TECHNICAL GUIDE 

COMMERCIAL

SPLIT-SYSTEM COOLING UNITS

FOUR PIPE SYSTEM

MODELS HB 180 & HB 240
MODELS LB 180 & LB 240
15 & 20 NOMINAL TONS
9.7  EER

                     

®  

GENERAL SPECIFICATIONS

OUTDOOR UNIT:

Two independent refrigerant circuits

Inherently protected fan motors

Two independent scroll compressors

V-Coil Design

Exterior service port connections

Refrigerant-22 holding charge

Five-minute compressor anti-short cycle timer

Two independent control circuits

Compressor operation to 40°F

Field-installed Low Ambient VFD Control to 0°F

Five-year limited warranty on compressor

One-year limited warranty on all other parts

Simplicity Controls

Factory installed disconnect and Technicoat coils

INDOOR UNIT:

Factory-mounted expansion valve and filter-drier in both 
refrigerant circuit

Adjustable TXV’s

Two-inch throwaway filters

Single point power connection

One-year limited warranty on all parts

Field installed drive packages

Summary of Contents for HB 180

Page 1: ...ice port connections Refrigerant 22 holding charge Five minute compressor anti short cycle timer Two independent control circuits Compressor operation to 40 F Field installed Low Ambient VFD Control to 0 F Five year limited warranty on compressor One year limited warranty on all other parts Simplicity Controls Factory installed disconnect and Technicoat coils INDOOR UNIT Factory mounted expansion ...

Page 2: ...40 22 13 LB180 SUPPLY AIR PLENUM DIMENSIONS 23 14 RETURN AIR GRILLE FOR LB180 DIMENSIONS 23 LIST OF TABLES Tbl Pg 1 UNIT APPLICATION DATA 7 2 ARI RATINGS COOLING AND SOUND 7 3 ELECTRICAL DATA COMPRESSORS 7 4 ELECTRICAL DATA FAN MOTORS 7 5 ELECTRICAL DATA OUTDOOR MCA MAX FUSE SIZE 7 6 OUTDOOR UNIT PHYSICAL DATA 8 7 INDOOR UNIT PHYSICAL DATA 8 8 CONNECTIONS 9 9 UNIT CLEARANCES 9 10 HB CORNER WEIGHTS...

Page 3: ...vertical applications the air velocity across the indoor coil keeps the condensate from dripping off the finned surface onto the filters NOTE On horizontal applications the unit must be installed with the condensate drain pan under the entire indoor coil NOTE The Supply Air Plenum and the Return Air Grille accessories can be used on either arrangement NOTE The Base accessory can only be used on th...

Page 4: ...oad operation Field installed Pump Out Kit for applications where liquid slugging could be an issue FIGURE 2 INDOOR PRODUCT NOMENCLATURE YORK INDOOR PRODUCT NOMENCLATURE H A 120 C 0 0 A 2 A A A 1 A Model Model Number Description Options H Product Category H Air Conditioner Split System E Heat Pump Split System A Product Identifier A R 22 Standard Efficiency 2 Pipe B R 22 Standard Efficiency 4 Pipe...

Page 5: ...s Base Sections are available to raise vertical indoor units above the floor Outdoor air may be introduced through these bases by cutting an access opening for the out door air duct connection These bases are finished to match the exterior of the basic unit They may have to be insulated in the field for certain applications Suspension Kit is available for indoor units installed hori zontally Manua...

Page 6: ... Unitary Products Group FIGURE 4 VERTICAL ARRANGEMENTS LB180 AND LB240 FIGURE 5 HORIZONTAL ARRANGEMENTS LB180 AND LB240 CERTAIN BLOWER POSITIONS ARE NOT RECOMMENDED BECAUSE THE BLOWER MOTOR SHOULD NOT BE MOUNTED UPSIDE DOWN ...

Page 7: ...ard 370 TABLE 3 ELECTRICAL DATA COMPRESSORS Model Number Compressors Power Supply System 1 System 2 RLA LRA RLA LRA HB180 208 230 3 60 25 6 190 0 25 6 190 0 HB180 460 3 60 12 8 95 0 12 8 95 0 HB180 575 3 60 10 2 75 10 2 75 HB240 208 230 3 60 42 0 239 0 42 0 239 0 HB240 460 3 60 19 2 125 0 19 2 125 0 HB240 575 3 60 13 8 80 13 8 80 TABLE 4 ELECTRICAL DATA FAN MOTORS Model Number Condenser Fans Power...

