MOTOR AND PULLEY DATA

TABLE 4: STANDARD BLOWER MOTOR AND DRIVE DATA

TABLE 5:

OVERSIZE BLOWER MOTOR AND DRIVE DATA

BLOWER SPEED ADJUSTMENT

The RPM of the supply air and condenser air blowers will
depend on the required CFM, and the static resistances of
both the supply/discharge and the return/intake duct systems.
With this information, the RPM for the blowers can be deter-
mined from the blower performance tables. Adjustment of
blower speed is accomplished as follows:

a.

Loosen belt tension by moving motor towards the
blower shaft via the adjustable mounting.

b.

Loosen the setscrew in the adjustable motor pulley
flange. Remove external key on pulleys 4 in. dia and
larger.

c.

Slower speed will increase when moveable flange is
adjusted towards the fixed flange (closed). Blower
speed will decrease when the moveable flange is
adjusted away from the fixed flange (opened). Pul-
leys are adjustable only in half-turn increments. Do
not ODen Dullev more than five full turns for "4L"
and "A" belts. or six full turns for "B" belts.

d.

Once the pulley has been opened/closed the appro-
priate number of turns, replace the external key and
tighten the adjustment setscrew. Proper torque is
110-130 in.-Ibs.

e.

Install drive belt and adjust motor mount to tension
belt.

START-UP AND OPERATION

Start unit and check rotation of fans and compressors.

Scroll compressors will only compress in one rotational direc-
tion. Three phase compressors will rotate in either direction
depending upon phasing of the power. Since there is a 50-50
chance of connecting power in such a way as to cause rota-
tion in the reverse direction, it is important to ensure
proper rotation direction is achieved when the system is
installed and operated
.

Verification of proper direction is made by observing that suc-
tion pressure drops and discharge pressure rises when the
compressor is energized. Reverse rotation also results in an
elevated sound level as well as substantially reduced current
draw.

Model

Drive Range

(RPM)

Motor

Adjustable

Motor Pulley

Pitch Dia. (in.)

Fixed Blower

Pulley Pitch

Dia. (in.)

Belts

HP

Frame

Size

RPM

Eff.
(%)

Designation

Qty.

CU060

843-1167

1

143

1800

82.5

2.4-3.4

5.2

4L-330

1

CU096

632-875

1-1/2

145

1800

84.0

2.4-3.4

7.0

4L-410

1

CU120

659-913

2

145

1800

84.0

2.4-3.4

6.7

A38

1

CU180

724-925

3

182

1800

86.5

3.4-4.4

8.5

A38

1

CU240

806-1012

5

184

1800

87.5

4.4-5.6

9.9

B60

1

CU300

892-1098

7-1/2

213

1800

88.5

4.9-6.1

9.4

BX60

1

Model

Drive Range

(RPM)

Motor

Adjustable

Motor Pulley

Pitch Dia. (in.)

Fixed Blower

Pulley Pitch

Dia. (in.)

Belts

HP

Frame

Size

RPM

Eff.
(%)

Designation

Qty.

CU060

1034-1432

1-1/2

145

1800

84.0

2.4-3.4

4.2

4L-320

1

CU096

711-984

2

145

1800

84.0

2.4-3.4

6.2

A37

1

CU120

875-1118

3

145

1800

86.5

3.4-4.4

7.0

A40

1

CU180

938-1155

5

184

1800

87.5

4.9-6.1

9.4

A42

1

CU240

1010-1191

7-1/2

213

1800

88.5

5.3-6.3

9.4

B59

1

CU300

1033-1296

10

213

3600

88.5

4.4-5.6

15.4

BX70

1

PRIOR TO STARTING UNIT FOR THE FIRST
TIME, TURN THE THERMOSTAT SYSTEM
SWITCH TO OFF - OR RAISE THE COLLING
SETPOINT TO THE HIGHEST TEMPERATURE
TO PREVENT THE UNIT FROM STARTING,
THEN CLOSE THE ELECTRICAL DISCONNECT
SWITCH.

CAUTION

Summary of Contents for CU096

Page 1: ...ANUAL WATER COOLED AIR CONDITIONING UNITS MODELS CU060 096 120 180 240 300 036 33072 001 Rev A 0601 CONTENTS GENERAL 3 INSTALLATION 4 GENERAL DATA 5 DIMENSIONAL DATA 6 WATER PIPING 8 DUCTWORK 11 EVAPORATOR BLOWER DISCHARGE CONVERSION 12 ELECTRICAL WIRING 12 MOTOR AND PULLEY DATA 16 MAINTENANCE SERVICE 19 ...

Page 2: ...IONAL DATA 6 WATER PIPING 8 CONDENSOR PRESSURE CONTROL 9 DUCTWORK 11 SUPPLY AIR I RETURN AIR CONFIGURATION 11 EVAPORATOR BLOWER DISCHARGE CONVERSION 12 ELECTRICAL WIRING 12 MOTOR AND PULLEY DATA 16 BLOWER SPEED ADJUSTMENT 16 START UP AND OPERATION 16 MAINTENANCE SERVICE 19 FILTERS 19 EVAPORATOR AND CONDENSER COILS 19 BLOWERS 19 DRIVE BELTS 19 REFRIGERANT CIRCUIT S 19 Tables GENERAL UNIT INFORMATIO...

Page 3: ...ressure switches All models are equipped with an adjustable thermal expansion valve with external equalizer one valve per circuit Each refrigerant cir cuit is also equipped with a liquid line filter drier sight glass moisture indicator and service access ports An electrically re setable lock out relay will shut off the compressor in the event of pressure switch trip during operation Control circui...

Page 4: ... no leaks have occurred during shipment Install gauge set to high and low pressure ports to confirm pressure has been maintained and no leaks have occurred during shipment Repair any damage prior to installation to ensure safe operation NOTE Record any unit damage on the Bill of Lading and report to carrier and factory immediately Shipping and han dling damages are not warranty items RIGGING Units...

Page 5: ... these units outdoors or in any area where the surrounding temperature may drop below 32 degrees F LOCK ALL ELECTRICAL POWER SUPPLY SWITCHES IN THE OFF POSITION BEFORE INSTALLING THE UNIT FAILURE TO DISCON NECT POWER SUPPLY MAY RESULT IN ELEC TRICAL SHOCK OR EVEN DEATH WARNING Model CU060 CU096 CU120 CU180 CU240 CU300 Nominal Cooling Ton 5 8 10 15 20 25 Cooling Performance Gross Cooling Capacity B...

Page 6: ...036 33072 001 Rev A 0601 6 Unitary Products Group DIMENSIONAL DATA FIGURE 2 DIMENSIONS CU060 CU096 CU120 ...

Page 7: ...036 33072 001 Rev A 0601 Unitary Products Group 7 FIGURE 3 DIMENSIONS CU180 ...

Page 8: ...be provided on the water supply and return lines if noise and vibration trans mission could be a problem Water piping should include shutoff balancing valves so that the unit can be serviced without shutting down and draining the entire water supply circuit Since units are piped in paral lel piping circuits the shutoff valves may be used to equalixe the pressure drop to each branch for even conden...

Page 9: ...djusting screw clockwise will lower the opening point and lower the condensing pressure being maintained If mains water is being used make sure the valve closes soon after the compressor stops If the flow does not stop after a few minutes raise the opening pressure by turning the adjusting shaft caunter clockwise until the flow stops If the unit is running on mains water we recommend adjust ing th...

Page 10: ...036 33072 001 Rev A 0601 10 Unitary Products Group FIGURE 5 WATERSIDE PRESSURE DROP STANDARD UNIT MANIFOLDED CONDENSERS ...

Page 11: ...om the con ditioned space 5 15 ton models with optional return air grille or mechanical room 20 and 25 ton models If a ducted return is desired duct connection flanges may be secured directly to the air intake opening of the 5 through 15 ton units filters are accessible from the right hand side The filter frame on 20 and 25 ton models has duct attachment flanges incorporated into the filter rack S...

Page 12: ...tion In order to utilize the rear vertical or rear horizontal dis charge on 5 through 15 ton models the upper fan module must be rotated a Disconnect power wiring at motor terminal box b Remove corner connecting brackets which secure the blower module to the lower evaporator unit c Carefully lift the blower module and rotate 1800 Reposition the blower module on top of the evapora tor compressor un...

Page 13: ...s utilizing space or return air thermostatic controls A low volt age terminal block is provided for hook up of conventional or programmable thermostats The CU6300 25 ton models feature three independent com pressor stages A multi stage commercial thermostat ie Honeywell T7300 series or other type of multi step control ler is recommended for use with these models Alternatively two of the three comp...

Page 14: ...0 1800 64 65 31 20 25 23 80 40 30 CU240A 208 230 3 60 460 3 60 575 3 60 2 2 2 33 6 17 3 13 5 225 0 114 0 80 0 5 00 5 00 5 00 14 0 6 6 5 7 1800 1800 1800 89 60 45 53 36 08 110 60 45 CU300A 208 230 3 60 460 3 60 575 3 60 3 3 3 32 1 16 4 12 0 195 0 95 0 80 0 7 50 7 50 7 50 22 2 10 8 8 4 1800 1800 1800 126 53 64 10 47 40 150 80 50 MODEL VOLTAGE COMPRESSOR EVAPORATOR MIN CCT MAX FUSE QTY RLA LRA HP RLA...

Page 15: ... 77 760 1 91 797 2 05 837 2 21 878 2 38 919 2 54 960 2 70 1001 2 87 1040 3 05 CU180A 5400 645 1 52 709 1 79 770 2 06 829 2 35 885 2 65 939 2 96 991 3 28 1042 3 61 1092 3 96 1140 4 32 1190 4 71 6000 700 2 00 759 2 30 815 2 60 870 2 91 922 3 23 973 3 56 1022 3 90 1070 4 25 1116 4 62 1162 4 99 6600 761 2 63 815 2 94 867 3 26 917 3 60 966 3 94 1014 4 29 1060 4 66 1104 5 02 CU240A 7200 659 2 10 714 2 3...

Page 16: ...ll rotate in either direction depending upon phasing of the power Since there is a 50 50 chance of connecting power in such a way as to cause rota tion in the reverse direction it is important to ensure proper rotation direction is achieved when the system is installed and operated Verification of proper direction is made by observing that suc tion pressure drops and discharge pressure rises when ...

Page 17: ...rnal protector will trip If opposite rotation is needed disconnect and reverse any two leads of the three phase supply Reconnect power and observe for correct rotation Observe unit operation and check for unusual noise or vibra tion TABLE 6 REFRIGERANT CHARGES TABLE 7 PRESSURE SWITCH SETTINGS ALL Ref Charge 5 TON 8 TON 10 TON 15 TON 20 TON 25 TON No of Cir cuits 1 2 2 2 2 3 Per Circuit LB 4 625 4 ...

Page 18: ...036 33072 001 Rev A 0601 18 Unitary Products Group FIGURE 7 TYPICAL WIRING DIAGRAM 208 230V 3PH 60 HZ ...

Page 19: ...ew is properly set Check that the blower wheel is tight on the shaft and that the hub set screws are properly torqued DRIVE BELTS Examine belts periodically for wear Glazed areas on the drive surfaces indicate overheating due to belt slippage Ideal tension is the lowest tension at which the belt will not slip under peak load conditions Over tensioning shortens belt and bearing life The tension on ...

Page 20: ...ject to change without notice Printed in U S A 036 33072 001 Rev A 0601 Copyright by Unitary Products Group 2000 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 73069 ...

Reviews: