Setpoint Limits (Setup Step 18)
Maximum Heat Setpoint (Setup Step 19) -
(35 - 99 ).
Minimum Cool Setpoint (Setup Step 20) -
(35 - 99 ).
When this feature is set to ON, the heat and cool setpoints can be restricted to preset
levels, set in steps 19 and 20.
Compressor Minimum Off Minutes (Setup Step 22)
This feature allows the user to set a minimum off time for the compressor. Settings are
5 mins., 3 mins., or 0 mins.
Number of Compressor Stages (Setup Step 24)
This feature is for heat pump application only.
This feature allows the thermostat to control 1 or 2 compressor stages when configured
for heat pump.
Minimum Heat/Cool Setpoint Difference(Setup Step 23)
This feature allows the user to set the minimum gap between Heat and Cool setpoints
in
AUTO
mode. Select from 0 to 6. If setup step 2 is not set for
AUTO-CHANGEOVER,
this step will not appear.
Cycles Per Hour (Setup Step 21)
The Cycles Per Hour setting may limit the number of times per hour
your HVAC unit may energize. For example, at a setting of 6 cycles
per hour the HVAC unit will only be allowed to energize once every 10
minutes. The Cycles Per Hour limit may be overridden and reset by
pressing the WARMER or COOLER buttons on the thermostat. Settings
are No Limit, 2, 3, 4, 5, or 6.
(This feature not available on all models)
Installer Setup
NOTE: When step 50 (Dual Fuel) is set to ON or EXTERNAL, this
step will not appear and Compressor Stages will automatically be set to 2.