5188235-YIM-E-0518
22
Johnson Controls Ducted Systems
060
(5.0)
208-1-60 24.4 144.2
38
4.4
7.6
0
NONE
-
-
-
42.5
60
E05
4
1
19.2
42.5
60
E07
5.6
1
26.9
43.2
60
E10
8
1
38.5
57.6
60
E15
11.9
2
57.2
81
90
E20
15.9
2
76.4
105.1
110
E30
22.2
2
106.7
142.9
150
230-1-60 24.4 144.2
38
4.4
7.6
0
NONE
-
-
-
42.5
60
E05
5.3
1
22.1
42.5
60
E07
7.5
1
31.2
48.6
60
E10
10.6
1
44.2
64.7
70
E15
15.9
2
66.2
92.3
100
E20
21.2
2
88.3
119.9
125
E30
29.6
2
123.3
163.7
175
208-3-60
16
110
24.9
4.4
7.6
0
NONE
-
-
-
32
40
E05
4
1
11.1
32
40
E07
5.6
1
15.5
32
40
E10
8
1
22.2
37.3
45
E15
11.9
2
33
50.8
60
E20
15.9
2
44.1
64.7
70
E30
22.2
2
61.6
86.5
90
230-3-60
16
110
24.9
4.4
7.6
0
NONE
-
-
-
32
40
E05
5.3
1
12.7
32
40
E07
7.5
1
18
32.1
40
E10
10.6
1
25.5
41.4
45
E15
15.9
2
38.2
57.3
60
E20
21.2
2
51
73.2
80
E30
29.6
2
71.2
98.5
100
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZE036-060 - Without Powered Convenience Outlet (Direct Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps