York Millennium YCAR 0100SC Wiring Diagram Download Page 9

FORM 150.52-W1

9

YORK INTERNATIONAL

NOTES (pages 4 - 9)

1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all

other loads included in the circuit, per N.E.C. Article 430-24.  If a Factory Mounted Control Transformer is provided, add the following to
the system #2 MCA values in the YCAR Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.

2. The recommendation disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the

circuit, per N.E.C. 440 - 12A1.

3. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1).

Minimum fuse rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,

per N.E.C. 440-22.  Maximum fuse rating  = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

5. Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2.

Minimum circuit breaker rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit,

per U.L. 1995 Fig. 36.2.  Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + ( # fans x each
fan motor FLA).

7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs.  The (1), (2), or (3)

indicate the number of termination points or lugs which are available per phase.  Actual wire size and number of wires per phase must
be determined based on ampacity and job requirements using N.E.C. wire sizing information.  The above recommendations are based
on the National Electric Code and using copper connectors only.  Field wiring  must also comply with local codes.

8. A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54.  A control

circuit grounding lug is also supplied.  Incoming ground wire range is #6 - 350 MCM.

9. The field supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the

available power supply to perform maintenance and troubleshooting.  This disconnect is not intended to be a Load Break Device.

SYSTEM #1

SYSTEM #2

MODEL

VOLTS

COMPRESSOR DATA

FAN DATA

11, 12

COMPRESSOR DATA

FAN  DATA

11,12

YCAR

RLA

PW-LRA

X-LRA

QTY

FLA

LRA

   RLA

  PW-LRA

 X-LRA

QTY

FLA

LRA

 (EA.)

(EA)

(EA)

(EA)

380

116

429

552

3

4.8

23

116

429

552

3

4.8

23

0100SC

460

92

360

463

3

3.8

19

92

360

463

3

3.8

19

575

74

286

368

3

3.1

15.2

74

286

368

3

3.1

15.2

380

148

557

707

3

4.8

23

116

429

552

3

4.8

23

0110SC

460

117

461

585

3

3.8

19

92

360

463

3

3.8

19

575

94

375

475

3

3.1

15.2

74

286

368

3

3.1

15.2

380

148

557

707

3

4.8

23

148

557

707

3

4.8

23

0120SC

460

117

461

585

3

3.8

19

117

461

585

3

3.8

19

575

94

375

475

3

3.1

15.2

94

375

475

3

3.1

15.2

380

165

623

769

3

4.8

23

148

557

707

3

4.8

23

0130SC

460

131

519

641

3

3.8

19

117

461

585

3

3.8

19

575

105

415

513

3

3.1

15.2

94

375

475

3

3.1

15.2

380

165

623

769

4

4.8

23

165

623

769

4

4.8

23

0140SC

460

131

519

641

4

3.8

19

131

519

641

4

3.8

19

575

105

415

513

4

3.1

15.2

105

415

513

4

3.1

15.2

380

207

767

961

4

4.8

23

165

623

769

4

4.8

23

0150SC

460

164

639

801

4

3.8

19

131

519

641

4

3.8

19

575

131

507

635

4

3.1

15.2

105

415

513

4

3.1

15.2

380

207

767

961

4

4.8

23

207

767

961

4

4.8

23

0170SC

460

164

639

801

4

3.8

19

164

639

801

4

3.8

19

575

131

507

635

4

3.1

15.2

131

507

635

4

3.1

15.2

380

237

767

961

4

4.8

23

207

767

961

4

4.8

23

0180SC

460

188

639

801

4

3.8

19

164

639

801

4

3.8

19

575

150

507

635

4

3.1

15.2

131

507

635

4

3.1

15.2

380

237

767

961

5

4.8

23

237

767

961

5

4.8

23

0190SC

460

188

639

801

5

3.8

19

188

639

801

5

3.8

19

575

150

507

635

5

3.1

15.2

150

507

635

5

3.1

15.2

380

288

1105

1424

5

4.8

23

237

767

961

5

4.8

23

0200SC

460

228

910

1173

5

3.8

19

188

639

801

5

3.8

19

575

182

737

950

5

3.1

15.2

150

507

635

5

3.1

15.2

380

288

1105

1424

5

4.8

23

288

1105

1424

5

4.8

23

0230SC

460

228

910

1173

5

3.8

19

228

910

1173

5

3.8

19

575

182

737

950

5

3.1

15.2

182

737

950

5

3.1

15.2

Summary of Contents for Millennium YCAR 0100SC

Page 1: ...WIRING DIAGRAM Supersedes Nothing Form 150 52 W1 1299 YCAR0100 0230 MODELS 60 HZ STYLE A U L C U L 200 230 460 575 Models Millennium TM AIR COOLED RECIPROCATING LIQUID CHILLERS 28971AR ...

