background image

INSTALLATION, OPERATION & MAINTENANCE MANUAL

York Taurus Commercial Ducted Splits

2

Summary of Contents for Mr. Slim PK-1.6FLA

Page 1: ...INSTALLATION OPERATION MAINTENANCE MANUAL York Taurus Commercial Ducted Splits 2...

Page 2: ...elines Interconnection Pipes heat 09 F Guidelines Interconnection Pipes Cool 10 G Sound Pressure Data 11 F Field Wiring Guide 12 G Commissioning of Electrical Wires 14 Power Cables H Servicing of the...

Page 3: ...inside the unit or in front of the coil Make provisions for condensate drainage Do proper conducting from drain outlet of the unit to soak pit to avoid drippage Detail installation method depends on...

Page 4: ...restrictions and practices Use 25 4mm 1 ID pipe or rubber hose to connect with GI nipple of unit to dispose the condensate water from unit to termination point Condensate drain pipe should be termina...

Page 5: ...st be lifted by 2 pipe hook rigging sling in base rail use spreader bar to prevent the sling from damaging the unit A minimum clearance of 1 m on serviceable side 300 mm for air inlets on all sides an...

Page 6: ...aximum lift should not exceed 100 feet suction line The oil trap to be repeated every 35 feet C If indoor unit YE2EU is located above outdoor unit YE2CE the maximum lift should not exceed 70 feet liqu...

Page 7: ...8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 150 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 175 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 200 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 YE2EU 072 YE...

Page 8: ...7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 150 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 175 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 200 1 1 8 7 8 1 1 8 1 1 8 1 3 8 1 3 8 1 5 8 1 5 8 YE2EU 072...

Page 9: ...22 UNITS 1M DISTANCE INDOOR dB A OUTDOOR dB A YE2EU072 53 4 YE2CE072 61 2 YE2EU090 57 6 YE2CE090 65 0 YE2EU120 61 5 YE2CE120 70 2 YE2EU150 64 4 YE2CE150 75 1 YE2EU180 66 2 YE2CE180 77 4 YE2EU216 70 0...

Page 10: ...OUT NOTICE Main Power Supply High Voltage High Voltage Terminal Block Circuit Breaker Low Voltage Terminal Block Low Voltage Terminal Block High Voltage Terminal Block Main Power Supply High Voltage C...

Page 11: ...at the isolators are easily accessible from the unit Connect the power cables to unit from isolator through the holes provided in the electrical panel of unit Route all control wires 24v or 240v separ...

Page 12: ...wiring at compressor terminal box Use tube cutter to cut suction and discharge lines at convenient place near compressor for easy reassemble to new compressor with copper slip Couplings if provided R...

Page 13: ...perly then replace it For other type of filters please refer the manufacturers instructions Condenser coil Inspect condenser coil regularly Clean it properly if found dirty or clogged A dirty or clogg...

Page 14: ...G A Drawing Indoor units VERTICAL HORIZONTAL MOUNTING POSITION YE2EU 072 TO 180 LAYOUT IS SUBJECT TO CHANGE WITHOUT NOTICE COMMERCIAL DUCTED SPLITS 16...

Page 15: ...G A Drawing Outdoor units YE2CE 072 SINGLE CIRCUIT UNITS COMMERCIAL DUCTED SPLITS 17...

Page 16: ...G A Drawing Outdoor units GA DRAWING SPACE CLEARANCE YE2CE072 R22 50HZ R22 60HZ R407C 50HZ UNITS COMMERCIAL DUCTED SPLITS 18...

Page 17: ...G A Drawing Outdoor units GA DRAWING SPACE CLEARANCE YE2CE090 216 R22 50HZ R22 60HZ R407C 50HZ UNITS COMMERCIAL DUCTED SPLITS 19...

Page 18: ...G A Drawing Outdoor units GA DRAWING SPACE CLEARANCE YE2CE240 300 R22 50HZ R22 60HZ R407C 50HZ UNITS COMMERCIAL DUCTED SPLITS 20...

Page 19: ...5 14 8 25 5 0 19 3 30 7 0 22 9 30 10 0 28 4 40 12 0 32 0 40 14 0 35 6 40 20 0 46 5 60 25 0 55 5 60 30 0 64 7 70 13 8 25 2 5 18 3 30 5 0 22 8 30 7 0 26 4 40 10 0 31 9 40 12 0 35 5 50 14 0 39 2 50 20 0...

Page 20: ...20 0 46 5 60 25 0 55 5 60 10 3 20 2 5 14 8 25 5 0 19 3 30 7 0 22 9 30 10 0 28 4 40 12 0 32 0 40 14 0 35 6 40 20 0 46 5 60 25 0 55 5 60 10 3 20 2 5 14 8 25 5 0 19 3 30 7 0 22 9 30 10 0 28 4 40 12 0 32...

