SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.79-O3
ISSUE DATE: 11/09/2018
2
Discharge Temperature
Displays the temperature of the refrigerant in its gas-
eous state at the discharge of the compressor #1 as it
travels to the condenser.
Discharge Superheat
Displays compressor #1 discharge superheat, calcu-
lated as (discharge temperature – condenser saturation
temperature).
Compressor 2
PROGRAMMABLE
None
NAVIGATION
Home
Access Level Required: VIEW
Causes an instant return to the Home Screen.
Compressor 1 and 2
Access Level Required: SERVICE
Only displayed in Service access level. Moves to a sub-
screen that allows calibration of the Proximity Probe
and Pre-rotational Vanes and viewing of parameters
for compressor #2. Also, manual control of the Dis-
charge Valve and Pre-rotation Vanes is performed on
this screen.
Capacity Control
Access Level Required: VIEW
Navigates to the Capacity Control Screen where the
Operator can view any override conditions that are in
effect and the status of the Capacity Control Output
devices. That screen also provides access to the Capac-
ity Cycling and Hot Gas screens.
Surge
Access Level Required: VIEW
Moves to a subscreen that allows viewing and pro-
gramming of the Surge Protection feature.
Oil Sump
Access Level Required: VIEW
Moves to a subscreen that allows viewing of the Oil
Pumps parameters and access to the individual pump
screens.