548267-YIM-C-0211

Unitary Products Group

11

Compressors

The compressor used in this product is specifically designed to 
operate with R-410A Refrigerant and cannot be interchanged.

The compressor also uses a polyolester (POE oil), Mobil 3MA 
POE. This oil is extremely hydroscopic, meaning it absorbs 
water readily. POE oil can absorb 15 times as much water as 
other oils designed for HCFC and CFC refrigerants. Take all 
necessary precautions to avoid exposure of the oil to the 
atmosphere.

POE (polyolester) compressor lubricants are known to cause 
long term damage to some synthetic roofing materials.

Procedures which risk oil leakage include, but are not limited to, 
compressor replacement, repairing refrigerant leaks, replacing 
refrigerant components such as filter drier, pressure switch, 
metering device or coil.

Units are shipped with compressor mountings which are 
factory-adjusted and ready for operation.

Power And Control Wiring

Field wiring to the unit must conform to provisions of the current 
N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. 
The unit must be electrically grounded in accordance with local 
codes or, in their absence, with the N.E.C./C.E.C. Voltage 
tolerances which must be maintained at the compressor 
terminals during starting and running conditions are indicated 
on the unit Rating Plate and Table 5.

The wiring entering the cabinet must be provided with 
mechanical strain relief.

A fused disconnect switch should be field provided for the unit. 
If any of the wire supplied with the unit must be replaced, 
replacement wire must be of the type shown on the wiring 
diagram.

Electrical line must be sized properly to carry the load. Each 
unit must be wired with a separate branch circuit fed directly 
from the meter panel and properly fused.

Power Wiring

This heat pump is equipped to accept a single circuit of supply 
power. If an auxiliary heater is installed, dual circuiting to the 
unit can be used. When installing a 14.3 KW heater, this 
method will avoid the use of large wiring. To provide single 
circuiting, an optional jumper bar can be used to electrically 
connect the circuit breakers provided with the heater kit. 

If auxiliary electric heaters are not installed, refer to data sheet 
for minimum circuit ampacity and maximum overcurrent protec-
tive device size. If auxiliary electric heaters are being installed, 
refer to the installation instructions (included with heater pack-
ages) for electrical requirements and wiring information.

To wire this system without the use of auxiliary electric heat, 
remove the control box access door. 

1.

Remove side panel. Run power line service wiring into 
control box through the bottom knockout opening in the 
casing. (The two top knockouts are used when installing an 
auxiliary heater.)

2.

For single phase units - Connect one supply wire to L1 on 
the contactor, and the other supply wire to L2 on the 
contactor. Connect ground wire to ground lug in control 
box. See Figure 10.

3.

For three phase units - connect supply wires to L1, L2 and 
L3 on the contactor. Connect ground wire to ground lug in 
control box.

4.

Unless the heat pump is grounded through proper wiring to 
the service entrance ground terminal, a suitable separate 
ground must be provided at the air conditioner.

This system uses R-410A Refrigerant which operates at 
higher pressures than R-22. No other refrigerant may be 
used in this system.

Do not leave the system open to the atmosphere. Unit 
damage could occur due to moisture being absorbed by 
the 

POE oil

 in the system. This type of oil is highly 

susceptible to moisture absorption

Exposure, even if immediately cleaned up, may cause 
embrittlement (leading to cracking) to occur in one year 
or more. When performing any service that may risk 
exposure of compressor oil to the roof, take precautions 
to protect roofing.

Do not loosen compressor mounting bolts.

Summary of Contents for Latitude UQ024-060

Page 1: ...stat Wiring 12 12 Switch Installation 13 13 Defrost Operation Curves 14 General YORK Model UQ units are factory assembled heat pump designed to be installed along side the home or building Field insta...

Page 2: ...ce with the installation instructions and any applicable local state and national codes including but not limited to building electrical and mechanical codes Before performing service or maintenance o...

Page 3: ...zed procedures identified by the Air Conditioning Contractors of America Figure 1 Component Location Direct Drive Condenser Fan Motor High Efficiency Enhanced Copper Tube Aluminum Fin High Efficiency...

Page 4: ...on See Figure 2 7 Wind direction The hot condenser air must be discharged up and away from the home or building and if possible in a direction with the prevailing wind 8 Relationship between building...

