TECHNICAL GUIDE

SPLIT-SYSTEM AIR CONDITIONERS
10 SEER
MODELS:
H*RA018 THRU 060
(1.5 THRU 5 NOMINAL TONS, 1 PH)
H*RA036 THRU 090
(3 THRU 7.5 NOMINAL TONS, 3 PH)

MODELS: 018 - 060 (1 PH & 3 PH)

MODELS: 076 - 090 (3 PH)

Due to continuous product improvement, specifica-
tions are subject to change without notice.
Visit us on the web at www.york.com for the most 
up-to-date technical information.
Additional rating information can be found at 
www.ariprimenet.org.

LISTED

This product was manufactured
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.

Certification applies only

when the complete

system is listed

with ARI.

R

N

E

M

P

I

U

Q

E

T

Y

R

AT

I

N

U

0

1

2

A R

I

R

A

D

N

A

T

S

D

I

S

N

O

T

C

E

S

F

O

C

C

I

F

I

T

R

E

N

O

I

T

A

HT

I

W

C

G N

I

YL

P

M

O

S

A

I

R

A

O

T

D

E

I

F

I

T

R

E

C

R

E

R

UT

C

A

F

U

N

A

M

C

-

G

NI

N O

I

TI

D

N

O

R

I

A

®  

036-21121-002 Rev. B (0103)

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

DESCRIPTION

The 10 SEER Series condensing unit is the outdoor part of a

versatile system of air conditioning. It is designed to be cus-

tom-matched with one of UPG’s complete line of evaporator
sections, each designed to serve a specific function. Match-

ing Air Handlers are available for upflow, downflow or hori-

zontal applications to provide a complete system. Electric
Heaters are available if required. Add-On coils are available

for use with upflow, downflow or horizontal furnaces and air

handlers.

WARRANTY

Single Phase Units:

5-year limited parts warranty.

5-year limited compressor warranty.

Three Phase Units:

1-year limited parts warranty.

5-year limited compressor warranty.

FEATURES

QUALITY CONDENSER COILS - 

The coil is constructed

of enhanced copper tube and aluminum fins.

COIL PROTECTION -

 Coils are protected from damage by

a polymer mesh applied between the coil face, and a PVC

coated steel coil guard.

PROTECTED COMPRESSOR - 

The compressor is inter-

nally protected against high pressure and temperature.
This is accomplished by the simultaneous operation of

high pressure relief valve and a temperature sensor which

protects the compressor if undesirable operating condi-
tions occur. A liquid line filter-drier further protects the

compressor.

DURABLE FINISH - 

The cabinet is made of pre-painted

steel. The pre-treated flat galvanized steel provides a bet-
ter paint to steel bond, which resists corrosion and rust

creep. Special primer formulas and matted desert sand fin-

ish insure less fading when exposed to sunlight.

LOWER INSTALLED COST - 

Installation time and costs

are reduced by easy power and control wiring connec-

tions. Discharge line heat exchanger knockouts are pro-

vided, if required. Available in sweat connect models only.
The unit contains enough refrigerant for matching indoor

coils and 15 feet of interconnecting piping. The small base

dimension means less space is required on the ground or
roof.

TOP DISCHARGE - 

The warm air from the top mounted

fan is blown up away from the structure and any landscap-

ing. This allows compact location on multi-unit applica-
tions.

LOW OPERATING SOUND LEVEL - 

The upward air flow

carries the normal operating noise up away from the living

area. The rigid top panel effectively isolates any motor
sound. Isolator mounted compressor and the rippled fins

of the condenser coil muffle the normal fan motor and

compressor operating sounds.

LOW MAINTENANCE - 

Long life permanently lubricated

motor-bearings need no annual servicing.

EASY SERVICE ACCESS - 

Fully exposed refrigerant con-

nections, a single panel covering the electrical controls

and the molex plug in the control box connecting the con-
denser fan, make for easy servicing of the unit.

SECURED SERVICE VALVES - 

Secured re-usable ser-

vice valves are provided on both the liquid and vapor

sweat connections for ease of evacuating and charging.

U.L. and C.U.L. 

listed - approved for outdoor application.

