NOTE:
ELEC / ELEC Models: Units and ductwork are
approved for zero clearance to combustible material
when equipped with electric heaters.
GAS / ELEC Models: A 1” clearance must be provided
between any combustible material and the supply air
ductwork for a distance of 3 feet from the unit.
The products of combustion must not be allowed to
accumulate within a confined space and recirculate.
Locate unit so that the vent air outlet hood is at least:
• Three (3) feet above any force air inlet located within
10 horizontal feet (excluding those integral to the
unit).
• Four (4) feet below, four horizontal feet from, or one
foot above any door or gravity air inlet into the
building.
• Four (4) feet from electric and gas meters, regulators
and relief equipment.
SUPPLY
AIR
RETURN
AIR
OUTDOOR
AIR
5-1/8"
18-5/8"
27-3/4"
39-5/8"
40-1/2"
OUTDOOR AIR
COMPARTMENT
ACCESS
FILTER
ACCESS
1" NPT FEMALE
COND. DRAIN
CONNECTION
DOT PLUG
(For pressure
drop reading)
EVAPORATOR
SECTION
40-3/8"
COMPRESSOR
ACCESS
SUPPLY AIR
ACCESS
RETURN AIR
ACCESS
REAR
VIEW
Dimensions listed are for side
duct flange openings; see
Field Accessories for Side
Duct Flange Kit.
LOCATION
CLEARANCE
Front
36”
Rear
24” (Less Economizer)
49” (With Economizer)
Left Side (Filter Access)
24” (Less Economizer)
36” (With Economizer)
3
Right Side (Cond. Coil)
36”
Below Unit
1
1. Units may be installed on combustible floors made from wood or
class A, B, or C roof covering material.
0”
Above Unit
2
2. Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge outlet.
3. If economizer is factory installed, the unassembled rain hood
must be removed from its ride along position in front of evapora-
tor coil, or in the outdoor air compartment, prior to final installa-
tion.
72” With 36” Maximum
Horizontal Overhang (For
Condenser Air Discharge)