background image

R-410A, 13 SEER
LATITUDE™ SERIES

      

   

      

UQ024-060

    

       

2-5 Ton

ISO 9001

Certified Quality

Management System

548267-YIM-C-0211

TABLE OF CONTENTS

General  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1
Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3

Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3
Unit Location  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4
Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4
Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

Installing Of Duct To Unit

(Manufactured Housing) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7

Supply and Return Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7
The Return — Air Grille Boxes. . . . . . . . . . . . . . . . . . . . . . . . . .  7
Wye Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8
Discharge Duct Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . .  9

Installing Of Duct To Unit (Residential)  . . . . . . . . . . . . . . . . . . . .  10
Installing Drain Tube And Connection  . . . . . . . . . . . . . . . . . . . . .  10
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  10

Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11

Power And Control Wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11

Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11
Control Wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  12

Wall Thermostat Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  12
Pre-start Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  13
System Startup, Check-out  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  13
Other Features Incorporated In The Control  . . . . . . . . . . . . . . . .  13

Anti-Short Cycle time Delay. . . . . . . . . . . . . . . . . . . . . . . . . . .  13
Safety Lock-Out. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  13

Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  17
Maintenance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  19

Normal Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  19

Typical Wiring Diagrams  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2

LIST OF TABLES

1

Unit Limitations  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   3

2

Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   6

3

Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   7

4

Demand Defrost Selection . . . . . . . . . . . . . . . . . . . . . . . . . . .   14

5

Electrical Data  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   15

6

Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   16

7

Airflow Performance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   17

8

Additional Static Resistance  . . . . . . . . . . . . . . . . . . . . . . . . .   17

9

Electric Heat Minimum Supply Air . . . . . . . . . . . . . . . . . . . . .   19

10

Indoor Blower Specifications . . . . . . . . . . . . . . . . . . . . . . . . .   19

11

Electric Heat Multipliers . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   19

LIST OF FIGURES

1

Component Location  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3

2

Air Discharge Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4

3

Unit 4 Point Load Weight  . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

4

Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

5

Return Air Box and Grille  . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7

6

Wye Installation (Outlet) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

7

Wye Installation (Inlet and Outlet)  . . . . . . . . . . . . . . . . . . . . .  9

8

Duct Connector (With Damper)  . . . . . . . . . . . . . . . . . . . . . . .   9

9

Duct Connector (No Damper)  . . . . . . . . . . . . . . . . . . . . . . . .   9

10

Unit Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . .   12

11

Thermostat Wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   12

12

Switch Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   13

13

Defrost Operation Curves  . . . . . . . . . . . . . . . . . . . . . . . . . .   14

General

YORK

®

 Model UQ units are factory assembled heat pump 

designed to be installed along side the home or building. Field-
installed electric heater accessories are available to provide 
supplemental electric heat.

The units are completely assembled on rigid base rails. All 
piping, refrigerant charge, and electrical wiring is factory 
installed and tested. The units require only electric power and 
duct connections at the point of installation.

The electric heaters have nickel-chrome resistance wire 
elements and utilize single point power connection.

Safety Considerations

This is a safety alert symbol  . When you see this symbol on 
labels or in manuals, be alert to the potential for personal injury.

Understand and pay particular attention the signal words 

DANGER

WARNING

 or 

CAUTION

.

DANGER

 indicates an 

imminently

 hazardous situation, which, 

if not avoided, 

will result in death or serious injury.

WARNING

 indicates a 

potentially

 hazardous situation, which, 

if not avoided, 

could result in death or serious injury.

CAUTION

 indicates a potentially hazardous situation, which, if 

not avoided 

may result in minor or moderate injury.

 It is also 

used to alert against unsafe practices and hazards involving 
only property damage.

Improper installation may create a condition where the 
operation of the product could cause personal injury or 
property damage. Improper installation, adjustment, 
alteration, service or maintenance can cause injury or 
property damage. Refer to this manual for assistance or 
for additional information, consult a qualified contractor, 
installer or service agency.

Summary of Contents for Latitude UQ024-060

Page 1: ...stat Wiring 12 12 Switch Installation 13 13 Defrost Operation Curves 14 General YORK Model UQ units are factory assembled heat pump designed to be installed along side the home or building Field insta...

Page 2: ...ce with the installation instructions and any applicable local state and national codes including but not limited to building electrical and mechanical codes Before performing service or maintenance o...

Page 3: ...zed procedures identified by the Air Conditioning Contractors of America Figure 1 Component Location Direct Drive Condenser Fan Motor High Efficiency Enhanced Copper Tube Aluminum Fin High Efficiency...

Page 4: ...on See Figure 2 7 Wind direction The hot condenser air must be discharged up and away from the home or building and if possible in a direction with the prevailing wind 8 Relationship between building...

Page 5: ...it operation Figure 3 Unit 4 Point Load Weight C X Y CG D A B Right Left Front Rear Size Tons Weight lbs Center of Gravity 4 Point Load Location lbs Shipping Operating X Y A B C D 024 2 0 328 325 21 7...

Page 6: ...NDENSATE DRAIN 3 4 NPT H Table 2 Unit Dimensions Size Tons Dimensions A B C D E F G H 024 2 0 32 13 16 30 15 16 47 1 4 12 9 16 8 1 2 24 1 16 12 2 3 4 030 2 5 32 13 16 30 15 16 47 1 4 12 9 16 8 1 2 24...

Page 7: ...nstalled first The return air grille box and filter should be located and installed in the out rigger areas of the home Keep in mind the closer to the cooling unit the better The return ducting connec...

Page 8: ...lar in the raw end of the duct and tape securely in place 4 Make sure the duct is not stretched tight and does not have kinks from excessive length after installation 5 Attach the duct end with the st...

Page 9: ...ster This will help to eliminate the transmission of sound into the home To locate the center of the duct first cut a 6 hole in the fiberboard below the duct at the desired location After locating the...

Page 10: ...air ducts passing through unconditioned spaces of the building must be insulated and covered with a vapor barrier Following this practice will prevent thermal losses and condensate formation on the du...

Page 11: ...pt a single circuit of supply power If an auxiliary heater is installed dual circuiting to the unit can be used When installing a 14 3 KW heater this method will avoid the use of large wiring To provi...

Page 12: ...er locate it in a room that is warmer or cooler than the rest of the home such as a kitchen or hallway 8 The living or dining room is normally a good location provided there is no cooking range or ref...

Page 13: ...f accessory heaters are not installed the blower will not run 9 Set the wall thermostat to the seasonal mode of operation heat or cool adjust the temperature selection lever to the desired setting Rec...

Page 14: ...forced defrost feature puts the system into a defrost period every 6 hours and 4 minutes to recirculate lubricants unless the coil temperature is above 40 F All defrost timing occurs only while the co...

Page 15: ...9 47 8 51 1 60 60 60 60 2PH08520706 4 9 6 5 1 23 5 27 1 55 6 60 1 60 70 60 70 2PH08521006 7 2 9 6 1 34 5 39 8 69 4 76 70 80 70 80 2PH08521506 10 8 14 3 1 51 7 59 7 90 9 100 9 100 110 100 110 208 230 3...

Page 16: ...oll Scroll Scroll Scroll Quantity 1 1 1 1 1 1 CONDENSER COIL DATA Face area Sq Ft 11 1 11 28 11 28 16 16 20 Rows 1 2 2 2 2 2 Fins per inch 20 15 20 15 15 20 Tube diameter in 3 8 3 8 3 8 3 8 3 8 3 8 Ci...

Page 17: ...2227 978 1086 1976 889 1129 1677 757 1151 048 4 0 Low 1260 275 807 1096 313 915 910 336 992 804 355 1057 774 290 979 Low Medium 1471 375 870 1338 415 968 1118 455 1079 963 474 1110 788 323 1016 Mediu...

Page 18: ...20 0 23 1200 0 21 0 21 0 21 0 22 0 25 1300 0 23 0 23 0 23 0 24 0 27 1400 0 25 0 25 0 25 0 26 0 29 1500 0 27 0 27 0 27 0 28 0 31 1600 0 29 0 29 0 29 0 30 0 33 1700 0 31 0 31 0 31 0 32 0 35 1800 0 33 0...

Page 19: ...ater kW 5 0 6 5 10 0 15 0 024 2 0 208 230 1 60 800 800 800 750 030 2 5 208 230 1 60 800 800 800 750 036 3 0 208 230 1 60 800 800 800 750 042 3 5 208 230 1 60 1300 1300 1270 1270 048 4 0 208 230 1 60 1...

Page 20: ...548267 YIM C 0211 20 Unitary Products Group Typical Wiring Diagrams UQ024 060 Typical Heat Pump 208 230 1 60 volt Wiring Diagram...

Page 21: ...548267 YIM C 0211 Unitary Products Group 21 UQ036 048 and 060 Typical Heat Pump 208 230 3 60 volt Wiring Diagram...

Page 22: ...ed in U S A 548267 YIM C 0211 Copyright 2011 by Unitary Products Group All rights reserved Supersedes 548267 YIM B 0910 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 UQ060 Typical...