YORK INTERNATIONAL
4
Specification
GENERAL
The 47 - 60 Ton (165 - 210 kW) YCAL models are
shipped complete from the factory ready for installation
and use.
The unit is pressure-tested, evacuated, and fully charged
with Refrigerant-22 (HCFC-22) and includes an initial
oil charge. After assembly, a complete operational test
is performed with water flowing through the cooler to
assure that the refrigeration circuit operates correctly.
The unit structure is heavy-gauge, galvanized steel. This
galvanized steel is coated with baked-on powder paint,
which, when subjected to ASTM B117 1000 hour, salt
spray testing, yields a minimum ASTM 1654 rating of
“6”. Corrosion resistant wire mesh panels are added to
protect the condenser coil from incidental damage and
restrict unauthorized access to internal components.
Units are designed in accordance with NFPA 70 (Na-
tional Electric Code), ASHRAE/ANSI 15 Safety code for
mechanical refrigeration, ASME, Listed and labeled with
Intertek Testing Services (ETL) and rated in accordance
with ARI Standard 550/590-2003.
COMPRESSORS
The chiller has suction-gas cooled, hermetic, scroll com-
pressors. The YCAL compressors incorporate a compli-
ant scroll design in both the axial and radial direction. All
rotating parts are statically and dynamically balanced. A
large internal volume and oil reservoir provides greater
liquid tolerance. Compressor crankcase heaters are also
included for extra protection against liquid migration.
COOLER
The cooler is equipped with a heater controlled by a
separate thermostat. The heater provides freeze protec-
tion for the cooler down to -20°F (-29°C) ambient. The
cooler is covered with 3/4” (19mm) flexible, closed-cell,
foam insulation (K~0.25).
Brazed plate heat exchangers shall be UL (Underwriters
Laboratories) listed. Installing contractor must include
accommodations in the chilled water piping to allow
proper drainage and venting of the heat exchanger.
Water inlet and outlet connections are grooved for com-
patibility with factory supplied victaulic connections.
A strainer with a mesh size between .5 and 1.5 mm (40
mesh) is recommended upstream of the heat exchanger
to prevent clogging.
CONDENSER
Coils
– Fin and tube condenser coils of seamless, inter-
nally-enhanced, high-condensing-coefficient, corrosion
resistant copper tubes are arranged in staggered rows,
mechanically expanded into aluminum fins. Integral
subcooling is included. The design working pressure of
the coil is 450 PSIG (31 bar).
Low Sound Fans
– The condenser fans are composed
of corrosion resistant aluminum hub and glass-fiberrein-
forced composite blades molded into a low noise airfoil
section. They are designed for maximum efficiency and
are statically and dynamically balanced for vibration free
operation. They are directly driven by independent mo-
tors, and positioned for vertical air discharge. All blades
are statically and dynamically balanced for vibration-free
operation. The fan guards are constructed of heavy-
gauge, rust-resistant, PVCcoated steel wire.
Motors
– The fan motors are Totally Enclosed Air-Over,
squirrel-cage type, current protected. They feature
ball bearings that are double-sealed and permanently
lubricated.
Summary of Contents for YCAL0065
Page 10: ...YORK INTERNATIONAL 10 This page intentionally left blank...
Page 61: ...YORK INTERNATIONAL 61 FORM 150 64 EG1 INTENTIONALLY LEFT BLANK...
Page 68: ...YORK INTERNATIONAL 68 Power Wiring FIG 1 STANDARD POWER SUPPLY WIRING YCAL 0014 0080...
Page 69: ...YORK INTERNATIONAL 69 FORM 150 64 EG1...
Page 70: ...YORK INTERNATIONAL 70...