Page 2: ...n Diagram System Wiring Part Wind Start 21 Fig 13 Connection Diagram System Wiring Across The Line Start 22 Fig 14 Connection Diagram System Wiring Across The Line Start 23 WARNING HIGH VOLTAGE is used in the operation of this equipment DEATH OR SERIOUS INJURY may result if personnel fail to observe safety precautions Work on electronic equipment should not be undertaken unless the individual s ha...

Page 3: ...ATIONAL UNIT NOMENCLATURE YC A R 100 46 P A Chiller Design Level YC YORK Chiller Type Start P Part Wind Air Cooled CompressorType R Reciprocating Voltage Code 17 200 3 60 Unit Model 28 230 3 60 40 380 3 60 46 460 3 60 58 575 3 60 ...

Page 4: ...KCM 6AWG 350KCM 105 415 513 3 3 1 15 2 200 409 5 400 500 700 2 1 0 500KCM 2 3 0 250KCM 2 250KCM 500KCM 301 1187 1465 4 8 2 33 0 230 359 2 400 450 600 1 0 500KCM 2 3 0 250KCM 2 250KCM 500KCM 262 1038 1282 4 7 8 38 0 0140SC 380 225 9 250 300 350 1 0 500KCM 6AWG 350KCM 2 3 0 250KCM 165 623 769 4 4 8 23 0 460 179 4 200 225 300 1 0 500KCM 6AWG 350KCM 6AWG 350KCM 131 519 641 4 3 8 19 0 575 144 1 200 175...

Page 5: ...0 500KCM 2 3 0 250KCM 2 250KCM 500KCM 262 1038 1282 4 7 8 38 0 0140SC 380 225 9 250 300 350 1 0 500KCM 6AWG 350KCM 2 3 0 250KCM 165 623 769 4 4 8 23 0 460 179 4 200 225 300 1 0 500KCM 6AWG 350KCM 6AWG 350KCM 131 519 641 4 3 8 19 0 575 144 1 200 175 225 1 0 500KCM 6AWG 350KCM 6AWG 350KCM 105 415 513 4 3 1 15 2 230 359 2 400 450 600 1 0 500KCM 2 3 0 250KCM 2 250KCM 500KCM 262 1038 1282 4 7 8 38 0 01...

Page 6: ... 383 5 400 450 500 1 0 500KCM 250 KCM 500KCM 460 304 0 400 350 400 1 0 500KCM 250 KCM 500KCM 575 244 3 400 300 300 2AWG 300KCM 6AWG 350KCM 200 743 3 800 1000 1000 3 2AWG 300KCM 3 2 0 400KCM 230 652 4 800 800 800 2 1 0 500KCM 3 2 0 400KCM 0140SC 380 410 1 600 500 500 2 2AWG 300KCM 2 250KCM 500KCM 460 325 6 400 400 450 1 0 500KCM 250 KCM 500KCM 575 261 5 400 300 350 1 0 500KCM 250 KCM 500KCM 230 734...

Page 7: ...475 3 3 1 15 2 200 301 1187 1465 4 8 2 33 301 1187 1465 4 8 2 33 230 262 1038 1282 4 7 8 38 262 1038 1282 4 7 8 38 0140SC 380 165 623 769 4 4 8 23 165 623 769 4 4 8 23 460 131 519 641 4 3 8 19 131 519 641 4 3 8 19 575 105 415 513 4 3 1 15 2 105 415 513 4 3 1 15 2 230 328 1287 1602 4 7 8 38 262 1038 1282 4 7 8 38 0150SC 380 207 767 961 4 4 8 23 165 623 769 4 4 8 23 460 164 639 801 4 3 8 19 131 519 ...

Page 8: ...0 450 500 1 0 500KCM 250 KCM 500KCM 575 294 400 350 400 1 0 500KCM 250 KCM 500KCM 380 505 600 600 700 2 1 0 500KCM 2 250KCM 500KCM 0170SC 460 400 600 450 500 1 0 500KCM 2 250KCM 500KCM 575 320 400 400 450 1 0 500KCM 250 KCM 500KCM 380 542 600 700 700 2 1 0 500KCM 2 250KCM 500KCM 0180SC 460 430 600 500 600 2 2GA 300KCM 2 250KCM 500KCM 575 344 400 400 450 1 0 500KCM 250 KCM 500KCM 380 582 800 700 80...

Page 9: ...nd lug is provided for each compressor system to accommodate field grounding conductor per N E C Article 250 54 A control circuit grounding lug is also supplied Incoming ground wire range is 6 350 MCM 9 The field supplied disconnect is a Disconnecting Means as defined in N E C 100 B and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting Th...

Page 10: ...10 YORK INTERNATIONAL YCAR0100 0230 STANDARD DUAL COMPRESSOR POWER SUPPLIES ACROSS THE LINE START LD04950A FIG 1 STANDARD COMPRESSOR POWER SUPPLIES ACROSS THE LINE START ...