Page 8: ...ectly connected to the condenser fans Motor rotation is counterclockwise when viewing the lead end which is opposite the shaft end 3 The amount of charge in the unit as shipped from the factory 4 Total operating charge for the condensing unit matching indoor unit and 25 feet of interconnecting pipe TABLE 7 INDOOR UNIT PHYSICAL DATA Description Unit Model LB180 LB240 Coil Rows Deep X Rows High 3 X ...

Page 9: ...wer Wiring 2 1 8 KO 2 1 8 KO Control Wiring 7 8 KO 7 8 KO TABLE 9 UNIT CLEARANCES Location Dimensions Overhead Top 1 1 Units must be installed outdoors Overhanging structures or shrubs should not obstruct condenser air discharge 120 Front access panels 36 Left Side 30 Right Side 30 Rear 24 Bottom2 2 Adequate snow clearance must be provided if winter operation is expected 0 TABLE 10 HB CORNER WEIGH...

Page 10: ...ION LOCATIONS TABLE 11 PIPING AND ELECTRICAL CONNECTION SIZES CONNECTION ENTRY SIZE A SUCTION LINE SYS 1 1 1 8 ID 15 Ton 1 3 8 ID 20 Ton B LIQUID LINE SYS 1 5 8 ID C SUCTION LINE SYS 2 1 1 8 ID 15 Ton 1 3 8 ID 20 Ton D LIQUID LINE SYS 2 5 8 ID E POWER WIRING 2 KO F CONTROL WIRING 7 8 KO ...

Page 11: ... check the following 1 Suction line pressure drop due to friction at full capacity 2 Liquid line pressure drop due to friction at full capacity 3 Suction line velocity for oil return at part capacity and 4 Liquid line pressure drop due to static head NOTE Never base refrigerant line sizes on the OD of the suction and liquid connections on the unit Tables 13 and 14 list friction losses for both the...

Page 12: ...s should be sized for a friction loss equivalent to a 2 F change in saturation temperature or approximately 3psi sizing the lines for the proper return of oil is more important 5 These friction losses do not include any allowances for valves or fittings TABLE 14 LIQUID LINES Model Designation Nominal Capacity Tons Refrigerant Flow Rate1 Lbs Min Copper Tubing Inches O D Friction Loss2 3 PSI 100 Ft ...

Page 13: ...1 145 7 123 4 101 0 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 15 Ton Capacity Tables HB180 Matched with LB180 AIR ON EVAPORATOR OUTDOOR AMBIENT TEMPERATURE F 95 CFM W B GROSS INPUT 86 GROSS SENSIBLE CAPACITY MBh TEMP CAP POWER RETURN AIR DRY BULB TEMP F F MBh kW 83 80 77 74 71 68 4500 72 190 9 16 89 114 1 101 3 ...

Page 14: ...50 2 127 8 105 5 83 1 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 15 Ton Capacity Tables HB180 Matched with LB180 AIR ON EVAPORATOR OUTDOOR AMBIENT TEMPERATURE F 115 CFM W B GROSS INPUT 86 GROSS SENSIBLE CAPACITY MBh TEMP CAP POWER RETURN AIR DRY BULB TEMP F F MBh kW 83 80 77 74 71 68 4500 72 174 7 20 88 109 7 96 ...

Page 15: ... 5 127 3 112 1 97 0 81 8 57 150 4 22 0 150 4 147 6 138 6 123 5 108 3 93 1 78 0 6000 72 174 2 23 3 129 7 112 2 94 7 77 2 59 7 N A N A 67 160 1 22 7 159 4 141 9 124 4 106 9 89 4 71 9 54 4 62 149 2 22 1 149 2 149 2 149 2 135 4 117 9 100 4 82 9 57 153 8 22 2 153 8 153 8 148 8 131 3 113 8 96 3 78 8 6750 72 178 0 23 4 141 5 121 5 101 6 81 7 61 8 N A N A 67 163 6 22 7 163 3 153 5 133 5 113 6 93 7 73 8 53...

Page 16: ...189 8 162 4 134 9 Indicates Nominal Capacity Rating Point INPUT POWER INCLUDES THE CONDENSER AND COMPRESSOR MOTORS BUT NOT THE INDOOR BLOWER MOTOR 20 Ton Capacity Tables HB240 LB240 AIR ON EVAPORATOR OUTDOOR AMBIENT TEMPERATURE F 95 CFM W B GROSS INPUT GROSS SENSIBLE CAPACITY MBh TEMP CAP POWER RETURN AIR DRY BULB TEMP F F MBh kW 86 83 80 77 74 71 68 6000 72 253 7 23 11 151 3 134 2 117 0 99 9 82 8...

Page 17: ...R MOTORS BUT NOT THE INDOOR BLOWER MOTOR 20 Ton Capacity Tables HB240 LB240 AIR ON EVAPORATOR OUTDOOR AMBIENT TEMPERATURE F 115 CFM W B GROSS INPUT GROSS SENSIBLE CAPACITY MBh TEMP CAP POWER RETURN AIR DRY BULB TEMP F F MBh kW 86 83 80 77 74 71 68 6000 72 237 4 28 09 146 1 129 0 111 9 94 8 77 7 N A N A 67 219 5 27 31 180 8 163 7 146 6 129 5 112 4 95 3 78 2 62 205 4 26 78 205 4 193 2 176 1 159 0 14...

Page 18: ... 3 1 2 91 972 3 6 3 36 5600 688 1 9 1 76 776 2 4 2 24 859 2 9 2 68 924 3 3 3 05 981 3 8 3 56 5800 696 2 0 1 85 785 2 5 2 36 873 3 0 2 83 931 3 4 3 2 990 4 0 3 75 6000 647 1 9 1 78 704 2 1 1 95 794 2 7 2 48 885 3 2 2 98 938 3 6 3 36 998 4 2 3 94 6200 654 2 0 1 83 712 2 2 2 06 804 2 8 2 61 897 3 4 3 14 946 3 8 3 53 1007 4 4 4 14 6400 662 2 0 1 89 722 2 3 2 18 814 2 9 2 74 909 3 5 3 29 954 4 0 3 7 66...

Page 19: ...ON BLOWER PERFORMANCE 15 TON BLOWER PERFORMANCE 0 4 0 6 0 8 1 1 2 1 4 1 6 4200 4700 5200 5700 6200 6700 7200 7700 CFM ESP FIGURE 9 20 TON BLOWER PERFORMANCE 20 TON BLOWER PERFORMANCE 0 4 0 6 0 8 1 1 2 1 4 1 6 6000 6500 7000 7500 8000 8500 9000 9500 10000 CFM ESP ...

Page 20: ...08 1LD0437 800 1000 2LR04605032 184 230 460 1LD0437 800 1000 2LP04605058 184 575 1LD0437 800 1000 1LD0439 700 830 LB240 5 2LR04605023 184 208 1LD0438 580 720 1LD0439 700 830 2LR04605032 184 208 230 460 1LD0438 580 720 1LD0439 700 830 2LP04605058 184 575 1LD0437 800 1000 1LD0439 700 830 1 Three phase motors will always be wired for 460 volt power supply Refer to the wiring diagram inside the motor ...

Page 21: ...5 Ton Indoor Vertical 720 830 198 224 217 191 89 5 29 5 20 Ton Indoor Horizontal 990 1115 212 195 340 368 100 74 20 Ton Indoor Vertical 990 1115 281 254 276 305 100 36 5 FIGURE 10 HORIZONTAL APPLICATION CORNER WEIGHTS D C 20 Ton Motor Location Return Air A B Horizontal Application Corner Weights 15 Ton Motor Location Supply Air FIGURE 11 VERTICAL APPLICATION CORNER WEIGHTS Supply Air 15 Ton Motor ...

Page 22: ...CTION D D D E LESS BOTTOM PANEL BLOWER SECTION J L K K KNOCKOUT FOR SUCTION PIPING KNOCKOUT FOR LIQUID PIPING KNOCKOUT FOR DRAIN PIPING 4 9 16 10 3 16 2 7 32 19 3 32 3 1 2 5 25 64 3 3 8 5 1 3 8 Knockout for Liquid Piping 1 3 4 Hole for Suction Piping LB 240 Piping Connection Dimensions F G H 5 8 5 8 5 8 Panel TABLE 27 UNIT DIMENSIONS LB180 AND LB240 MODEL A B C D E F G H J K L M LB180 89 1 2 85 0 ...

Page 23: ...036 21323 002 C 0206 Unitary Products Group 23 FIGURE 13 LB180 SUPPLY AIR PLENUM DIMENSIONS1 1 Shipped knocked down for field assembly FIGURE 14 RETURN AIR GRILLE FOR LB180 DIMENSIONS ...

Page 24: ...ibration generated by the unit CONDENSER LA300 LB180 240 360 480 600 EACH UNIT SHALL BE ETL and cETL approved completely assembled for one piece shipping and rig ging leak pressure and functionally tested at the factory to assure a trouble free start up after installation covered by a 1 year limited parts warranty on the com plete unit EACH UNIT SHALL HAVE a steel angle frame to provide the rigid ...