MAINTENANCE
TABLE 43 – REAL TIME ERROR NUMBERS
ERROR NUMBER
(##)
DESCRIPTION
0
ALL OK
1
DATUM TYPE OK TEST FAILED
2
ENGLISH TEXT TOO LONG
3
FLOATING POINT EXCEPTION
4
GET PACKET FAILED
5
GET TYPE FAILED
6
INVALID UNIT CONVERSION
7
INVALID HARDWARE SELECTION
8
REAL TIME FAULT
9
SPANISH TEXT TOO LONG
10
THREAD EXITED
11
THREAD FAILED
12
THREAD STALLED
13
IO BOARD RESET
14
BRAM INVALID
15
BACNET SETUP FAILED
TABLE 42 – VALUES REQUIRED FOR BAS COMMUNICATION
SETTING DESCRIPTION
Protocol
BACnet MS/TP
Modbus RTU
5
YorkTalk 2
DE MODIFIER ADDRESS
0 to 41943
(3)
1
-1
DE MODIFIER OFFSET
0 to 99
(4)
0
N/A
P1 PROTOCOL
BACNET
N/A
N/A
P1 MANUAL MAC ADDRESS
0-127
(1)
N/A
N/A
P1 BAUD RATE
9600 to 76800 or Auto Selectable
(1)
N/A
N/A
P1 PARITY
NONE
N/A
N/A
P1 STOP BITS
1
N/A
N/A
P2 PROTOCOL
N/A
MODBUS SVR
N/A
P2 MANUAL MAC ADDRESS
N/A
0-127
(1)
N/A
P2 BAUD RATE
N/A
19,200
(2)
N/A
P2 PARITY
N/A
NONE
(2)
N/A
P2 STOP BITS
N/A
1
N/A
P2 HW SELECT BIT
N/A
RS-485 or RS-232
(1)
N/A
RESET REAL TIME ERROR
N/A
N/A
N/A
P1 HW SELECT BIT
N/A
N/A
N/A
CHILLER ID
N/A
N/A
0
1
as required by network
2
or other as required by network
3
number is multiplied by 100, set as required by network
4
number is added to DE MODIFIER ADDRESS, set as required by network
5
unit operating software version C.MMC.13.03 or later required for Modbus protocol
The table below shows the real time error numbers that
may be encountered during communication setup and
a description of each.
Reboot required (cycle power) after set
-
tings are changed.
Summary of Contents for YCAL0014E Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...JOHNSON CONTROLS 126 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 140: ...JOHNSON CONTROLS 140 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM8 1020 5 6 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM8 1020 5 6 LD08855 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM8 1020 161 5 6 ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM8 1020 5 6 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM8 1020 5 6 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM8 1020 5 6 ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM8 1020 5 6 ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM8 1020 5 6 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM8 1020 5 6 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM8 1020 5 6 ...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 NM8 1020 5 6 ...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 NM8 1020 5 6 LD08833 ...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 NM8 1020 5 6 ...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 NM8 1020 5 6 ...
Page 189: ...JOHNSON CONTROLS 189 FORM 150 62 NM8 1020 5 6 ...
Page 191: ...JOHNSON CONTROLS 191 FORM 150 62 NM8 1020 5 6 ...
Page 195: ...JOHNSON CONTROLS 195 FORM 150 62 NM8 1020 5 6 ...
Page 197: ...JOHNSON CONTROLS 197 FORM 150 62 NM8 1020 5 6 ...
Page 199: ...JOHNSON CONTROLS 199 FORM 150 62 NM8 1020 5 6 ...
Page 200: ...JOHNSON CONTROLS 200 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 211: ...JOHNSON CONTROLS 211 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...