Certified in accordance with the Unitary Small Equipment cer-
tification program, which is based on ARI Standard 210/240.

Summary of Contents for H1RA018S06

Page 1: ...OR The compressor is inter nally protected against high pressure and temperature This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect...

Page 2: ...3 6 3 11 3 14 3 15 5 4 7 5 6 2 Charge Per Foot Oz 4 0 66 0 66 0 68 0 68 0 68 0 70 070 Operating Weight Lbs 118 123 135 137 161 176 188 Physical and Electrical Data 3 Phase MODEL H1RA 036S25 H1RA 042S2...

Page 3: ...G1NA036S17J 67 67 7 G1NA036S21C 67 67 7 G1NA048S21D 78 78 0 78 4 G1NA048S24P 78 78 0 78 4 G1NA060S24T 87 96 0 G1NF024SOF 63 57 0 3 63 4 3 G1NF036SOF 67 67 7 3 G1NF048SOF 78 78 03 78 4 3 G1NF060SOF 87...

Page 4: ...tems 3 PHASE ADDITIONAL R 22 CHARGE ORIFICE SIZE FOR VARIOUS MATCHED SYSTEMS Outdoor Unit H1RA036 H1RA042 H1RA048 H1RA060 H1RA076 H1RA090 Unit Orifice s 1 67 71 73 75 78 81 81 90 Factory R 22 Charge l...

Page 5: ...7 5 10 00 9 10 H2RA030S06 F2RP F2FP030 5 8 10 15 18 1000 28 4 21 0 10 00 9 50 F2RP F2FP036 5 8 10 15 19 21 1000 28 0 20 0 10 00 9 00 H2RA036S06 F2RC F2FC036 5 8 10 15 21 1200 33 6 21 5 10 00 9 10 F2RP...

Page 6: ...0 9 55 17 G2FD030 S H 17 850 25 0 18 5 10 60 9 65 14 G2FD035 S H 14 850 25 0 18 9 10 60 9 65 17 G2FD036 S H 17 850 25 6 18 9 10 70 9 70 H2RA030S06 875 1125 14 G1FA030S14 1000 28 0 20 7 10 00 9 30 14 G...

Page 7: ...9 2 10 00 9 00 17 G2FD046 S H 17 1380 40 0 29 6 10 00 9 05 21 24 G2FD048 S H 21 24 1450 41 0 30 3 10 10 9 15 H1RA048S06 1400 1800 17 G1FA048S17 1500 44 5 33 5 10 00 9 15 21 24 G1FA048S21 1600 45 5 33...

Page 8: ...0 62 7 4 32 56 9 5 38 50 2 5 61 H2RA030S06 35 61 5 25 1 2 68 20 3 2 97 17 0 3 17 H1RA060S 25 46 35 61 5 54 4 4 46 50 5 4 74 46 3 5 08 40 68 5 27 4 2 70 23 1 3 04 19 7 3 30 40 68 5 60 1 4 44 56 0 4 83...

Page 9: ...ase for 1H 1C 1H 1C manual change over electronic non programmable thermostat 1H 1C auto manual changeover electronic programmable deluxe 7 day thermostat 1H 1C auto manual changeover electronic progr...

Page 10: ...LER TERMINAL BLOCK ROOM THERMOSTAT CONDENSING UNIT ALL OUTDOOR WIRING MUST BE WEATHERPROOF USE COPPER CONDUCTORS ONLY TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT ALL FIELD WIRING TO BE IN ACCORDA...

Page 11: ...1 54 1 53 1 62 1 59 1 58 1 65 1 63 1 62 95 T C 19 0 17 5 15 5 19 5 18 0 16 1 19 8 18 2 16 5 S C 12 8 12 4 11 5 13 7 13 3 12 8 14 5 14 1 13 6 K W 1 97 1 91 1 90 2 02 1 96 1 95 2 05 2 00 1 99 105 T C 1...

Page 12: ...7 5 18 5 17 6 17 9 18 8 18 1 19 0 18 3 18 4 K W 2 42 2 28 2 06 2 06 2 44 2 20 2 20 2 08 2 34 2 32 2 21 1 99 105 T C 24 7 22 4 19 5 18 3 24 8 21 6 20 9 18 6 23 8 22 8 21 1 17 9 S C 16 8 16 8 15 3 16 9...

Page 13: ...2 27 1 24 4 S C 20 3 20 4 19 5 20 8 21 5 21 5 20 7 21 6 22 4 22 5 21 7 22 7 K W 3 07 2 98 2 91 2 81 3 15 3 07 3 00 2 92 3 25 3 16 3 10 2 99 105 T C 29 3 26 7 24 6 22 0 29 5 27 0 25 0 22 4 29 7 27 2 2...

Page 14: ...84 3 71 4 02 3 91 3 77 4 06 3 96 3 81 115 T C 31 0 27 6 23 5 31 1 28 2 24 2 31 3 28 5 24 4 S C 23 1 21 3 19 6 23 9 22 6 20 7 24 8 23 7 21 6 K W 4 22 4 06 3 90 4 29 4 13 3 94 4 33 4 18 4 00 125 T C 28...

Page 15: ...28 8 27 2 31 7 30 9 29 3 K W 4 58 4 44 4 30 4 74 4 60 4 47 4 89 4 77 4 64 115 T C 37 1 32 3 28 3 38 2 33 3 28 9 39 2 34 2 29 6 S C 26 8 25 1 23 3 29 0 27 2 25 4 31 1 29 4 27 4 K W 4 81 4 62 4 45 4 96...

Page 16: ...33 5 33 7 32 4 33 8 34 9 35 0 33 7 35 6 K W 4 91 4 70 4 51 4 31 5 02 4 81 4 64 4 43 5 13 4 92 4 74 4 53 105 T C 45 6 41 6 38 4 34 3 46 0 42 2 39 0 35 0 46 2 42 5 39 3 36 2 S C 30 5 30 6 29 5 30 9 32...

Page 17: ...41 2 39 2 39 7 38 2 36 5 K W 4 94 4 86 4 77 5 58 5 50 5 40 5 48 5 40 5 28 95 T C 60 9 57 3 52 7 60 4 56 0 51 5 59 9 54 7 50 3 S C 45 7 43 5 40 8 42 4 40 2 38 0 39 2 37 0 35 2 K W 6 19 6 10 6 00 6 09...

Page 18: ...58 4 55 85 T C 60 6 58 0 55 0 61 2 58 6 55 8 61 9 59 3 56 7 S C 37 6 37 3 36 5 40 2 39 9 39 1 42 8 42 5 41 7 K W 5 26 5 13 5 08 5 27 5 14 5 10 5 28 5 15 5 11 95 T C 60 0 57 4 53 7 60 7 58 5 54 8 61 4...

Page 19: ...6 18 6 15 6 58 6 48 6 46 85 T C 76 4 73 7 70 6 79 1 76 3 73 4 81 7 79 0 76 2 S C 47 9 47 6 46 8 54 7 54 4 53 5 61 5 61 2 60 3 K W 6 53 6 42 6 37 6 86 6 74 6 70 7 18 7 07 7 04 95 T C 73 8 71 1 67 2 76...

Page 20: ...8 36 8 29 8 23 85 T C 99 1 92 4 85 8 102 0 94 7 87 5 104 8 97 0 89 1 S C 72 5 67 4 62 3 74 0 68 4 62 8 75 5 69 4 63 4 K W 8 97 8 86 8 75 9 01 8 90 8 79 9 04 8 94 8 84 95 T C 94 0 87 7 81 5 95 8 89 0...

Page 21: ...DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1NA UNCASED UPFLOW G1FA FULL CASED UPFLOW G2FD090 is upflow only AIR HANDLERS FOR NON FURNACE APPL...

Page 22: ...036 21121 002 Rev B 0103 22 Unitary Products Group NOTES...

Page 23: ...036 21121 002 Rev B 0103 Unitary Products Group 23...

Page 24: ...nge without notice Printed in U S A 036 21121 002 Rev B 0103 Copyright by York International Corp 2003 All rights reserved Supersedes 036 21121 002 Rev A 0602 Unitary 5005 Norman Products York OK Grou...