254599-YTG-C-0807

10

Unitary Products Group

TABLE 6:  SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION

Unit

Tonnage

Air Flow

(CFM)

Available External Static Pressure - IWG

1

1. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for resis-

tance values on applications other than gas / electric units with side duct airflows.

0.2

0.3

0.4

0.5

0.6

0.7

0.8

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

6

2,3

2. 230/460/575 Volts
3. For 208 Volts multiply values by 0.95.

2500

1059

1560

1077

1590

1095

1630

1114

1650

1134

1660

1158

1685

1181

1720

2400

1032

1405

1054

1470

1074

1525

1094

1560

1116

1595

1140

1620

1167

1640

2300

1005

1260

1024

1275

1049

1370

1069

1440

1090

1475

1116

1505

1142

1535

2200

980

1160

1002

1170

1022

1190

1044

1250

1066

1350

1090

1410

1117

1440

2100

930

1060

957

1070

983

1080

1010

1100

1039

1160

1064

1260

1092

1340

2000

877

950

908

975

941

1000

976

1020

1009

1050

1040

1100

1070

1225

1900

-

-

-

-

894

885

940

940

980

980

1014

1020

1047

1095

1800

-

-

-

-

855

815

903

860

950

905

988

940

1022

970

1700

-

-

-

-

-

-

884

815

925

850

964

880

1001

910

1600

-

-

-

-

-

-

864

770

908

805

948

835

987

870

1500

-

-

-

-

-

-

-

-

882

740

926

780

965

830

Unit

Tonnage

Air Flow

(CFM)

Available External Static Pressure - IWG

1

0.9

1.0

1.1

1.2

1.3

1.4

1.5

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

6

2

,

3

2500

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2400

1193

1665

-

-

-

-

-

-

-

-

-

-

-

-

2300

1170

1580

1202

1620

-

-

-

-

-

-

-

-

-

-

2200

1148

1480

1180

1530

-

-

-

-

-

-

-

-

-

-

2100

1121

1385

1155

1425

1190

1475

-

-

-

-

-

-

-

-

2000

1100

1285

1133

1340

1169

1385

1205

1445

-

-

-

-

-

-

1900

1079

1180

1110

1240

1143

1280

1178

1330

1222

1375

-

-

-

-

1800

1058

1060

1090

1135

1122

1190

1158

1240

1196

1295

-

-

-

-

1700

1035

960

1071

1030

1103

1100

1134

1140

1164

1175

1197

1205

-

-

1600

1020

900

1056

965

1088

1035

1118

1065

1145

1105

1170

1130

1198

1150

1500

1004

860

1038

880

1070

925

1101

980

1130

1045

1158

1075

1184

1110

TABLE 7:  BELT DRIVE BLOWER MOTOR AND DRIVE DATA

MODEL

SIZE

BLOWER

RANGE

(RPM)

MOTOR

1

ADJUSTABLE MOTOR PULLEY

FIXED BLOWER PULLEY

BELT

(NOTCHED)

HP

FRAME

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

PITCH

LENGTH

(IN.)

QTY.

6 TON

850/1220

1 1/2

56

1VL40

2.7-3.7

2.4-3.4

5/8

AK56

5.4

5.2

1

A36

37.3

1

1. All motors have solid bases and are inherently protected.  these motors can be selected to operate into their service factor because they are located 

in the moving air, upstream of any heating device.

Summary of Contents for DF 072

Page 1: ...at meets ASTM B 117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertible Manufactured under the quality standards of ISO9001 Simplicity Control Board Copper tube aluminum fin coils Easy access to all components Rigging holes in base rails for lifting Fork lift slots on three sides Single point power connection Complete...

Page 2: ...WER RATING 8 2 CAPACITY RATINGS ARI 210 240 8 3 GAS HEAT RATINGS 8 4 2 STAGE GAS HEAT RATINGS 8 5 DF072 COOLING CAPACITIES 6 TON 9 6 SUPPLY AIR BLOWER PERFORMANCE 6 TON BELT DRIVE SIDE DUCT APPLICATION 10 7 BELT DRIVE BLOWER MOTOR AND DRIVE DATA 10 8 SUPPLY AIR BLOWER PERFORMANCE 6 TON BELT DRIVE SIDE DUCT APPLICATION 11 9 STATIC RESISTANCES 11 10 ELECTRIC HEATER CFM LIMITATIONS 11 11 ELECTRICAL D...

Page 3: ...an Configuration Options not required for all units These four digits will not be assigned until a quote is requested or an order placed CPC Controller DFS APS Johnson Controller DFS APS Honeywell Controller DFS APS Novar Controller DFS APS Simplicity IntelliComfort Controller Simplicity IntelliComfort Controller w ModLinc 2 Pleated filters BAS Ready Economizer 2 10 V D C Actuator without a Contro...

Page 4: ...rol board monitors the high and low pressure switches the freezestats the gas valve if applicable and the temperature limit switch on gas heat units The unit control board will alarm on ignition failures compressor lockouts and repeated limit switch trips Nuisance Trip Protection To prevent nuisance trouble calls the control board uses a three strikes you re out philosophy The high and low pressur...

Page 5: ...protection ELECTRIC HEATERS Wired for single point power supply These nickel chromium heater elements are pro vided with limit and automatic reset capability to prevent operation at excessive temperatures FILTER OPTIONS Standard units are shipped with 1 throw away filters installed 2 pleated filters are offered as a factory installed option CONVENIENCE OUTLET This 110 volt outlet can be powered by...

Page 6: ... installed Includes supply air sensor return air sensor dirty filter indicator switch and air proving switch HONEYWELL BAS CONTROL The Honeywell W7750C building automation system controller is factory installed Includes air supply sensor return air sensor dirty filter indicator switch and air proving switch SMOKE DETECTORS supply air return air The smoke detectors stop operation of the unit by int...

Page 7: ... propane HIGH ALTITUDE PROPANE Burner orifices and pilot orifices are provided for proper furnace operation at alti tudes up to 6 000 feet This accessory supplements the basic propane conversion kit LOW NOX KIT Required to reduce the emission of nitrogen oxides below 40 nanograms per joule POWER EXHAUST Our single input economizer options are available with power exhaust Whenever the outdoor air i...

Page 8: ... tee requiring a dBA value or sound data in any other form than sound power level ratings 2 At a distance of 10 feet from the blower TABLE 2 CAPACITY RATINGS ARI 210 240 1 1 80 67 F Indoor and 95 F outdoor MODEL MBH EER2 2 EER Energy Efficiency Ratio at full load the cooling capacity in Btu s per hour Btuh divided by the power input in watts expressed in Btuh per watt Btuh watt DF072 70 5 10 4 TAB...

Page 9: ...2 69 4 5 08 67 7 64 0 58 5 52 9 47 3 41 8 36 2 65 6 5 68 64 5 61 5 55 9 50 3 44 8 39 2 33 7 57 63 6 5 04 63 6 62 3 58 3 52 7 47 2 41 6 36 1 63 2 5 71 63 2 61 7 57 7 52 1 46 5 41 0 35 4 1650 72 77 5 21 41 6 36 9 32 2 27 5 22 8 74 5 5 85 39 8 35 1 30 4 25 7 21 0 67 73 6 5 12 52 7 48 0 43 3 38 6 33 9 29 2 24 5 69 9 5 73 51 0 46 3 41 6 36 9 32 2 27 5 22 8 62 67 3 5 06 64 0 59 3 54 6 49 9 45 2 40 5 35 ...

Page 10: ...1700 884 815 925 850 964 880 1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 Unit Tonnage Air Flow CFM Available External Static Pressure IWG1 0 9 1 0 1 1 1 2 1 3 1 4 1 5 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 62 3 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 1475 2000 1100 1285 1133 13...

Page 11: ... 2800 3000 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 0 26 0 30 7 15KW 0 04 0 05 0 06 0 07 0 08 0 10 0 12 0 14 0 16 0 19 0 22 20 30KW 0 06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 0 26 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 0 19 0 22 0 08 0 10 0 12 0 14 0 16 0 18 0 20 0 23 0 26 0 29 0 32 COOLING ONLY2 RESISTANCE IWG CFM DESCRIPTION ECONOMIZER1 3 BOTTOM DUCT CONNECTIONS1 ELECTRIC HEATER...

Page 12: ...5 9 15 3 21 6 25 2CE04512058 21 2 20 4 28 30 2CE04513058 30 4 29 3 39 1 40 1 HACR Type per NEC 2 These electric heaters do not include a fuse box If a fuse box is required to meet a local code i e Chicago the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation TABLE 12 ELECTRICAL DATA DF072 DIRECT DRIVE W O POWERED CONV OUTLET MODEL TONNAGE VOLTAGE COMPRESSORS O...

Page 13: ... 9 15 3 26 6 30 2CE04512058 21 2 20 4 33 35 2CE04513058 30 4 29 3 44 1 45 1 HACR Type per NEC 2 These electric heaters do not include a fuse box If a fuse box is required to meet a local code i e Chicago the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation TABLE 14 ELECTRICAL DATA DF072 DIRECT DRIVE W POWERED CONV OUTLET MODEL TONNAGE VOLTAGE COMPRESSORS OD F...

Page 14: ...LS Rows Deep 2 Fins Per Inch 18 Face Area Sq Ft 17 1 COMPRESSOR Qty Per Unit Recip Type 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 Quantity Per Unit 14 X 25 X 1 or 2 1 Total Face Area sq ft 6 3 CHARGE Refrigerant 22 lbs oz 11 10 TABLE 16 ELECTRIC HEAT CORRECTION FACTORS NOMINAL VOLTAGE VOLTAGE kW CAP MULTIPLIER 208 208 0 75 240 230 0 92 480 460 0 92 600 575 0 92 TABLE 17 VOLTAGE LIMITATION...

Page 15: ...OMIZER 3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE ELECTRIC HEATER OR 2 STAGE GAS HEAT 4 COOLING HEATING ELECTRONIC THERMOSTAT MULTI STAGE REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR P6 ON UNITS WITH ECONOMIZER TERMINALS A1 AND A2 PROVIDE A RELAY OUT PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE THERMOSTAT SWITCHES TO THE SET BACK POSITION RC Y R Y...

Page 16: ...254599 YTG C 0807 16 Unitary Products Group FIGURE 3 UNIT DIMENSIONS 6 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 6 TON COOLING GAS HEAT FRONT VIEW ...

Page 17: ...254599 YTG C 0807 Unitary Products Group 17 FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL A DETAIL B ...

Page 18: ...o the unit can be located by the side in the insulation Control Wiring2 2 Do not remove the 2 knockout ring Side Bottom B 2 KO1 Power Wiring Side Bottom C 1 5 8 KO Gas Piping Front D 1 1 2 KO Gas Piping Bottom TABLE 19 MINIMUM CLEARANCES LOCATION CLEARANCE Front 24 Cooling Electric Heat 32 Gas Heat Rear 12 Less Economizer 36 With Economizer or Fixed Air Motorized Damper Left Side Filter Access 24 ...

Page 19: ...254599 YTG C 0807 Unitary Products Group 19 FIGURE 9 TYPICAL APPLICATIONS ...

Page 20: ...A B C D E F DF072 Cooling Electric 660 147 144 183 186 98 97 96 122 123 125 DF072D06 710 158 155 197 201 105 104 103 131 132 134 DF072N08 720 160 157 200 203 107 106 104 133 134 136 DF072 D N 10 730 162 159 202 206 108 107 106 135 136 138 TABLE 21 CENTER OF GRAVITY DIMENSION 3 5 TON 6 TON X 40 44 Y 19 22 TABLE 22 DF OPERATING WEIGHTS LBS MODEL SIZE 6 TON BASIC UNIT DF Cooling Only 660 DF Gas Elect...

Page 21: ...tch and a suction line with a freezestat and low pres sure loss of charge switch The unit control circuit includes a 75 VA transformer a 24 volt circuit breaker and a relay board with a compressor lockout circuit a terminal strip for thermo stat wiring plus an additional set of pin connectors to simplify the interface of additional field controls All units have long lasting powder paint cabinets w...

Page 22: ... isolation and sound muf fling to minimize vibration and noise and be exter nally isolated on a dedicated independent mounting Coils a Evaporator and condenser coils shall have alumi num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed Special Phenolic coating shall be available as a factory option b Evaporator and Condenser coils shall be of the d...

Page 23: ...air dampers that are inter locked and positioned by a fully modulating spring return damper actuator The maximum leakage rate for the outdoor air intake dampers shall not exceed 2 when dampers are fully closed and operating against a pressure differential of 0 5 IWG A unit mounted potenti ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to...

Page 24: ...NUAL OUTDOOR AIR DAMPER COIL GUARD KIT Guard for cooling coil HAIL GUARD FLUE EXHAUST EXTENSION OTHER FACTORY INSTALLED OPTIONS POWER EXHAUST OPTION To work in conjunction with economizers STAINLESS STEEL HEAT EXCHANGER STAINLESS STEEL DRAIN PAN BOTTOM DRAIN CONNECTION TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL ELECTRONIC SINGLE ENTHALPY ECONOMIZER DIRTY FILTER SWITCH PHASE MONITOR C...

Reviews: