MODEL
MOTOR
PULLEY
EXTERNAL STATIC PRESSURE, INCHES W.C.
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
P4UCB30N12206
High Static Drive
Closed
✚
✚
✚
✚
✚
3382
3277
3084
2925
2760
2625
2465
1 Open
✚
3740
3623
3477
3356
3227
3032
2869
2659
2347
2232
2096
3 Open
3573
3396
3237
3074
2873
2724
2360
1922
◆
◆
◆
◆
5 Open
3032
2848
2683
2422
2283
1905
◆
◆
◆
◆
◆
◆
Airlfow is expressed in standard cubic feet per minute.
u
Operation at these conditons will cause excessive furnace furnace temperature rise
✚
Operation at these conditions will cause motor overload
NOTES:
●
Return air is through both sides.
●
Air filters installed
●
Motor voltage at 230V
●
For bottom only return, reduce rating by 6%.
BLOWER PERFORMANCE
650.64-N4
14
Unitary Products Group