background image

2.

Use the correct size fuse or circuit breaker as listed on the
unit rating plate and data sheet. See data sheet for mini-
mum recommended wire size. If using nonmetallic-
sheathed cable (NM or NM-B) ampacities shall be that of
60°C conductors per NEC 336-26.

3. Wiring 

connections.

Two are provided in the control box:

a. One for low voltage wiring.

b.  One entrance for high voltage Ll and L2

The reversible High Voltage Conduit Plate is factory

installed for 1/2" conduit connections. For 3/4" conduit,
remove the screw holding the plate in place and reverse
the location of the holes. For 1" conduit, remove the
conduit plate and discard. Re - install screw to maintain
the integrity of the unit structure, regardless of the
conduit being used. See Figures 3 and 4.

 4.  Power connection to the unit is facilitated by screw termi-

nals, marked Ll  and L2 on the outdoor unit contactor. See
Figures 3  and 4.

 5.  Ground the outdoor unit using the ground lug provided.

Unless the outdoor unit is grounded through proper wiring
to the service entrance ground, a suitable separate ground
should be provided at the outdoor unit.

C O N T A C T O R

S T A R T   R E L A Y

( N o t   o n   a l l   M o d e l s )

F A N

M O T O R

P L U G

D U A L

R U N   /   F A N

C A P A C I T O R

S T A R T

C A P A C I T O R

( N o t   o n   a l l   M o d e l s )

" F I N G E R E D "     B U S H I N G

G R O U N D   L U G

L O W

V O L T A G E

B O X

R E V E R S I B L E   H I G H   V O L T A G E   C O N D U I T   P L A T E

L1

L2

FIGURE 3 - TYPICAL CONDENSING UNIT CONTROL BOX

C O N T A C T O R

S T A R T   R E L A Y

( N o t   o n   a l l   M o d e l s )

F A N

M O T O R

P L U G

D U A L

R U N   /   F A N

C A P A C I T O R

S T A R T

C A P A C I T O R

( N o t   o n   a l l   M o d e l s )

" F I N G E R E D "  

    B U S H I N G

G R O U N D   L U G

L O W

V O L T A G E

B O X

R E V E R S I B L E   H I G H   V O L T A G E   C O N D U I T   P L A T E

L1

L2

FIGURE 4 - TYPICAL CONDENSING UNIT CONTROL BOX

(Start Components Shown)

(Start Components Shown)

550.46-N1YI

Unitary Products Group

5

Summary of Contents for H*RA Series

Page 1: ...ir Conditioning and Refrigeration Institute Using unmatched components may not only affect the performance of the system but may also void the warranty of the equipment Do not install any coil in a fu...

Page 2: ...tdoor coil can be eliminated by placing the outside unit where the wind does not blow across the unit Trees shrubs corners of buildings and fences standing off from the coil can reduce capacity loss d...

Page 3: ...and permitted to flow through tubing during brazing to displace air and prevent oxidation Remove the Schrader valve cores from the service valves Remove the plugs from the service valve field tubing c...

Page 4: ...d the refrigerantlines maybeconnectedpertheoutdoorunitinstruction However if another orifice should be used see the coil instruction for details to change to change the orifice in the coil OPENING BAS...

Page 5: ...Figures 3 and 4 5 Ground the outdoor unit using the ground lug provided Unless the outdoor unit is grounded through proper wiring to the service entrance ground a suitable separate ground should be pr...

Page 6: ...ned as follows 1 Determine outdoor unit charge from tabular data sheet 2 Determine indoor coil adjustment from tabular data sheet 3 Calculate the line charge using Table 2 factors Calculate over 15 fe...

Page 7: ...73 75 77 79 79 2 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 82 4 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Saturation Temperature TABLE 4 Temperature and Pressure TEMP F PRESSUR...

Page 8: ...orrectly SYSTEM OPERATION CHECK OUT STEP 1 With thermostat set to the OFF position close disconnect switch or switches to complete circuits to condens ing unit furnace or air handler Set thermostat to...

Reviews: