YORK INTERNATIONAL
10
FORM 201.19-W2 (304)
ELECTRICAL DATA (CONT'D)
OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION
AND INDIVIDUAL SYSTEM CIRCUIT BREAKERS
One
fi
eld provided power sup ply cir cuits to the unit with
in di vid u al branch cir cuit protection. Field Power Wiring
connections to fac to ry provided, Non-Fused Dis con nect
Switches (Opt), or Ter mi nal Blocks (Opt) in the Option
Box.
Suitable for:
Y -
∆
Start and
Across-The-Line-Start
LD05548
See page 6 for notes.
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION WITH INDIVIDUAL UNIT CIRCUIT BREAKERS
3 & 4 COMPRESSOR UNITS
(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block (standard) or Non-Fused Disconnect (option)
in ‘Option Panel’. Circuit Breakers in each Motor Control Center
FIELD SUPPLIED WIRING
CHILLER
FIELD PROVIDED POWER SUPPLY
FACTORY PROVIDED (LUGS) WIRE RANGE
7
MODEL
YCAS
VOLTS
MCA
1
MIN NF OVER-CURRENT PROTECTION
13
TERMINAL BLOCK NF DISC. SWITCH
DISC SW
2, 9
MIN.
3, 5
MAX.
4, 6
(LUGS) WIRE RANGE (LUGS) WIRE RANGE
380 561 600 600 700 (2) 2/0-500 (2) 250-500
0250EC
460 464 600 500 500 (2) 1/0-300 (2) 250-500
575 372 400 400 450 (2) # 2-4/0 (3) 2/0-250
380 651 800 800 800 (2) 2/0-500 (3) 2/0-400
0270EC
460 534 600 600 700 (2) 2/0-500 (2) 250-500
575 427 600 500 500 (2) 1/0-300 (2) 250-500
380 678 800 800 800 (3) 1/0-300 (3) 2/0-400
0300EC
460 559 600 600 700 (2) 2/0-500 (2) 250-500
575 445 600 500 500 (2) 1/0-500 (2) 250-500
380 745 800 800 800 (3) 1/0-300 (3) 2/0-400
0330EC
460 612 800 700 700 (2) 2/0-500 (3) 2/0-400
575 487 600 600 600 (2) 1/0-300 (2) 250-500
380 835 1000 1000 1000 (3) 2/0-500 (4) 4/0-500
0360EC
460 689 800 800 800 (3) 1/0-300 (3) 2/0-400
575 550 600 600 600 (2) 2/0-500 (2) 250-500
380 896 1000 1000 1000 (3) 2/0-500 (4) 4/0-500
0400EC
460 739 1000 800 800 (3) 2/0-500 (4) 4/0-500
575 589 800 700 700 (2) 2/0-500 (3) 2/0-400
380 991 1200 1200 1200 (3) 2/0-500 (4) 4/0-500
0440EC
460 812 1000 1000 1000 (3) 2/0-500 (4) 4/0-500
575 647 800 800 800 (2) 2/0-500 (3 )2/0-400
CB
3
CB
4
CB
1
CB
2
TB
or
DS
Field Supply
Suitable for:
Y - D Start and
Across the Line Start
See Note 3
Summary of Contents for YCAS0250
Page 5: ...YORK INTERNATIONAL 5 FORM 201 19 W2 304 This page intentionally left blank...
Page 21: ...YORK INTERNATIONAL 21 FORM 201 19 W2 304 LD09359 Electronic Panel...
Page 24: ...YORK INTERNATIONAL 24 FORM 201 19 W2 304 FIG 11 CONNECTION DIAGRAM 3 COMPRESSOR LD09362...
Page 33: ...YORK INTERNATIONAL 33 FORM 201 19 W2 304 This page intentionally left blank...
Page 40: ...YORK INTERNATIONAL 40 FORM 201 19 W2 304 LD09379 FIG 25 CONNECTION DIAGRAM 4 COMPRESSOR...