036-21187-001 REV A (0301)
Unitary Products Group
9
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE 8 TO 15 TON
MODEL
DHH
SUPPLY CFM
EXTERMAL STATIC PRESSURE - INCHES W.C.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BHP
RPM
BHP
096
3000
640
0.77
700
0.88
757
1.01
810
1.14
861
1.26
908
1.36
854
1.58
995
1.65
1088
1.80
3200
676
0.92
733
1.06
787
1.18
888
1.31
887
1.44
8.84
1.59
979
1.71
1020
1.95
1059
1.96
3400
710
1.08
764
1.22
816
1.38
885
1.48
812
1.64
858
1.78
1001
1.82
1043
2.07
-
-
120
3600
758
1.30
807
1.44
858
1.58
903
1.78
848
1.88
992
2.08
1034
2.18
1074
2.34
1118
2.48
4000
830
1.75
876
1.80
822
2.07
965
2.23
1007
2.38
1048
2.58
1087
2.72
1128
2.88
1168
3.05
4400
910
2.31
852
2.49
884
2.00
1084
2.84
1078
3.02
-
-
-
-
-
-
-
-
144
4300
688
1.31
745
1.48
788
1.65
847
1.83
885
2.02
841
2.21
888
2.40
1030
2.60
1075
2.80
4800
757
1.77
808
1.99
857
2.16
808
2.35
847
2.55
990
2.78
1031
2.97
1078
3.19
1133
3.41
5300
828
2.84
878
2.55
818
2.76
861
2.98
1002
3.20
1042
3.42
1081
3.64
1119
3.37
1157
4.11
180
5400
817
2.87
884
2.58
909
2.79
858
3.01
884
3.28
1034
3.45
1078
3.63
1111
3.91
1148
4.15
6000
888
3.20
842
3.43
983
3.67
1028
3.91
1062
4.15
1099
4.40
1136
4.94
1171
4.89
-
-
6600
878
4.20
1018
4.45
1057
4.71
1084
4.98
-
-
-
-
-
-
-
-
-
-
NOTE:
1. At higher evaporator airflows, and wet bulb conditions condensate carry-over may occur. Adjust airflow downward as necessary
2. Values include pressure drop from wet coil and clean filters
3. Shaded ares indicate oversized motors are required
TABLE 13: CONDENSER AIR BLOWER PERFORMANCE 2 TO 5 TON
MODEL
DHH
OUTDOOR
CFM
EXTERNAL STATIC PRESSURE - INCHES W.C.
0.2
0.4
0.6
0.8
1.0
1.2
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BPH
024
1400
731
0.23
842
0.29
946
0.36
1043
0.43
1133
0.50
-
-
036
1950
941
0.54
1024
0.62
1104
0.71
1182
0.80
1258
0.89
1320
1.05
048
2550
669
0.58
743
0.68
816
0.79
887
0.90
956
1.02
-
-
060
3300
826
1.17
885
1.30
942
1.42
999
1.56
1056
1.70
1112
1.85
TABLE 14: CONDENSER AIR BLOWER PERFORMANCE 8 TO 15 TON
MODEL
DHH
OUTDOOR CFM
EXTERNAL STATIC PRESSURE - INCHES W.C.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.8
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BPH
RPM
BHP
RPM
BHP
096
4800
757
1.77
808
1.96
857
2.18
903
2.35
947
2.55
880
2.76
1031
2.97
1073
3.19
120
5700
801
2.88
845
3.20
986
3.43
1026
3.66
1085
3.90
1103
4.13
1133
4.87
1175
4.62
144
6800
811
3.41
848
3.62
889
3.35
930
4.09
971
4.35
1010
4.61
1046
4.87
1087
5.14
Summary of Contents for D3HH 024
Page 12: ...036 21187 001 REV A 0301 12 Unitary Products Group FIGURE 1 2 TO 3 TON UNIT DIMENSIONS...
Page 13: ...036 21187 001 REV A 0301 Unitary Products Group 13 FIGURE 2 4 TO 5 TON UNIT DIMENSIONS...
Page 14: ...036 21187 001 REV A 0301 14 Unitary Products Group FIGURE 3 8 TO 10 UNIT DIMENSIONS...
Page 15: ...036 21187 001 REV A 0301 Unitary Products Group 15 FIGURE 4 12 TO 15 UNIT DIMENSIONS...