Page 11: ...FORM 150 52 W1 11 YORK INTERNATIONAL YCAR0100 0230 STANDARD DUAL COMPRESSOR POWER SUPPLIES PART WIND START LD04950B FIG 2 STANDARD COMPRESSOR POWER SUPPLIES PART WIND START ...

Page 12: ...12 YORK INTERNATIONAL YCAR0100 0230 ELEMENTARY DIAGRAM STANDARD REMOTE EVAPORATOR UNITS POWER CIRCUIT LD04948 FIG 3 ELEMENTARY DIAGRAM POWER CIRCUIT ...

Page 13: ...FORM 150 52 W1 13 YORK INTERNATIONAL YCAR0100 0230 ELEMENTARY DIAGRAM STANDARD REMOTE EVAPORATOR UNITS CONTROL POWER TRANSFORMER KIT LD04949 FIG 4 CONTROL POWERTRANSFORMER KIT ...

Page 14: ...IAGRAM CONTROL CIRCUIT FIG 5 ELEMENTARY DIAGRAM CONTROL CIRCUIT DETAIL A FIG 6 ELEMENTARY DIAGRAM CONTROL CIRCUIT DETAIL B ACROSS THE LINE START ACROSS THE LINE START PART WIND START LD04926 LD04927 FIG 7 ELEMENTARY DIAGRAM CONTROL CIRCUIT DETAIL B PART WIND START ...

Page 15: ... shown install the stop contact between terminals 5 and 1 If a stop device is not installed a jumper must be connected between terminals 5 and 1 Device must have a minimum contact rating of 6A at 115 volts A C 5 Contacts are rated at 115V 100VA resistive load only and must be suppressed at load by user 6 See Installation Operation and Maintenance Manual when optional equipment is used YCAR0100 023...

Page 16: ...ed with YORK P N 031 00808 000 suppressor across the relay contactor coil Any contacts connected to flow switch inputs or BAS inputs on terminals 13 19 orTB3 or any other termi nals must be suppressed with a YORK P N 031 00808 000 suppressor across the relay contactor coil Control wiring connected to the control panel should never be run in the same conduit with power wiring CONTROL POWER SUPPLY M...

Page 17: ... 150 52 W1 YORK INTERNATIONAL YORK INTERNATIONAL 17A 17 FORM 150 52 W1 YCAR0100 0230 WIRING DIAGRAM CONNECTION DIAGRAM CONTROL CIRCUIT YCAR0100 0230 WIRING DIAGRAM CONNECTION DIAGRAM CONTROL CIRCUIT LD04928 ...

Page 18: ...YCAR0100 0230 WIRING DIAGRAM CONNECTION DIAGRAM ELECTRICAL BOX YCAR0100 0230 WIRING DIAGRAM CONNECTION DIAGRAM ELECTRICAL BOX 17B YORK INTERNATIONAL 18 FORM 150 52 W1 YORK INTERNATIONAL LD04951 ...

Page 19: ...FORM 150 52 W1 19 YORK INTERNATIONAL YCAR0100 0230 WIRING DIAGRAM CONNECTION DIAGRAM ELECTRICAL BOX LD04953 FIG 10 CONNECTION DIAGRAM ELECTRICAL BOX ...

Page 20: ...0 YORK INTERNATIONAL YCAR0100 0230 WIRING DIAGRAM CONNECTION DIAGRAM SYSTEM WIRING PART WIND START LD04929 LD04930 LD04931 LD04932 LD04933 LD04934 FIG 11 CONNECTION DIAGRAM SYSTEM WIRING PART WIND START ...

Page 21: ...FORM 150 52 W1 21 YORK INTERNATIONAL YCAR0100 0230 WIRING DIAGRAM CONNECTION DIAGRAM SYSTEM WIRING PART WIND START LD04935 LD04936 LD04937 FIG 12 CONNECTION DIAGRAM SYSTEM WIRING PART WIND START ...

Page 22: ... INTERNATIONAL YCAR0100 0230 WIRING DIAGRAM CONNECTION DIAGRAM SYSTEM WIRING ACROSS THE LINE START LD04938 LD04939 LD04940 LD04941 LD04942 LD04943 FIG 13 CONNECTION DIAGRAM SYSTEM WIRING ACROSS THE LINE START ...

Page 23: ...RM 150 52 W1 23 YORK INTERNATIONAL YCAR0100 0230 WIRING DIAGRAM CONNECTION DIAGRAM SYSTEM WIRING ACROSS THE LINE START LD04944 LD04945 LD04946 FIG 14 CONNECTION DIAGRAM SYSTEM WIRING ACROSS THE LINE START ...

Page 24: ...U S Olympic Team 36USC380 P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by York International Corporation 1999 ALL RIGHTS RESERVED Form 150 52 W1 1299 Supersedes Nothing ...

Reviews: