background image

JOHNSON CONTROLS

4

FORM 115.20-NOM6 (1106)

INSTALLATION

2.  Frame  around  the  perimeter  of  the  unit  as 

required for securing the drywall. 

See Table 1 

below for drywall openings.

3.  Mount the unit in its permanent location, making 

sure it is level to insure proper drainage and 

operation (two 1/2” holes have been provided 

on each end of the unit for securing the unit to 

the wall studs).

4.  After the drywall has been installed, recheck to 

make sure the unit’s front panel is flush with the 

exterior drywall surface. Shimming of the unit 

may be required to get a seal between the unit 

and panel.

FIG. 3 – CW-HW RECESSED WALL and CLOSET 

MOUNTING

VERTICAL 2X 4
WALL STUDS

CLOSET MOUNT:
BRACKET
PLACEMENT
FOR HANGING

MOUNT UNIT
FLUSH WITH
DRY WALL (1/2"
MIN. IN FRONT
OF WALL STUD)

LEAVE SUFFICIENT SPACE
FOR DRAIN PIPING 10" TO 12"
MIN. RECOMMENDED

ATTACH UNIT TO FRAMING

USING SIX SCREWS/NAILS

IN CABINET LOCATIONS

SHOWN

CROSS MEMBER - TOP &

BOTTOM (PLACE UPPER CROSS

MEMBER 3" ABOVE UC UNIT)

SUPPORT FRAMING

RECESSED WALL UNIT TOP VIEW

THERMOSTAT

WIRING

POWER SUPPLY

WIRING

WALL PANEL FRAME

HOT

WATER

OUTLET

HOT

WATER

INLET

DRY WALL

2 X 4 WALL
STUD

CW UNITS:
CHILLED WATER
CONNECTION

Note: Front edge of unit to
be flush with dry wall.

CROSS MEMBER
(ON EDGE)

2 X 4 WALL STUD

WALL PANEL FRAME

SCREW

DETAIL OF WALL PANEL FRAME INSTALLATION

DRY WALL

LD11695A

TABLE 1 - DRYWALL OPENINGS

MODEL NUMBER

DRYWALL CUTOUT DIM

HT x WD

3YWC

28 x 42

4YWC

28 x 50

6YWC

28 x 58

8YWC

28 x 66

10YWC

28 x 74

12YWC

28 x 82

5.  Install the wall panel to the front of the unit using 

the 1/4-20 x 1-1/2” long, painted, Phillips head 

screws (four on unit sizes 3, 4, 6 and 8; six on 

unit sizes 10 and 12) (1/4” cage nuts are located 

in the slotted front panel of the unit). 

6.  Remove the lower return air grille to get access 

to the filter.

7. 

See Fig. 2 for unit details and dimensions.

Hung on a Closet Wall

Unit can be mounted in a closet using the bracket 

support option 90PK3.

These brackets mount to the top, back of the cabinet. 

See Fig 3 for location.

The unit should be isolated from the wall to be sure 

sound is not transferred from the unit to the wall.

Platform Mounted in a Closet

Unit can be set on a platform (provided by others) in 

a closet.

Be sure to allow for sufficient space below the platform 

for drain piping.

Summary of Contents for YCW SERIES LD11554

Page 1: ...ance and or a possible hazardous safety condition to service personnel and occupants Company employees and or contractors are not authorized to waive this warning Notes 1 For proper operation control...

Page 2: ...ILLED WATER LINES 5 8 OD COPPER STUBOUTS HOT WATER RETURN HOT WATER SUPPLY FIG 1 UNIT NOMENCLATURE LD11557A LD11698A CABINET DIMENSIONS INCHES A B C D E F FILTER SIZE COIL CONN OD SWEAT HW CW YCW 22 1...

Page 3: ...provided with 2 coils with single end sheets cooling connections are on the top panel right side and the hot water connec tions are on the top panel middle front This unit is designed to be installed...

Page 4: ...POWER SUPPLY WIRING WALL PANEL FRAME HOT WATER OUTLET HOT WATER INLET DRY WALL 2 X 4 WALL STUD CW UNITS CHILLED WATER CONNECTION Note Front edge of unit to be flush with dry wall CROSS MEMBER ON EDGE...

Page 5: ...tandard 120 volt power wired to a dis connect terminal block and a ground lug Fan motor hi med and low speed leads are wired to the control board There may be an unused motor lead from the motor its n...

Page 6: ...N A N A N A N A N A 2 2 1 5 9 4 8 3 12 11 15 15 3 3 2 3 13 6 11 9 17 15 20 15 4 4 3 0 17 8 15 5 23 20 25 20 5 5 3 8 21 9 19 1 28 24 30 25 6 6 4 5 26 1 22 7 33 29 35 30 8CWE 0 0 0 0 1 7 N A N A N A N A...

Page 7: ...eringtobronzeorbrass heatthepiping while in the socket cup and begin introducing the solder when the ux boils rapidly Avoid direct ame into the solder joint Heat can only be applied to the cup of the...

Page 8: ...re exists at the drain pan and a minimum trap of 1 1 2 must be provided in the drain line to assure proper drainage Drain connections primary and secondary are 3 4 MPT see Fig 5 for details On units w...

Page 9: ...O thermostat and the TB3 3 TB2 5 jumper is in place the fan will con tinue to operate at the fan speed selected Removing the jumper will cause the fan to shut down when the thermostat is satis ed Whe...

Page 10: ...the air and heating capacities of the unit When the lters are excessively dirty the unit heating capacity will be so reduced that it is in effective for heating the room When a room fails to heat alw...

Page 11: ...11 JOHNSON CONTROLS FORM 115 20 NOM6 1106 This Page Intentionally Left Blank...

Page 12: ...sture from accumulating in the bearings See Form 50 20 NM3 Long Term Storage Installer has cleaned out interior Ensure drain pan free from foreign material Ensure air lters are clean installed properl...

Reviews: