Technical Guide

SPLIT-SYSTEM

EVAPORATOR BLOWERS

K2EU060, K4EU090, K3EU120 &

K3EU180

5 THRU 15 NOMINAL TONS

036-21300-002-A-0905

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

DESCRIPTION

These completely assembled units include a well-insulated cabinet, a
DX cooling coil with copper tubes and aluminum fins,  expansion
valve(s), distributor(s), throwaway filters, a centrifugal blower, a blower
motor, an adjustable belt drive, a blower motor contactor and a small
holding charge of refrigerant-22.

The units are shipped in the vertical position ready for field installation.
They can be installed for horizontal operation by reversing the position
of the solid bottom panel with the return air duct flange on the front of
the unit.

ACCESSORIES—FIELD INSTALLED

SUPPLY AIR PLENUMS

These fully insulated plenums are available for free standing units
located within the conditioned space, are shipped knocked-down for
easy field assembly, are finished to match the exterior of the basic
unit, and have double deflection grills that can be adjusted to vary the
throw, spread and drop of the supply air.

RETURN AIR GRILLS

These expanded metal grills are available for free standing units
located within the conditioned space, are finished to match the exterior
of the basic unit and are shipped in one piece for easy installation.

BASES

Bases are available to raise vertical units above the floor. Outdoor air
may be introduced through these bases by cutting an access opening
to accommodate the outdoor air duct connection. These bases are fin-
ished to match the exterior of the basic unit. They may have to be insu-
lated in the field for certain applications.

THREE-PHASE ELECTRIC HEATERS

Electric heaters are available in several capacities to provide maxi-
mum flexibility. Both the air conditioning unit and the heater can be
selected to precisely match the cooling and heating requirements of
the conditioned space. These heaters are designed for easy field
installation over the supply air opening of the unit. They have been
tested by and will be shipped with a CSA label. Every heater will be
fully protected against excessive current and temperature by fuses
and two high limit thermostats.

Units with electric heat will require only one power supply for both the
heating elements and the supply air blower motor, and the power wir-
ing can be protected by either dual element/time delay fuses or an
inverse time circuit breaker.

Summary of Contents for EVAPORATOR BLOWERS K2EU060

Page 1: ...RILLS These expanded metal grills are available for free standing units located within the conditioned space are finished to match the exterior of the basic unit and are shipped in one piece for easy...

Page 2: ...WITH ELECTRIC HEAT 25 LIST OF TABLES Tbl Pg 1 UNIT SUSPENSION MOUNTING HORIZONTAL APPLICATION WEIGHTS 5 2 KEU OPERATING WEIGHTS LBS 5 3 SOUND POWER RATINGS 6 4 HEATING CAPACITY ELECTRIC HEAT ACCESSORY...

Page 3: ...The hanger rods must be supplied by the field THERMOSTATS Wall mounted thermostats and subbases 24 volt with sys tem and fan switches are available to control the operation of these split system air c...

Page 4: ...Return Air Grill and Base acces sories can be applied on arrangement a The Return Air Grill and Base accessories can be applied on arrangement b The Supply Air Plenum Return Air Grill and Suspension a...

Page 5: ...Weight lb Operating Weight lb CG in 4 Point Loading lb X Y A B C D K EU060 225 210 22 50 15 00 47 51 58 53 K EU090 340 235 26 50 24 00 78 84 84 78 K EU120 370 355 26 50 24 00 86 92 92 86 K EU180 440 4...

Page 6: ...SHQVLRQ KDQQHOV DQJHU 5RGV LHOG 6XSSOLHG 2 6 7 21 2 5 6 7 21 5 7851 5 5 FFHVVRU QVWDOOHG 2Q 7KLV QG 2I 8QLW 6833 5 3 180 QG 75 7 5 FFHVVRULHV QVWDOOHG 2Q 7KLV QG 2I 8QLW 5 287 5 1 5HIHU WR 3DUW 1R IRU...

Page 7: ...4 2 46 4803 58 6004 2HS045036 25 208 2402 36 123 16 54 7 20 68 3 46 4803 58 6004 180 2HS045010 25 208 2402 10 34 2 10 34 2 46 2803 58 6004 2HS045016 25 208 2402 16 54 7 10 34 2 6 20 5 46 2803 58 6004...

Page 8: ...he following factors to correct for higher steam pressures Steam Pressure psig 5 10 15 20 25 Capacity correction factor 1 05 1 12 1 19 1 25 1 30 TABLE 6 HOT WATER CAPACITY1 MBH WATER COIL MODEL UNIT M...

Page 9: ...100 1286 1 38 1178 1380 1 48 1258 1468 1 57 3000 1076 1395 1 50 1152 1495 1 60 1230 1589 1 70 1311 1677 1 80 3200 1129 1622 1 74 1205 1721 1 85 1283 1815 1 95 CFM EXTERNAL STATIC PRESSURE 1 0 1 2 1 4...

Page 10: ...65 880 1667 1 79 944 1798 1 93 4400 792 1510 1 62 843 1629 1 75 901 1759 1 89 965 1890 2 03 4600 813 1599 1 72 864 1718 1 84 922 1848 1 98 986 1979 2 12 CFM EXTERNAL STATIC PRESSURE 1 0 1 2 1 4 1 6 RP...

Page 11: ...5200 861 2352 2 52 920 2562 2 75 972 2718 2 92 1022 2847 3 05 5400 884 2538 2 72 943 2748 2 95 995 2905 3 12 1045 3033 3 25 5600 907 2728 2 93 966 2939 3 15 1019 3095 3 32 1069 3224 3 46 CFM EXTERNAL...

Page 12: ...299 3 54 6800 690 2753 2 95 729 2991 3 21 768 3222 3 46 811 3456 3 71 7000 701 2915 3 13 740 3153 3 38 780 3384 3 63 823 3618 3 88 CFM EXTERNAL STATIC PRESSURE 1 0 1 2 1 4 1 6 RPM W BHP RPM W BHP RPM...

Page 13: ...0 0 04 0 08 0 13 0 19 0 10 0 10 0 33 0 43 5000 0 04 0 09 0 14 0 21 0 10 0 10 0 36 0 46 TABLE 14 STATIC RESISTANCE FOR UNIT ACCESSORIES IWG KEU180 CFM Electric Heat KW Supply Air Plenum Return Air Gril...

Page 14: ...12 62 97 38 57 21 11 47 73 76 115 12 6 4800 1230 94 147 35 53 23 12 68 106 41 62 21 11 51 80 85 127 12 6 180 4800 880 84 132 32 48 23 12 61 95 38 56 21 11 46 72 73 112 12 6 5400 1000 95 149 36 54 24 1...

Page 15: ...1 NPTE 1 3 8 O D Outlet Connection 1 NPTE 1 NPTE 1 NPTE 1 3 8 O D STEAM COIL Rows Deep 1 1 1 1 Finned Length in 30 46 46 54 Fins Per Inch 8 8 8 8 Face Area ft 2 3 8 5 4 5 4 9 0 Inlet Connection 1 1 2...

Page 16: ...Side with RETURN AIR opening 24 Side with SUPPLY AIR opening1 24 Side with PIPING CONNECTIONS2 36 Side opposite with PIPING CONNECTIONS 12 Side with access for both POWER CONTROL WIRING3 Bottom4 1 Ove...

Page 17: ...SITION DO NOT BLOCK THIS AREA WITH REFRIGERANT PIPING TABLE 19 UNIT CLEARANCES KEU090 120 MINIMUM CLEARANCES 090 120 Side with RETURN AIR opening 24 Side with SUPPLY AIR opening1 24 Side with PIPING C...

Page 18: ...s e d 7 8 K N O C K O U T F O R P O W E R W I R I N G D o n o t r e m o v e t h i s k n o c k o u t w h e n t h e u n i t i s e q u i p p e d w i t h a n E l e c t r i c H e a t A c c e s s o r y R e...

Page 19: ...ute the control wires through the 7 8 openings and connect them to the terminals on block TB1 Secure them with the 1 2 squeeze connec tors Electric Heaters are NOT CSA approved for installation within...

Page 20: ...36 090 120 180 27 1 4 25 1 4 14 1 4 1 4 1 2 5 1 2 1 1 2 1 1 2 22 1 4 19 1 4 2HS04507225 46 58 72 180 29 7 8 26 3 8 21 3 4 2 3 8 5 1 4 3 4 6 3 8 2 1 4 2 1 2 22 1 4 19 1 4 1 The 2HT heaters are not CSA...

Page 21: ...Installs between the coil and blower section of the unit 180 60 3 4 32 1 4 6 3 5 16 3 1 2 17 1 2 FIGURE 9 HOT WATER COIL 137 211 6 Coil Model Unit Model Hot Water Coil Dimensions inches A B C D E F G...

Page 22: ...2 5 85 7 90 2HS04503625 36 36 0 86 6 115 8 125 460 3 0 None 3 8 15 2HS04501046 10 10 0 12 0 18 8 20 2HS04501646 16 16 0 19 2 27 8 30 2HS04502646 26 26 0 31 3 42 8 45 2HS04503646 36 36 0 43 3 57 9 60 5...

Page 23: ...1025 10 10 0 24 1 42 1 45 2HS04501625 16 16 0 38 5 60 1 70 2HS04502625 26 26 0 62 5 90 2 100 2HS04503625 36 36 0 86 6 120 3 125 2HS04507225 72 72 0 173 2 228 5 250 460 4 8 None 6 0 15 2HS04501046 10 1...

Page 24: ...Y FIGURE 11 COOLING ONLY UNIT TERMINALS ON THERMOSTAT 6TH13700724 WITH SUB BASE 2TB08700124 TERMINAL BLOCK 4TB ON BLOWER UNIT 1 STAGE COOLING 24 VOLT CONTROL WIRING TO COND UNIT R R Y Y G G B TERMINAL...

Page 25: ...f i e l d w i r i n g c o n n e c t e d t o t h e s e d u m m y t e r m i n a l s o n 4 T B c a n b e r o u t e d d i r e c t l y f r o m t h e c o n d e n s i n g u n i t t o t h e t e r m o s t a t...

Page 26: ...036 21300 002 A 0905 26 Unitary Products Group...

Page 27: ...036 21300 002 A 0905 Unitary Products Group 27...

Page 28: ...o change without notice Printed in U S A 036 21300 002 A 0905 Copyright by Unitary Products Group 2005 All rights reserved Supersedes 036 21300 001 A 0901 Unitary 5005 Norman Products York OK Group Dr...

Reviews: