679948-YTG-A-0111
14
Unitary Products Group
TABLE 17:STATIC RESISTANCE FOR UNIT ACCESSORY (IWG) - NE240
CFM
Supply
Air Plenum
Return
Air
Grille
Non
Freeze
Steam Coil
Hot
Water
Coil
6400
.03
.04
.14
.07
7200
.03
.05
.17
.08
8000
.04
.06
.21
.10
8800
.05
.07
.25
.12
9600
.06
.08
.29
.14
TABLE 18: SUPPLY AIR PLENUM PERFORMANCE DATA - NE090, NE/NF120 & NE180
Model
CFM
Face
Velocity
(FPM)
Angle of Deflection
Vertical
Louvers
1
(Plan
View)
Horizontal
Louvers
2
(Elevation
View)
Vertical
Louvers
(Plan
View)
Horizontal
Louvers
(Elevation
View)
Vertical
Louvers
(Plan
View)
Horizontal
Louvers
(Elevation
View)
Throw
(Feet)
Spread
(Feet)
3
Throw
(Feet)
Spread
(Feet)
Throw
(Feet)
Spread
(Feet)
Min.
Max.
Min. Max
Drop (Feet)
4
Min.
Max
Min. Max
Drop (Feet)
Min.
Max.
Min.
Max.
Drop (Feet)
090
2400
615
47
74
20
29
19
9
34
53
23
33
17
8
26
39
45
65
9
5
2700
690
53
83
22
32
20
10
39
59
25
36
18
9
29
45
48
71
10
5
3000
770
59
92
24
35
21
10
42
66
27
40
19
9
32
50
52
78
10
5
3300
845
65
101
26
38
21
10
46
73
29
44
19
9
35
55
56
85
10
5
3600
920
71
110
28
41
22
11
50
79
32
47
20
10
38
60
60
91
11
6
120
3200
820
63
98
25
37
21
10
45
70
29
43
19
9
34
53
54
82
10
5
3600
920
71
110
28
41
22
11
50
79
32
47
20
10
38
60
60
91
11
6
4000
1025
78
123
30
45
22
11
56
88
35
52
20
10
42
66
67
102
11
6
4400
1130
86
135
33
49
23
12
62
97
38
57
21
11
47
73
76
115
12
6
4800
1230
94
147
35
53
23
12
68
106
41
62
21
11
51
80
85
127
12
6
180
4800
880
84
132
32
48
23
12
61
95
38
56
21
11
46
72
73
112
12
6
5400
1000
95
149
36
54
24
12
68
107
42
63
22
11
52
81
81
124
12
6
6000
1110
106
165
39
59
25
13
76
119
46
69
23
12
57
89
90
138
13
7
6600
1220
116
182
43
65
26
13
84
131
50
76
23
12
63
98
99
152
13
7
7200
1330
126
199
46
70
27
14
92
143
55
83
24
12
68
107
109
166
14
7
1. Adjusting the vertical louvers will vary the throw, the spread and the drop.
2. Adjusting the horizontal louvers will only vary the drop.
3. The velocity of the air will be 125 ft./min. at the minimum distance and 80 ft./min. at the maximum distance.
4. The velocity of the conditioned air at the bottom of the drop will be 50 ft./min. Drafts will occur if the drop extends into the occupied
level of the conditioned space.
TABLE 19: SUPPLY AIR PLENUM PERFORMANCE DATA - NE240
CFM
Throw, Feet
Minimum
Maximum
6400
80
145
8000
98
165
9600
115
185
0°
SPREAD
22-1/2°
SPREAD
45°
SPREAD
0°
SPREAD
18˚
0°
SPREAD
18˚
0°
SPREAD
18˚