Installation of Floor And Ceiling Type Indoor Unit

4

Loosen two hanger bracket setting bolts (M8) on eath side for less than 10mm. Remove two hanger 

bracket fixing bolts (M6) on the rear side. Detach the hanger bracker by pulling it backward (Refer to Fig.5).

                                                         Fig.2                                                                       Fig.3

c.  Set the suspension bolt. (Use W3/8 or M10 size suspension bolts)

Adjust the distance from the unit to the ceiling slab beforehand. (Refer to Fig.4)

d.  Fix the hanger bracket to the suspension bolt.

 

Warning

Make sure that extended suspension bolt from the ceiling stays inside the arrowed position. Readjust 

the hanger bracket when it is outside the arrowed position. (Refer to Fig.6)

Suspension bolt stays inside the cap of indoor unit. Never remove the cap.

e.  Lift the unit and slide forward unit the dent. (Refer to Fig.7)
f.  Screw tightly both hanger bracket-setting bolts (M8). (Refer to Fig.5)
g.  Screw tightly both hanger bracket-fixing bolts (M6) to prevent the movement of the indoor unit. (Refer 

to Fig.5)

h.  Adjust the height so that rear side of the drainpipe slightly inclines to improve drainage.

Caution

Adjust the height by turning the nut with a spanner.

Insert the spanner from the hanger bracket opening. (Refer to Fig.8)

In case of hanging

It is possible to install using inward facing hanger brackets by not removing the brackets from the indoor 

unit. (Refer to Fig.9)

Be sure to use only the specified accessories and parts for installation work.

Summary of Contents for EOKC 09

Page 1: ...Johnson Controls Manufacturing Espa a S L is participating in the EUROVENT Certification Programme Products are as listed in the EUROVENT Directory of Certified Products in the program AC1 AC2 AC3 LC...

Page 2: ...door operating mode to make the operation normal The cooling mode is not clash with the dry mode while the fan mode is not clash with any mode The appliance shall not be installed in the laundry The a...

Page 3: ...pe Indoor Unit 6 1 Space dimension for installation of the unit 6 2 Important notice 6 3 There are 2 styles of installation 6 4 Electrical wiring 9 5 Install the drainage pipe 10 6 Install the connect...

Page 4: ...Do not mangle wire or adopts wires that are not recommend to use otherwise electric shock or fire may happened Please don t operate the unit by wet hand or electric shock may happened Don t insert fin...

Page 5: ...Installation Location Such a place where cool air can be distributed throughout the room Such a place where is condensation water is easily drained out Such a place that can handle the weight of indo...

Page 6: ...y malfunction caused by the unit that is installed by the department that is not special nominated by YORK would not deal with on time by the inconvenience of the business contact b It should be done...

Page 7: ...it is outside the arrowed position Refer to Fig 6 Suspension bolt stays inside the cap of indoor unit Never remove the cap e Lift the unit and slide forward unit the dent Refer to Fig 7 f Screw tight...

Page 8: ...ig 4 Fig 5 Hanger bracket setting bolt M8 Hanger bracket fixing bolt M6 Hanger bracket Fig 6 Fig 7 Fig 9 Fig 8 When installing the indoor unit you can refer the paper pattern for installation and make...

Page 9: ...the bottom of the appliance upward then connect the brown wire to the Terminal board 3 black wire the communication wire to the Terminal board 2 blue wire to the Terminal board N 1 and connect the ear...

Page 10: ...f the drainpipe should be equal to or greater than the diameter of the connecting pipe Keep the drain pipe short and incline downwards at a gradient of at least 1 100 to prevent air pockets Refer to F...

Page 11: ...nnection pipes Connect the connect pipe with the two relative leading pipe tie the nut on tie in of the connect pipe tightly Caution Be careful in bending the connection pipes or you will damage the p...

Page 12: ...tutes and Names of Every Part of Floor And Ceiling Type Indoor Unit Surface Panel Connecting pipe Air outlet Air inlet Guide louver Air filter purifier in air inlet grille Suitable model EOKC 09 R EOK...

Page 13: ...ure Range Working Temperature Range Indoor side state Outdoor side state Dry bulb temp Wet bulb temp Dry bulb temp Wet bulb temp Rated Cooling 27 19 35 24 Max cooling 32 23 48 26 Min cooling 21 15 18...

Page 14: ...essary 2 Cleaning the unit Clean the air conditioner and the remote control with dry cloth or a vacuum cleaner If damp cloth is used remove moisture by using dry cloth afterward Caution Do not use ben...

Page 15: ...to diffuse cool air Clean the air filter every week for higher efficiency by professional Close window and door while operating the unit to prevent leakage of cooled air and save energy Draw close cu...

Page 16: ...t should be done by professional Do not use pieces of wire instead of fuse Do not insert objects into the air inlet or outlet when the air conditioner is running as it may cause damage or personal inj...

Page 17: ...be operated by professional The cooling heating effect of the air conditioner is not good Is the temp set in proper Is the inlet outlet vent of outdoor unit blocked Is the air filter too dirty to caus...

Page 18: ...by johnson controls 18...

Page 19: ...000 6 3 EN61000 6 1 EN61800 3 EN ISO 9001 EN ISO 14001 2006 95 CEE 2004 108 CEE 97 23 CEE NORMAS INTERNACIONALES Y ESPECIFICACIONES T CNICAS APLICADAS Paseo Espronceda 278 08204 SABADELL TYPE EC STAND...

Page 20: ...www johnsoncontrols com...

Reviews: