TABLE 15: WJ240 BLOWER PERFORMANCE - 20 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW
Blower Performance (Downflow Discharge)
ESP
CFM
RPM
KW
BHP
CFM
RPM
KW
BHP
CFM
RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP
0.4
-
-
-
-
-
-
-
-
9345 1035 6.99 8.53 8835 1001 6.23 7.60 8588 966 5.69 6.94 8216 932 4.89 5.97
0.6
-
-
-
-
9328 1073 7.36
8.98
8947 1036 6.76 8.25 8418 1002 5.87 7.16 8130 968 5.22 6.36 7759 933 4.60 5.62
0.8
9516 1107 8.00
9.77
8929 1073 7.03
8.58
8557 1038 6.31 7.70 8070 1005 5.60 6.83 7731 969 4.96 6.05 7319 934 4.44 5.42
1.0
9127 1108 7.54
9.20
8551 1075 6.80
8.29
8122 1039 5.97 7.28 7723 1005 5.34 6.52 7244 971 4.60 5.62 6838 936 3.92 4.70
1.2
8726 1109 7.02
8.57
8157 1077 6.16
7.51
7708 1041 5.46 6.67 7202 1007 4.82 5.88 6767 972 4.33 5.28 6346 937 3.66 4.39
1.4
8331 1112 6.78
8.28
7689 1077 5.83
7.12
7281 1042 5.18 6.32 6741 1007 4.48 5.47 6369 972 3.89 4.67 5851 937 3.45 4.14
1.6
7742 1113 6.21
7.58
7240 1079 5.50
6.71
6794 1043 4.74 5.78 6360 1008 4.23 5.16 5809 974 3.58 4.30 5355 938 3.26 3.92
1.8
7337 1115 6.01
7.33
6762 1080 4.95
6.04
6275 1045 4.48 5.47 5787 1110 3.85 4.63 5251 975 3.27 3.93 4628 940 2.66 3.19
2.0
6826 1116 5.51
6.72
6279 1082 4.80
5.86
5732 1047 4.23 5.16 5215 1011 3.48 4.17 4414 976 2.77 3.33 3613 941 2.36 2.83
2.2
6313 1118 5.27
6.44
5728 1083 4.56
5.56
5190 1048 3.69 4.43
-
-
-
-
-
-
-
-
-
-
-
-
2.4
5802 1120 4.88
5.95
5176 1084 4.12
4.94
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.6
5289 1121 4.39
5.36
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 turn
2 turns
3 turns
4 turns
5 turns
6 turns
10 HP motor
7.5 HP motor
5 HP motor
20-Ton High Static Drive, Gas Heat, Bottom Duct Connection
VP68 x BK100
3000
4000
5000
6000
7000
8000
9000
10000
11000
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
External Static ("WC)
SCFM
1 Turn
2 Turns
3 Turns
5 Turns
6 Turns
4 Turns