background image

17

ENGLISH

EN

OPERATION TIPS

The following events may occur during normal operation.

1. Protection of the air conditioner.

Compressor protection

The compressor cannot restart for 3 minutes after it stops.
Anti-cold air (Cooling and heating models only)

The unit is designed not to blow cold air on HEAT mode, when the indoor heat exchanger is in one of the following
three situations and the set temperature has not been reached.
A)   When heating has just starting.
B)   Defrosting.
C)   Low temperature heating.

The indoor or outdoor fan stop running when defrosting (Cooling and heating models only).
Defrosting (Cooling and heating models only)

Frost may be generated on the outdoor unit during heat cycle when outdoor temperature is low and humidity is
high resulting in lower heating efficiency of the air conditioner.

During this condition air conditioner will stop heating operation and start defrosting automatically.

The time to defrost may vary from 4 to 10 minutes according to the outdoor temperature and the amount of frost
buildup on the outdoor unit.

2. A white mist coming out from the indoor unit.

A white mist may generate due to a large temperature difference between air inlet and air outlet on COOL mode
in an indoor environment that has a high relative humidity.

A white mist may generate due to moisture generated from defrosting process when the air conditioner restarts in
HEAT mode operation after defrosting.

3. Low noise of the air conditioner

.

You may hear a low hissing sound when the compressor is running or has just stopped running.
This sound is the sound of the refrigerant flowing or coming to a stop.

You can also hear a low “squeak” sound when the compressor is running or has just stopped running. This is
caused by heat expansion and cold contraction of the plastic parts in the unit when the temperature is changing.

A noise may be heard due to louver restoring to its original position when power is first turned on.

4. Dust in blown out from the indoor unit.

This is a normal condition when the air conditioner has not been used for a long time or during first use of the unit.

5. A peculiar smell come out from the indoor unit.

This is caused by the indoor unit giving off smells permeated from building material, from furniture, or smoke.

6. The air conditioner turns to FAN only mode from COOL or HEAT (For cooling and heating models only) mode.

When indoor temperature reaches the temperature setting on air conditioner, the compressor will stop automatically,
and the air conditioner turns to FAN only mode. The compressor will start again when the indoor temperature rises
on COOL mode or falls on HEAT mode (For cooling and heating models only) to the set point.

7.

Dripping water may generate on the surface of the indoor unit when cooling in a high relatively humidity (relative
humidity higher than 80%). Adjust the horizontal louver to the maximum air outlet position and select HIGH fan speed.

8. Heating mode (For cooling and heating models only)

The air conditioner draws in heat from the outdoor unit and releases it via the indoor unit during heating operation.
When the outdoor temperature falls, heat drawn in by the air conditioner decreases accordingly. At the same time,
heat loading of the air conditioner increases due to larger difference between indoor and outdoor temperature. If a
comfortable temperature cannot be achieved by the air conditioner, we suggest you use a supplementary heating
device.

9. Auto-restart function

Power failure during operation will stop the unit completely.
For the unit without Auto-restart feature, when the power restores, the OPERATION indicator on the indoor unit
starts flashing. To restart the operation, push the ON/OFF button on the remote controller. For the unit with Auto-
restart feature, when the power restores, the unit restarts automatically with all the previous settings preserved by
the memory function.

10.Lightning or a car wireless telephone operating nearby may cause the unit to malfunction.

Disconnect the unit with power and then re-connect the unit with power again. Push the ON/OFF button on the
remote controller to restart operation.

J174_lastRev4.pmd

3/14/05, 3:27 PM

17

Summary of Contents for HECB-HEHB 07-30

Page 1: ...ner s Manual MODELS HLCA HLHA 07 36 HECB HEHB 07 30 MINISPLIT HIGH WALL AIR CONDITIONER EN035M80000 000 The units comply with one or more of the following marks see unit for details J174_lastRev4 pmd 3 14 05 3 27 PM 1 ...

Page 2: ...n Quality POLICY We will continuously strive to satisfy our customers with consistent reliability in product service and support through superior quality service culture and distinctive technology R22 50 Hz R22 60 Hz R22 60Hz UL R407C 50 Hz Set HLCAxxFSAAAA HLCAxxFSAADA HLCAXXFSAAKF HECBxxFSAAAA HLHAxxFSAAAA HLHAxxFSAADA HLHAXXFSAAKF HEHBxxFSAAAA Outdoor HLDAxxFS AAA HLDAxxFS ADA HLDAXXFS AKF HEDB...

Page 3: ...on which may be dangerous and can cause injury Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel After unpacking please check the unit carefully for possible damage Before undertaking any work on the unit make sure that the power supply has been disconnected WARNING CAUTIONS Do not store or unpack the unit in a wet area or ex...

Page 4: ...splay panel Active Carbon Electrostatic Fiber Filter Standard DISPLAY PANEL OPERATION Indicator The indicator flashes once every second after power is on and illuminates when the air connditioner is in operation TIMER Indicator The indicator illuminates when TIMER is set ON PRE DEF Indicator For cooling heating model only The air conditioner starts defrosting automatically if outdoor unit frosts i...

Page 5: ...AUTO mode it will automatically select cooling heating cooling heating models only or fan only operation depending on what temperature you have selected and the room temperature The air conditioner will control room temperature automatically round the temperature point set by you If the AUTO mode is uncomfortable you can select desired conditions manually ECONOMIC OPERATION When you push ECONO but...

Page 6: ... and the main breaker capacity are sufficient and the installation area is sufficient and complies with the requirements Check that the power supply available agrees with name plate voltage Electrical work wiring and cables must be performed in compliance with national and local wiring codes and standard Do not use the extension cables In the case extended cables are needed use the terminal block ...

Page 7: ...10 62 590 750 HLDA HLJA 07 09 HEDB HEJB 07 09 HLDA HLJA 12 HEDB HEJB 12 HLDA HLJA 09 12 115V 60Hz UL HLDA HLJA 18 HEDB HEJB 18 HLDA HLJA 21 30 HEDB HEJB 21 30 HLDA HLJA 18 220 230V 60Hz UL HLDA HLJA 36 HEDB HEJB 36 HLDA HLJA 24 220 230V 60Hz UL 335 125 560 1 141 5 135 351 2 694 5 301 5 843 313 235 598 6 895 860 328 77 62 142 9 302 J174_lastRev4 pmd 3 14 05 3 27 PM 7 ...

Page 8: ...sition Drill a hole and mount installation plate After determining the pipe hole position drill the hole at a slight downward slant towards the outdoor side ø 65 mm Outdoor Indoor Note When installing the refrigerant pipes from others side A hole must be place to allow fall towards the outdoor unit 20 30 70 750 5 4 0 5 2 MODEL 07 09 12 220 240V 50 60Hz Indoor unit outline 15 cm or more to ceiling ...

Page 9: ...the left or the right side Verification of condensate water drainage Fill the drain pan with water and observe evacuation Note Do not put the drain hose end into water Drain hose For left and left rear piping Drain cap Drain cap For right and right rear piping CAUTIONS CAUTIONS 325 95 95 55 1250 815 257 178 55 58 55 Drain hose Wiring This indoor unit is ready for connection to the outdoor unit Nev...

Page 10: ...t Fix piping with pipe clamps and check that any pipe vibrations cannot be transmitted to the building structure Connect the pipe correctly Do not apply the excessive torque Use an appropriate bending tool to form curves and avoid over tightening the refrigerant tubes To prevent heat loss the two lines must be insulated separately Maximum Piping Length The suction line must have a 2 gradient up to...

Page 11: ...piping length of 5 meters Liquid Cooling GAS Cooling suction Low pressure High pressure Manifold Gas valve Liquid valve Pressure tap Outdoor Unit Indoor Unit Gas Line Liquid Line R22 R407C Outdoor heat pump unit install the unit at least 10 cm above ground level to facilitate drainage of defrost water and prevent accumulation of ice In effect defrost water can cause accumulation of ice under the u...

Page 12: ...on acceptance please refer to your contract with the power supplier if restrictions do apply for products like washing machines air conditioner or electrical ovens 4 For power details of the air conditioner refer to the rating plate of the product 5 For any question contact your local dealer Cautions Never modify the unit by removing any of the safety guards or by bypassing any of the safety inter...

Page 13: ...it Indoor Outdoor Indoor Outdoor Power supply 380 415V 3Ph 50Hz 430V 3Ph 60Hz Power supply 380 415V 3Ph 50Hz 430V 3Ph 60Hz Wiring Connection Model 07 21 Indoor Outdoor To outdoor unit Cooling Heating type Cooling only type Cooling Heating type Cord clamp 1 2 N 3 4 To outdoor unit To outdoor unit 1 2 N 3 4 1 2 3 4 L N G 1 2 3 4 Model 09 12 115V 60Hz UL Indoor Outdoor Terminal block of indoor unit T...

Page 14: ...7 A N A N Cooling Heating type Cooling only type Cord clamp Terminal block of indoor unit Terminal block of indoor unit Cooling only type Cooling Heating type Cord clamp Terminal block of outdoor unit Terminal block of outdoor unit A B C N 1 2 3 4 A B C N 1 2 3 4 5 6 7 1 2 N S 1 2 N S L N Model 18 24 220 230V 60Hz UL Indoor Outdoor To outdoor unit Terminal block of indoor unit Terminal block of ou...

Page 15: ...will switch to defrosting mode when either of the following conditions is met a Unit has been running under T3 0o C for 40 minutes and T3 3o C for 3 minutes b Unit has been running at high temperature protection mode for 90 minutes High temperature protection mode when coil temperature of indoor unit reaches 55 C outdoor unit will turn off external unit fan but still keep compressor running 2 Cond...

Page 16: ...e the batteries from the remote controller 3 The outdoor unit requires periodic maintenance and cleaning Do not attempt to do this yourself Contact your dealer or servicer Checks before operation Check that the wiring is not broken off or disconnected Check that the air filter is installed Check if the air outlet or inlet is blocked after the air conditioner has not been used for a long time Do no...

Page 17: ...unit This is a normal condition when the air conditioner has not been used for a long time or during first use of the unit 5 A peculiar smell come out from the indoor unit This is caused by the indoor unit giving off smells permeated from building material from furniture or smoke 6 The air conditioner turns to FAN only mode from COOL or HEAT For cooling and heating models only mode When indoor tem...

Page 18: ...sulate them separately together 3 The room was probably very hot 3 Wait while unit has enough time to cool when you star ted the cool the room system D The compressor run continuously 1 Thermostat adjustment too low 1 Check Thermostat setting in heating mode or too high in cooling mode 2 Faulty fan 2 Check condenser air circulation 3 Refrigerant charge too low leak 3 Find leak repair and recharge ...

Page 19: ...0 1370 1220 1740 1850 1900 2250 2450 2250 2450 2400 2450 2400 2450 220 240 1 50 or 380 415 3 50 1 1 1 1 1 1 1 1 380 350 320 450 420 390 550 500 460 750 710 650 800 760 700 1050 950 850 1150 1050 950 1350 1200 1050 36 5 53 65 63 60 68 65 62 72 67 63 85 80 77 0 17 0 26 0 317 0 38 250 286 330 325 750 906 1080 1250 188 235 222 230 8 5 13 5 17 18 Rotary 220 240 1 50 or 380 415 3 50 Indoor Unit Fan Pipi...

Page 20: ...7 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Rotary Scroll 535 540 590 695 700 780 760 845 235 250 285 335 27 28 32 30 34 36 43 44 50 55 58 60 67 69 3 8 1 2 5 8 1 4 1 4 3 8 Flare Nut Wireless Control with LCD Display R22 HLDA HLJA HLEA HLKA 220 230 1 60 220 230 1 60 220 230 1 60 Indoor Models Unit Outdoor Unit Power Supply V Ph Hz Ph Power Consumption W Running Current A Refrigerant Type Refrigerant Charge Noise...

Page 21: ...ations Ultra R22 60Hz UL Outdoor Unit Indoor Unit Wireless Control with LCD Display R22 HLDA HLJA HLDA09 HLDA12 HLDA18 HLDA24 HLEA HLKA HLEA09 HLEA12 HLEA18 HLEA24 115 1 60 220 230 1 60 115 1 60 220 230 1 60 115 1 60 220 230 1 60 Flare Nut Piping Fan Indoor Models Unit Outdoor Unit Power Supply V Ph Hz Ph Power Consumption W Running Current A Refrigerant Type Refrigerant Charge Noise level Indoor ...

Page 22: ...86 330 750 906 1080 188 235 222 8 5 13 5 17 1 1 1 1 1 1 1 3 1 1 1 1 1 1 1 Rotary Scroll 535 540 590 695 700 780 760 845 235 250 285 335 29 30 28 29 34 36 41 41 52 55 61 62 63 64 63 64 3 8 1 2 5 8 1 4 1 4 3 8 TECHNICAL SPECIFICATION Technical Specifications Eco Ultra R407C 50 Hz Outdoor Unit Indoor Unit Wireless Control with LCD Display R407C HEDB HEJB HEEB HEKB 220 240 1 50 or 380 415 3 50 220 240...

Page 23: ...e unit installation instructions for unit weight and correct methods of lifting Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above 4 4 4 4 4 After removal from position the unit parts may be disposed of according to local laws and regulations INSTALLATION REMOVAL AND DISPOSAL This product contains refrigerant under pressure rotating parts and ele...

Reviews: