER TEMPERATURE (°F)
LCWT
(°F)
75.0
85.0
95.0
TONS
KW
MBH
EER
TONS
KW
MBH
EER
TONS
KW
MBH
EER
40.0
127.0
78.7
1792.0
19.4
119.5
91.7
1747.0
15.6
112.0
106.7
1708.0
12.6
42.0
131.8
78.3
1848.0
20.2
124.0
91.3
1800.0
16.3
116.2
106.2
1757.0
13.1
44.0
136.7
77.9
1906.0
21.1
128.7
90.8
1854.0
17.0
120.6
105.7
1808.0
13.7
46.0
141.8
77.5
1966.0
21.9
133.5
90.4
1910.0
17.7
125.1
105.2
1860.0
14.3
48.0
147.0
77.2
2027.0
22.9
138.4
89.9
1968.0
18.5
129.8
104.6
1914.0
14.9
50.0
152.4
76.8
2091.0
23.8
143.5
89.5
2027.0
19.2
134.6
104.2
1970.0
15.5
MODEL: YCWL0157HE
IPLV= 24.3
ENTERING CONDENSER WATER TEMPERATURE (°F)
LCWT
(°F)
75.0
85.0
95.0
TONS
KW
MBH
EER
TONS
KW
MBH
EER
TONS
KW
MBH
EER
40.0
146.9
90.5
2071.0
19.5
138.5
104.2
2017.0
15.9
129.8
120.2
1968.0
13.0
42.0
152.2
90.3
2135.0
20.2
143.6
103.9
2078.0
16.6
134.7
119.7
2025.0
13.5
44.0
157.8
90.1
2200.0
21.0
148.9
103.6
2140.0
17.2
139.8
119.3
2084.0
14.1
46.0
163.4
89.9
2267.0
21.8
154.3
103.3
2204.0
17.9
144.9
118.9
2145.0
14.6
48.0
169.2
89.7
2336.0
22.6
159.8
103.0
2269.0
18.6
150.2
118.5
2206.0
15.2
50.0
175.1
89.5
2406.0
23.5
165.5
102.7
2336.0
19.3
155.6
118.1
2270.0
15.8
Ratings - High Efficiency (Cont'd)
Summary of Contents for YCWL 0056SE
Page 4: ...JOHNSON CONTROLS FORM 150 26 EG1 116 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 43: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 43 Unit Dimensions Four Compressor Cont d ...
Page 45: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 45 Unit Dimensions Five Six Compressor Cont d ...
Page 47: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 47 Unit Dimensions SI Four Compressor Cont d ...
Page 49: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 49 Unit Dimensions SI Five Six Compressor Cont d ...