YORK INTERNATIONAL
OPERATING MODES
OPERATING MODES
The MicroComputer Control Center can be operated
in four different operating modes as follows:
SERVICE
enables all the
Service keys
except
DIS-
PLAY DATA, MANUAL OIL PUMP,
and
HISTORY
PRINT,
which are enabled in all modes. See Service
Keys, page 20.
LOCAL
This is the normal operating mode. The com-
pressor can be started and stopped from the Control
Center. Also, the
Display
and
Setpoints
parameters
can be displayed.
PROGRAM
Allows the operator to program the
Set-
points
parameters, and change operating modes.
REMOTE
In this mode, the Control Center will ac-
cept control signals from a remote device (i.e. Energy
Management System) or cycling input. The control sig-
nal inputs are:
1. Remote Start
2. Remote Stop
3. Remote LCWT Setpoint
4. Remove Current Limit Setpoint
NOTE: The compressor can be stopped by the
COM-
PRESSOR
switch, regardless of the operating
mode. The switch must be in
RUN
position to
enable
REMOTE
mode. The operator cannot
locally start the compressor using the
COM-
PRESSOR
switch when in the
REMOTE
mode.
To determine which operating mode the Control Cen-
ter is presently in, simply press the
MODE
key.
If the Control Center is in
LOCAL
mode,
LOCAL OPERATING MODE IN EFFECT
is displayed.
If the Control Center is in
REMOTE
mode,
REMOTE OPERATING MODE IN EFFECT
is displayed.
If the Control Center is in
SERVICE
mode,
SERVICE OPERATING MODE IN EFFECT
is displayed.
To change operating mode, proceed as follows:
1. Press
ACCESS CODE
key.
2.
ENTER VALID ACCESS CODE _ _ _ _
is displayed.
3. Using
Entry
keys, enter
9 6 7 5
.
4. As each digit is entered, the characters
Y O R K
are displayed.
NOTE: If digits other than
9 6 7 5
are entered,
Y O R K
is still displayed.
5. Press
ENTER
key.
NOTE: If digits other than
9 6 7 5
were entered in
step No. 4,
INVALID ACCESS CODE
is dis-
played when the
ENTER
key is pressed. If
this occurs, enter the correct access code
(9675)
and proceed.
6.
ACCESS TO PROGRAM KEY AUTHORIZED
is displayed.
NOTE: Unless terminated by pressing the
AC-
CESS CODE
key again, the operator will
have access to the
PROGRAM
key for 10
minutes. When 10 minutes have elapsed,
access to
PROGRAM
key will be automati-
cally disabled and the operator must return
to step No. 1 to gain access.
7. Press
PROGRAM
key.
8.
PROGRAM MODE, SELECT SETPOINT
is displayed.
9. Press
MODE
key.
10.The mode that has been previously selected will be
displayed as follows:
LOCAL MODE SELECTED
or
SERVICE MODE SELECTED
or
REMOTE MODE SELECTED
11. Press
ADVANCE DAY
key to scroll to desired mode.
Each time this key is pressed, a different mode is
displayed as above.
12.When the desired mode is displayed, press
ENTER
key.
13.
PROGRAM MODE, SELECT SETPOINT
is displayed.
14.Press
ACCESS CODE
key to exit
PROGRAM
mode
and terminate access to
PROGRAM
mode.
15.
ACCESS TO PROGRAM MODE DISABLED
is displayed.