SECTION 3 – LOGIC/TRIGGER BOARD
LOGIC/TRIGGER BOARD INDICATOR LEDS
The Logic/Trigger Board contains only two LEDs.
Since all of the shutdown messages are displayed on
the OptiView Control Center, there is no need for
LEDs to annunciate a shutdown condition. The two
LEDs are used to verify that the serial communications
link is working.
CR6 is the Receive LED. This LED will flash green
every 2 seconds to indicate that the Logic/Trigger
Board has received data from the OptiView Control
Center. (Refer to
of LED.)
CR7 is the Transmit LED. This LED will flash red ev-
ery 2 seconds to indicate that the Logic/Trigger Board
has sent data to the OptiView Control Center. (Refer to
for location of LED.)
RELAY FUNCTIONS
Relay K1 shall provide a hardware shutdown signal to
the OptiView Control Center via wires 16 and 53. The
relay will provide a normally open set of contacts that
are driven closed when the LCSSS is operating satis-
factorily, and the contacts will open when the LCSSS
initiates a Cycling or Safety shutdown. These contacts
will remain open until the cause of the shutdown has
been rectified.
Relay K2 controls the operation of the closed loop
coolant pump. When the Micro Board commands the
LCSSS to run, the main system microprocessor, via an
output driver, causes the K2 relay contacts to close. As
long as the K2 contacts are closed, the closed loop cool-
ant pump will run. When the Micro Board commands
the LCSSS to stop, the main system microprocessor, via
an output driver, causes the K2 relay contacts to open
(provided all of the thermistor temperatures are below
110°F). This will stop the closed loop coolant pump.
Therefore, the closed loop coolant pump may start and
stop with the compressor motor. Also, the K2 relay will
be energized by the main system microprocessor when
any heatsink temperature exceeds 110°F regardless
of whether the chiller is running or not. When the
temperature falls below 110°F, the main system micro-
processor will de-energize K2 relay causing the pump
to stop.
FIGURE 6 -
LCSSS – LOGIC/TRIGGER BOARD DETAIL
J11
J10
J9
J8
J7
J6
J5
J1
TB-2
TB-1
J4
J3
J2
JP1
CR7
CR6
U15 RAM CHIP U16 EPROM
J12
00287VIP
Summary of Contents for SSS 14L-B
Page 4: ...JOHNSON CONTROLS 4 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 8: ...JOHNSON CONTROLS 8 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 24: ...JOHNSON CONTROLS 24 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...JOHNSON CONTROLS 30 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...