Page 21: ...7 40 0 60 10 49 4 60 12 55 8 70 14 62 0 80 20 80 8 100 25 96 5 110 18 0 30 2 5 25 9 40 5 33 8 50 7 40 0 60 10 49 4 60 12 55 8 70 14 62 0 80 20 80 8 100 25 96 5 110 30 112 2 130 24 0 40 2 5 31 9 50 5 3...

Page 22: ...25 0 55 8 60 8 6 15 2 5 13 4 20 5 0 18 2 25 7 0 21 9 30 10 0 27 7 40 12 0 31 4 40 14 0 35 4 50 20 0 46 7 60 25 0 55 8 60 8 6 15 2 5 13 4 20 5 0 18 2 25 7 0 21 9 30 10 0 27 7 40 12 0 31 4 40 14 0 35 4...

Page 23: ...WIRING DIAGRAM OUTDOOR UNITS Unit Specifications COMMERCIAL DUCTED SPLITS 25...

Page 24: ...WIRING DIAGRAM OUTDOOR UNITS Unit Specifications WIRING DIAGRAM FOR OUTDOOR UNITS HEAT PUMP YE2CE072 YE2CE216 COMMERCIAL DUCTED SPLITS 26...

Page 25: ...WIRING DIAGRAM INDOOR UNITS Unit Specifications WIRING DIAGRAM FOR INDOOR UNIT HEAT PUMP ALL MODELS COMMERCIAL DUCTED SPLITS 27...

Page 26: ...WIRING DIAGRAM OUTDOOR UNITS Unit Specifications WIRING DIAGRAM FOR OUTDOOR UNITS COOL YE2CE240 YE2CE300 COMMERCIAL DUCTED SPLITS 28...

Page 27: ...WIRING DIAGRAM OUTDOOR UNITS Unit Specifications WIRING DIAGRAM FOR OUTDOOR UNITS COOL YE2CE072 YE2CE216 COMMERCIAL DUCTED SPLITS 29...

Page 28: ...Unit Specifications WIRING DIAGRAM INDOOR UNITS WIRING DIAGRAM FOR INDOOR UNITS COOL ALL MODELS COMMERCIAL DUCTED SPLITS 30...

Page 29: ...15154 3IAU15M04 3IAU15M02 3IAU15097 35 WIRING DIAGRAM 1BCO11580 1BCO11580 1BCO11580 1BCO11580 1BCO11580 1BCO11580 1BCO11666 1BCO11666 Spare Parts List INDOOR UNITS 380 420V 3PH 50HZ R22 S DESCRIPTION...

Page 30: ...DESCRIPTION PARTS COMMON YE2CE072E YE2CE090E YE2CE120E YE2CE150E YE2CE180E YE2CE216E YE2CE240E YE2CE300E 1 COMPRESSOR SCROLL 1BCC17041 1BCC09014 1BCC08016 1BCC17041 1BCC17062 1BCC17042 1BCC17044 1BCC...

Page 31: ...TDOOR UNITS 208 230V 3PH 60HZ R22 S DESCRIPTION PARTS COMMON YE2CE072T YE2CE090T YE2CE120T YE2CE150T YE2CE180T YE2CE216T YE2CE240T YE2CE300T 1 COMPRESSOR SCROLL 1BCC17019 1BCC10006 1BCC11023 1BCC17019...

Page 32: ...49 3IAU15019 3IAU15155 3IAU15153 3IAU15153 3IAU15M03 3IAU15M01 3IAU15096 34 COND COIL RHS 3IAU15150 3IAU15020 3IAU15156 3IAU15154 3IAU15154 3IAU15M04 3IAU15M02 3IAU15097 35 WIRING DIAGRAM 1BCO11580 1B...

Page 33: ...EXPLODED VIEW OF INDOOR UNIT YE2EU 072 090 120 150 180 216 240 ALL VOLTAGES COOL ELECTRIC HEATER HEAT PUMP EXPLODED VIEW INDOOR UNIT YE2EU 300 ALL VOLTAGES COOL ELECTRIC HEATER HEAT PUMP COMMERCIAL DU...

Page 34: ...Exploded View EXPLODED VIEW ODU YE2CE072 ALL VOLTAGES COOL HEAT PUMP EXPLODED VIEW OUTDOOR UNIT YE2CE 090 120 150 180 216 ALL VOLTAGES COOL HEAT PUMP COMMERCIAL DUCTED SPLITS 36...

Page 35: ...Exploded View EXPLODED VIEW OUTDOOR UNIT YE2CE240 300 ALL VOLTAGES COOL HEAT PUMP COMMERCIAL DUCTED SPLITS 37...

Page 36: ...mpressor Air in system Condenser coil dirty or restricted Dirty air filter Dirty condenser coil Refrigerant overcharged Air in system Condenser air restricted or air short cycling Low refrigerant char...

Page 37: ......

Reviews: