York TM8X Series Technical Manual Download Page 3

445348-YTG-D-0612

Johnson Controls Unitary Products

3

1. Air velocity through throwaway type filters may not exceed 300 feet per min-

ute (91.4 m/min). All velocities over this require the use of high velocity fil-
ters.

2. Do not exceed 1800 CFM using a single side return and a 16x25 filter. For 

CFM greater than 1800, you may use two side returns or one side and the 
bottom or one return with a transition to allow use of a 20x25 filter.

ACCESSORIES

Propane (LP) Conversion Kit - 

This accessory conversion kit

may be used to convert natural gas units for propane (LP) oper-
ation.

1NP0347 - All Models 

Side Return Filter Racks - 

1SR0200 - All Models
1SR0302 - All Models

Bottom Return Filter Racks - 

1BR05xx series are galvanized

steel filter racks. 1BR06xx are pre-painted steel filter racks to
match the appearance of the furnace cabinet.

1BR0514 or 1BR0614 - For 14-1/2” cabinets
1BR0517 or 1BR0617 - For 17-1/2” cabinets
1BR0521 or 1BR0621 - For 21” cabinets

Masonry Chimney Kits - 

For installations where these fur-

naces are vented using existing or new lined masonry chim-
neys.

1CK0603
1CK0604

Combustible Floor Base Kit - 

For installation of these fur-

naces in downflow applications directly onto combustible floor-
ing material. These kits are required to prevent potential
overheating situations. These kits are also required in any appli-
cations where the furnace in installed in a downflow configura-
tion without an evaporator coil, where the combustible floor
base kit provides access for combustible airflow.

1CB0514 - For 14-1/2” cabinets
1CB0517 - For 17-1/2” cabinets
1CB0521 - For 21” cabinets

High Altitude Pressure Switches - 

For installation where the

altitude is less than 5,000 feet it is not required that the pres-
sure switch be changed. For altitudes above 5,000 feet, see kits
below.

1PS3301  060, 080, 120
1PS3302  100

Thermostats - 

Compatible thermostat controls are available

through accessory sourcing. For optimum performance and
installation, refer to the UPGNET “Low Voltage Wiring Diagram”
document to select and apply controls.

Single side return above 1800 CFM is approved as long as
the filter velocity does not exceed filter manufacturer’s rec-
ommendation and a transition is used to allow use on a
20x25 filter.

NOTICE

Recommended Filter Sizes

CFM

Cabinet

Size

Side

(in)

Bottom

(in)

1200

A

16 x 25

14 x 25

1200

B

16 x 25

16 x 25

1600

C

16 x 25

20 x 25

2000

C

(2) 16 x 25

20 x 25

Unit Clearances to Combustibles (All dimensions in inches, and all surfaces identified with the unit in an upflow configuration)

Application

Top

Front

Rear

Left 

Side

Right 

Side

Flue

Floor/

Bottom

Closet

Alcove

Attic

Line 

Contact

Upflow

1

6

0

0

3

6

Combustible

Yes

Yes

Yes

No

Upflow B-Vent

1

3

0

0

0

1

Combustible

Yes

Yes

Yes

No

Downflow

1

6

0

0

3

6

1

1

1. Special floor base or air conditioning coil required for use on combustible floor.

Yes

Yes

Yes

No

Downflow B-Vent

1

3

0

0

0

1

1

1

Yes

Yes

Yes

No

Horizontal

1

6

0

0

3

6

Combustible

No

Yes

Yes

Yes

2

2. Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace jacket and build-

ing joists, studs or framing.

Horizontal B-Vent

1

3

0

0

0

1

Combustible

No

Yes

Yes

Yes

2