Page 5: ...it operation Figure 3 Unit 4 Point Load Weight C X Y CG D A B Right Left Front Rear Size Tons Weight lbs Center of Gravity 4 Point Load Location lbs Shipping Operating X Y A B C D 024 2 0 328 325 21 7...

Page 6: ...NDENSATE DRAIN 3 4 NPT H Table 2 Unit Dimensions Size Tons Dimensions A B C D E F G H 024 2 0 32 13 16 30 15 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 030 2 5 32 13 16 30 15 16 47 1 4 12 9 16 8 1 2 24...

Page 7: ...nstalled first The return air grille box and filter should be located and installed in the out rigger areas of the home Keep in mind the closer to the cooling unit the better The return ducting connec...

Page 8: ...lar in the raw end of the duct and tape securely in place 4 Make sure the duct is not stretched tight and does not have kinks from excessive length after installation 5 Attach the duct end with the st...

Page 9: ...ster This will help to eliminate the transmission of sound into the home To locate the center of the duct first cut a 6 hole in the fiberboard below the duct at the desired location After locating the...

Page 10: ...air ducts passing through unconditioned spaces of the building must be insulated and covered with a vapor barrier Following this practice will prevent thermal losses and condensate formation on the du...

Page 11: ...pt a single circuit of supply power If an auxiliary heater is installed dual circuiting to the unit can be used When installing a 14 3 KW heater this method will avoid the use of large wiring To provi...

Page 12: ...er locate it in a room that is warmer or cooler than the rest of the home such as a kitchen or hallway 8 The living or dining room is normally a good location provided there is no cooking range or ref...

Page 13: ...f accessory heaters are not installed the blower will not run 9 Set the wall thermostat to the seasonal mode of operation heat or cool adjust the temperature selection lever to the desired setting Rec...

Page 14: ...forced defrost feature puts the system into a defrost period every 6 hours and 4 minutes to recirculate lubricants unless the coil temperature is above 40 F All defrost timing occurs only while the co...

Page 15: ...9 47 8 51 1 60 60 60 60 2PH08520706 4 9 6 5 1 23 5 27 1 55 6 60 1 60 70 60 70 2PH08521006 7 2 9 6 1 34 5 39 8 69 4 76 70 80 70 80 2PH08521506 10 8 14 3 1 51 7 59 7 90 9 100 9 100 110 100 110 208 230 3...

Page 16: ...oll Scroll Scroll Scroll Quantity 1 1 1 1 1 1 CONDENSER COIL DATA Face area Sq Ft 11 1 11 28 11 28 16 16 20 Rows 1 2 2 2 2 2 Fins per inch 20 15 20 15 15 20 Tube diameter in 3 8 3 8 3 8 3 8 3 8 3 8 Ci...

Page 17: ...2227 978 1086 1976 889 1129 1677 757 1151 048 4 0 Low 1260 275 807 1096 313 915 910 336 992 804 355 1057 774 290 979 Low Medium 1471 375 870 1338 415 968 1118 455 1079 963 474 1110 788 323 1016 Mediu...

Page 18: ...20 0 23 1200 0 21 0 21 0 21 0 22 0 25 1300 0 23 0 23 0 23 0 24 0 27 1400 0 25 0 25 0 25 0 26 0 29 1500 0 27 0 27 0 27 0 28 0 31 1600 0 29 0 29 0 29 0 30 0 33 1700 0 31 0 31 0 31 0 32 0 35 1800 0 33 0...

Page 19: ...ater kW 5 0 6 5 10 0 15 0 024 2 0 208 230 1 60 800 800 800 750 030 2 5 208 230 1 60 800 800 800 750 036 3 0 208 230 1 60 800 800 800 750 042 3 5 208 230 1 60 1300 1300 1270 1270 048 4 0 208 230 1 60 1...

Page 20: ...548267 YIM C 0211 20 Unitary Products Group Typical Wiring Diagrams UQ024 060 Typical Heat Pump 208 230 1 60 volt Wiring Diagram...

Page 21: ...548267 YIM C 0211 Unitary Products Group 21 UQ036 048 and 060 Typical Heat Pump 208 230 3 60 volt Wiring Diagram...

Page 22: ...ed in U S A 548267 YIM C 0211 Copyright 2011 by Unitary Products Group All rights reserved Supersedes 548267 YIM B 0910 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 UQ060 Typical...

Reviews: