FORM 150.64-EG1
Options and Accessories
POWER OPTIONS:
COMPRESSOR POWER CONNECTIONS –
Single-
point (YCAL0041-0065) terminal block connection(s) are
provided as standard. The following power connections
are available as options. (See electrical data for specific
voltage and options availability.) (
Factory-Mounted
.)
SINGLE-POINT SUPPLY TERMINAL BLOCK –
(stan-
dard on YCAL0041 - 0065 models). Includes enclosure,
terminal-block and interconnecting wiring to the com-
pressors. Separate external protection must be supplied,
by others, in the incoming compressor-power wiring. (Do
not include this option if either the SinglePoint NonFused
Disconnect Switch or Single-Point Circuit Breaker op-
tions have been included.)
SINGLE-POINT NON-FUSED DISCONNECT SWITCH
–
Unit-mounted disconnect switch with external, lockable
handle (in compliance with Article 440-14 of N.E.C.),
can be supplied to isolate the unit power voltage for
servicing. Separate external fusing must be supplied,
by others in the power wiring, which must comply with
the National Electrical Code and/or local codes.
SINGLE-POINT CIRCUIT BREAKER –
A unit mounted
circuit breaker with external, lockable handle (in com-
pliance with N.E.C. Article 440-14), can be supplied
to isolate the power voltage for servicing. (This option
includes the Single-Point Power connection.)
CONTROL TRANSFORMER –
Converts unit power
voltage to 115-1-60 (0.5 or 1.0 KVA capacity). Fac-
tory mounting includes primary and secondary wiring
between the transformer and the control panel. (
Fac-
tory-Mounted
.)
POWER FACTOR CORRECTION CAPACITORS –
Will
correct unit compressor power factors to a 0.90-0.95.
(
Factory-Mounted
.)
CONTROL OPTIONS:
AMBIENT KIT (LOW) –
Units will operate to 25°F (-4°C).
This accessory includes all necessary components to
permit chiller operation to 0°F (-18°C). (This option in-
cludes the Discharge Pressure Transducer / Readout
Capability option.) For proper head pressure control in
applications below 25°F (-4°C), where wind gusts may
exceed five mph, it is recommended that Optional Con-
denser Louvered Enclosure Panels also be included.
(
Factory-Mounted
.)
AMBIENT KIT (HIGH) –
Required if units are to operate
when the ambient temperature is above 115°F (46°C).
Includes discharge pressure transducers. (This option
includes the Discharge Pressure Transducer / Readout-
Capability option.) (
Field-Mounted
.)
BUILDING AUTOMATION SYSTEM INTERFACE –
The
factory addition of a Printed Circuit Board to accept a
4-20 milliamp, 0-10VDC or contact closure input to reset
the leaving chiller liquid temperature from a Building Au-
tomation System. (Only one of following options can be
offered on a unit at a time: BAS, Remote Control Panel
or Multi-unit Sequence Control.) (
Factory-Mounted
.)
(The standard unit capabilities include remote startstop,
remote water temperature reset via a PWM input signal
or up to two steps of demand (load) limiting depending
on model.) (The standard control panel can be directly
connected to a YORK Building Automated System via
the standard onboard RS485 communication port.)
LANGUAGE LCD AND KEYPAD DISPLAY –
Spanish,
French, and German unit LCD controls and keypad
display available. Standard language is English.
DISCHARGE PRESSURE TRANSDUCERS AND
READOUT CAPABILITY –
The addition of pressure
transducers allows models to sense and display dis-
charge pressure. This is recommended for brine chilling
applications. (This option is included with either the low
or high ambient kits.) (
Factory-Mounted
.)
•
Suction Pressure Transducers
: Permits unit to
sense and display suction pressure. This capability
is standard on YCAL0041-0065 models.
MOTOR CURRENT MODULE –
Capable of monitoring
compressor motor current. Provides extra protection
against compressor reverse rotation, phase-loss and
phase imbalance. Option consists of one module per
electrical system. (
Factory-Mounted
.)
OPTIVIEW REMOTE CONTROL PANEL -
Graphical
interface panel to remotely control and monitor up to 8
different units. (Refer to form 201.18-SG4 for detailed
information)
MULTI-UNIT SEQUENCING –
A separate Sequencing
Control Center is provided to handle sequencing control
of up to eight chillers in parallel based on mixed liquid
temperature (interconnecting wiring by others). (Only
one of following options can be offered on a unit at a
time: BAS, Remote Control Panel or Multi-unit Sequence
Control.) (
Factory-Mounted
.)
COMPRESSOR, PIPING, EVAPORATOR
OPTIONS:
LOW TEMPERATURE BRINE –
Required for brine
Summary of Contents for YCAL0041
Page 10: ...YORK INTERNATIONAL 10 This page intentionally left blank...
Page 61: ...YORK INTERNATIONAL 61 FORM 150 64 EG1 INTENTIONALLY LEFT BLANK...
Page 68: ...YORK INTERNATIONAL 68 Power Wiring FIG 1 STANDARD POWER SUPPLY WIRING YCAL 0014 0080...
Page 69: ...YORK INTERNATIONAL 69 FORM 150 64 EG1...
Page 70: ...YORK INTERNATIONAL 70...