5495504-YTG-B-0518
44
Johnson Controls Unitary Products
PERFORMANCE DATA - 2 TON
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °
F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
@ COMPRESSOR
Outdoor Ambient Temperature
55 °F
65 °F
75 °F
85 °F
95 °F
105 °F
115 °F
T (°F)
P (PSIG)
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
YCD24B21(H,S)
35
107
25.2
1.25
22.9
1.38
20.7
1.50
18.4
1.62
16.2
1.71
13.9
1.78
11.7
1.82
40
119
28.3
1.23
25.9
1.37
23.5
1.51
21.0
1.65
18.6
1.77
16.2
1.86
13.8
1.93
45
130
31.5
1.20
28.9
1.36
26.3
1.52
23.8
1.67
21.2
1.81
18.6
1.93
16.0
2.02
50
143
34.8
1.16
32.1
1.34
29.4
1.52
26.6
1.69
23.9
1.84
21.1
1.98
18.3
2.10
55
156
38.4
1.12
35.4
1.32
32.5
1.51
29.6
1.70
26.7
1.87
23.8
2.03
20.8
2.17
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°
F subcooling and 15°
F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°
F increase in subcooling.
b. Decrease capacity by 1% for each 2°
F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°
F.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
YCD24B21(H,S)
INDOOR COIL MODEL NO.
CF24AXA1
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
ID CFM
600
800
1000
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
55
T.C.
22.9
25.0
25.2
29.4
27.7
24.2
26.0
26.3
28.6
27.6
25.4
26.9
27.3
28.4
27.4
S.C.
22.0
19.2
15.0
22.6
13.6
23.2
21.3
17.9
19.4
14.2
24.2
23.3
20.8
19.3
14.9
KW
1.48
1.49
1.48
1.49
1.49
1.56
1.57
1.56
1.57
1.57
1.63
1.65
1.63
1.64
1.65
65
T.C.
22.1
23.8
24.5
27.0
27.1
23.8
25.1
25.6
27.3
27.2
25.5
26.2
26.8
27.6
27.4
S.C.
21.2
18.9
15.9
18.0
13.5
22.9
21.2
18.3
18.5
14.2
24.4
23.5
20.8
19.3
14.9
KW
1.61
1.63
1.62
1.63
1.63
1.69
1.71
1.69
1.71
1.71
1.77
1.79
1.77
1.79
1.79
75
T.C.
21.3
22.7
23.7
25.2
26.6
23.5
24.2
24.9
26.0
26.9
25.6
25.6
26.1
26.8
27.2
S.C.
20.6
18.6
16.8
16.4
13.4
22.5
21.0
18.8
17.9
14.2
24.3
23.4
20.7
19.4
14.9
KW
1.73
1.77
1.75
1.77
1.77
1.82
1.85
1.83
1.85
1.85
1.91
1.93
1.91
1.93
1.93
85
T.C.
20.1
20.8
22.1
23.9
25.5
22.1
22.5
22.9
24.8
25.8
24.0
24.2
23.7
25.7
26.2
S.C.
19.2
17.7
16.1
15.9
13.0
21.0
20.3
18.0
17.6
13.9
22.8
22.8
20.0
19.3
14.8
KW
1.86
1.88
1.87
1.91
1.93
1.96
1.97
1.96
2.00
2.01
2.05
2.06
2.05
2.08
2.09
95
T.C.
18.8
19.0
20.6
22.8
24.4
20.5
20.9
21.0
23.6
24.9
22.1
22.9
21.3
24.4
25.3
S.C.
17.8
16.9
15.3
15.5
12.6
19.6
19.6
17.2
17.4
13.7
21.3
22.2
19.2
19.3
14.8
KW
1.98
2.00
1.99
2.05
2.08
2.09
2.10
2.09
2.15
2.17
2.20
2.20
2.18
2.24
2.25
105
T.C.
17.5
16.7
17.8
20.4
22.7
19.0
18.5
18.4
21.3
23.0
20.6
20.4
19.0
22.3
23.4
S.C.
16.6
15.6
14.2
14.6
12.0
18.1
17.6
16.0
16.5
13.2
19.7
19.7
17.7
18.6
14.3
KW
2.10
2.11
2.10
2.17
2.22
2.22
2.22
2.20
2.27
2.31
2.34
2.32
2.30
2.36
2.41
115
T.C.
16.2
14.4
15.1
18.1
20.9
17.7
16.2
15.9
19.1
21.2
18.9
17.9
16.7
20.1
21.4
S.C.
15.3
14.1
13.2
13.6
11.5
16.6
15.6
14.7
15.8
12.7
18.0
17.2
16.3
17.9
13.8
KW
2.23
2.21
2.20
2.29
2.36
2.35
2.33
2.31
2.39
2.46
2.48
2.45
2.41
2.49
2.57
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.