Unitary Products Group
TABLE 11: COOLING CAPACITIES FOR DJ210 AT 105°F
RETURN AIR
OUTDOOR AMBIENT TEMPERATURE (°F): 105
CFM
WB
TEMP °F
GROSS
CAPACITY
1
(MBH)
INPUT
POWER
2
(kW)
GROSS SENSIBLE CAPACITY
1
(MBH)
(RETURN AIR DRY BULB TEMP. - (°F) )
86
83
80
77
74
71
68
6000
72
210.2
17.65
131.0
113.9
96.8
79.7
62.6
#N/A
#N/A
67
195.1
17.21
167.5
150.4
133.3
116.2
99.1
82.0
64.9
62
186.9
17.01
186.9
170.6
153.5
136.4
119.3
102.2
85.1
57
174.4
16.80
174.4
172.3
155.2
138.1
121.0
103.9
86.8
6500
72
218.3
17.77
143.8
125.0
106.3
87.5
68.7
#N/A
#N/A
67
202.6
17.33
183.9
165.1
146.4
127.6
108.8
90.1
71.3
62
194.1
17.12
194.1
186.0
168.5
149.8
131.0
112.2
93.5
57
181.1
16.92
181.1
180.1
170.4
151.7
132.9
114.1
95.4
7000
72
226.4
17.89
156.6
136.2
115.7
95.3
74.9
#N/A
#N/A
67
210.1
17.45
200.2
179.8
159.4
139.0
118.6
98.2
77.8
62
201.3
17.24
201.3
201.3
183.6
163.1
142.7
122.3
101.9
57
187.8
17.03
187.8
187.8
185.6
165.2
144.8
124.4
104.0
7875
72
228.5
17.97
171.3
148.0
124.8
101.5
78.3
#N/A
#N/A
67
212.1
17.53
207.1
193.3
171.9
148.6
125.4
102.2
78.9
62
203.2
17.32
203.2
203.2
194.3
171.0
147.8
124.5
101.3
57
189.6
17.11
189.6
189.6
188.5
165.2
142.0
118.7
95.5
8750
72
230.6
18.05
186.0
159.9
133.8
107.7
81.7
#N/A
#N/A
67
214.0
17.61
214.0
206.7
184.4
158.3
132.2
106.1
80.0
62
205.0
17.40
205.0
205.0
205.0
178.9
152.8
126.8
100.7
57
191.3
17.19
191.3
191.3
191.3
165.2
139.1
113.0
87.0
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.