York GY8S*UH Series Technical Manual Download Page 4

278436-YTG-A-0407

4

Unitary Products Group

NOTES:

1. Airflow expressed in standard cubic feet per minute (CFM).

2. Motor voltage at 115 V.

BLOWER PERFORMANCE CFM - UPFLOW (WITHOUT FILTER) - BOTTOM RETURN

Models

Speed

Bottom Airflow Data (SCFM)

Ext. Static Pressure (in. H2O)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

(G,L)Y8S040A12UH11

High

1610

1540

1460

1360

1290

1200

1110

1020

900

760

Medium High

1430

1390

1330

1250

1190

1110

1030

940

840

710

Medium Low

1200

1180

1140

1100

1050

1000

930

850

750

620

Low

980

980

960

920

890

840

790

720

620

530

(G,L)Y8S060A12UH11

High

1570

1490

1420

1340

1250

1180

1090

990

870

700

Medium High

1410

1360

1310

1250

1190

1090

1020

920

810

650

Medium Low

1200

1180

1150

1100

1050

990

920

830

700

580

Low

960

960

950

930

900

840

800

720

610

500

(G,L)Y8S080A12UH11

High

1590

1520

1460

1380

1300

1240

1150

1050

930

800

Medium High

1400

1360

1310

1260

1200

1140

1070

960

860

740

Medium Low

1180

1160

1130

1090

1040

990

920

840

750

640

Low

940

940

940

920

880

840

790

710

630

530

(G,L)Y8S080B16UH11

High

1850

1820

1790

1750

1690

1630

1570

1500

1430

1330

Medium

1470

1450

1440

1430

1390

1360

1310

1270

1220

1150

Low

1260

1260

1260

1260

1250

1200

1150

1110

1070

1010

(G,L)Y8S080C16UH11

High

2077

1992

1922

1830

1727

1617

1507

1355

1219

1050

Medium

1729

1673

1631

1581

1507

1421

1293

1187

1053

907

Low

1448

1452

1432

1390

1324

1264

1176

1058

939

774

GY8S080C22UH11

LY8S080C20UH11

High

2490

2410

2320

2230

2130

2030

1900

1790

1630

1470

Medium High

2120

2060

2000

1970

1840

1730

1680

1570

1460

1260

Medium Low

1720

1700

1670

1620

1570

1500

1430

1310

1160

1000

Low

1410

1390

1360

1330

1280

1220

1170

1060

930

840

(G,L)Y8S100B12UH11

High

1700

1620

1560

1480

1390

1300

1210

1110

970

820

Medium High

1430

1400

1350

1300

1230

1160

1080

980

870

710

Medium Low

1180

1170

1160

1130

1080

1030

1000

860

750

510

Low

950

950

930

920

880

840

790

720

620

530

(G,L)Y8S100B16UH11

High

1880

1850

1770

1720

1650

1560

1490

1420

1320

1210

Medium

1470

1460

1420

1390

1360

1300

1250

1190

1110

1000

Low

1250

1240

1220

1190

1150

1130

1070

1030

970

880

(G,L)Y8S100C16UH11

High

2152

2075

1978

1888

1797

1677

1594

1459

1299

1158

Medium

1789

1717

1677

1648

1562

1487

1407

1288

1148

991

Low

1475

1471

1451

1423

1371

1309

1225

1123

1012

874

(G,L)Y8S100C20UH11

High

2590

2500

2400

2280

2180

2080

1970

1840

1720

1560

Medium High

2180

2120

2040

1980

1900

1810

1720

1600

1480

1320

Medium Low

1750

1720

1680

1640

1580

1520

1440

1350

1220

1060

Low

1450

1420

1380

1330

1300

1240

1160

1070

970

860

GY8S115C16UH11

High

2020

1930

1820

1730

1640

1540

1400

1250

1090

920

Medium

1750

1710

1650

1590

1490

1390

1290

1160

1010

810

Low

1540

1500

1460

1410

1350

1260

1180

1060

910

750

(G,L)Y8S115C20UH11

High

2500

2400

2320

2220

2110

2000

1870

1750

1610

1450

Medium High

2130

2070

1990

1920

1840

1760

1660

1570

1460

1320

Medium Low

1700

1680

1650

1620

1560

1500

1410

1320

1210

1070

Low

1420

1390

1360

1330

1290

1240

1150

1060

950

840

(G,L)Y8S130D20UH11

High

2640

2550

2440

2340

2230

2110

2010

1870

1750

1580

Medium High

2120

2070

2010

1950

1890

1810

1730

1610

1490

1320

Medium Low

1690

1660

1640

1600

1550

1490

1410

1330

1240

1100

Low

1370

1360

1340

1310

1270

1230

1150

1070

990

850

Summary of Contents for GY8S*UH Series

Page 1: ...hese units are Category I listed and may be common vented with another gas appliance as allowed by the National Fuel Gas Code WARRANTY 20 year limited warranty on the heat exchanger 10 year heat excha...

Page 2: ...L Y8S040A12UH11 1200 A 14 1 2 13 1 4 11 1 2 10 1 8 G L Y8S060A12UH11 1200 A 14 1 2 13 1 4 11 1 2 10 1 8 G L Y8S080A12UH11 1200 A 14 1 2 13 1 4 11 1 2 10 1 8 G L Y8S080B16UH11 1600 B 17 1 2 16 1 4 14...

Page 3: ...1600 17 1 2 12 0 80 0 35 65 G L Y8S100C16UH11 100 80 1600 21 12 0 80 0 35 65 G L Y8S100C20UH11 100 80 2000 21 14 0 80 0 25 55 GY8S115C16UH11 115 92 1600 21 12 0 80 0 35 65 G L Y8S115C20UH11 115 92 200...

Page 4: ...970 1840 1730 1680 1570 1460 1260 Medium Low 1720 1700 1670 1620 1570 1500 1430 1310 1160 1000 Low 1410 1390 1360 1330 1280 1220 1170 1060 930 840 G L Y8S100B12UH11 High 1700 1620 1560 1480 1390 1300...

Page 5: ...High 2710 2640 2560 2480 2360 2260 2160 2010 1860 1650 Medium High 2110 2110 2070 2030 1980 1910 1850 1710 1570 1300 Medium Low 1690 1690 1650 1610 1540 1480 1410 1280 1170 1030 Low 1350 1330 1310 129...

Page 6: ...ters may not exceed 300 feet per minute All velocities over this require the use of high velocity filters 2 Air flows above 1800 CFM require either return from two sides or one side plus bottom RECOMM...

Page 7: ...ool Y Y2 Single Second Stage Cool Y Single Stage Cool DN11C00124 C 24 Volt Common C 24 Volt Common Optional w Batteries BN11C01124 DP11C40124 PSC FURNACE CONTROL SINGLE STAGE AIR CONDITIONING BN11C001...

Page 8: ...CFM 33 4 m3 min Subtract the airflow 0 50 w c 125 Pa from the airflow 0 60 w c 150 Pa to obtain airflow difference 1180 1250 70 CFM 12 m3 min Subtract the total system static from 0 50 w c 125 Pa and...

Reviews: