16
T2GY INSTALLER’S GUIDE
Auxiliary Heat
NOTES:
The heat pump requires Medium and High blower setting to be above the minimum CFM for the heater selected.
Rear discharge uses the horizontal auxiliary heat kits, EALH10A, 15A, or 20A.
Auxiliary Heat Ratings
Auxiliary Heat Electrical Data
Model
KW
Stages
BTU/HR
Min
CFM
Compatibility
208V
230V
208V
230V
038
049
064
072
EAL10A
7.2
9.6
2
24,600 32,700 1100
•
•
•
•
EAL15A
10.8
14.4
3
36,900 49,100 1250
•
•
•
•
EAL20A
14.4
19.2
4
49,200 65,500 1500
•
•
•
5/6/09
Model
Supply
Circuit
Heater Amps
Min Circuit Amp
Max Fuse (USA)
Max Fuse (CAN)
Max CKT BRK
208V
240V
208V
240V
208V
240V
208V
240V
208V
240V
EAL(H)10A
Single
34.7
40
53.3
60
60
60
60
60
60
60
EAL(H)15A
Single
52.0
60
75
85
80
90
80
90
70
100
L1/L2
34.7
40
53.3
60
60
60
60
60
60
60
L3/L4
17.3
20
21.7
25
25
25
25
25
20
30
EAL(H)20A
Single
69.3
80
96.7
110
100
110
100
110
100
100
L1/L2
34.7
40
53.3
60
60
60
60
60
60
60
L3/L4
34.7
40
43.3
50
45
50
45
50
40
50
All heaters rated single phase 60 cycle and include unit fan load
All fuses type “D” time delay (or HACR circuit breaker in USA)
Vertical rear discharge models use the horizontal (EALH) auxiliary heat kit