987158-UIM-B-1013
28
Johnson Controls Unitary Products
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0”
to 0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than
1.0” w.c. external static pressure is not recommended.
NOTE:
At some settings, LOW COOL airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Con-
sult the instructions for the electronic air cleaner for further details.
Table 13:
Blower Performance CFM - Any Position
High / Low Speed Cooling CFM
060A12 080B12
Jumper
Settings
Hi Cool
Lo Cool
Hi Cool
Lo Cool
COOL Jumper
ADJ Jumper
1340 900 1290 790 H
B
1125 750 1065 660 MH B
1225 820 1165 720 H
A
1050 680 960 600 MH A
1100 740 1050 590 H
C
890 600 855 525 ML B
920 615 875 540 MH C
675 450 640 395 L
B
815 545 775 495 ML A
600 440 580 380 L
A
720 499 700 430 ML C
540 440 525 380 L
C
High / Low Speed Cooling CFM
080C16 100C16
Jumper
Settings
Hi Cool
Lo Cool
Hi Cool
Lo Cool
COOL Jumper
ADJ Jumper
1715 1165 1600 1120 H
B
1520 1020 1450 980 MH
B
1575 1060 1500 1020 H
A
1395 930 1345 900 MH A
1430 950 1315 930 H
C
1320 875 1265 845 ML B
1260 840 1210 805 MH C
1100 730 1080 700 L
B
1200 795 1165 765 ML A
1000 665 980 635 L
A
1080 715 1050 695 ML C
900 600 885 585 L
C
High / Low Speed Cooling CFM
100C20 120C20
Jumper
Settings
Hi Cool
Lo Cool
Hi Cool
Lo Cool
COOL Jumper
ADJ Jumper
2110 1360 1990 1290 H
B
1670 1085 1760 1030 MH
B
1900 1235 1900 1210 H
A
1515 990 1510 935 MH A
1710 1130 1800 1095 H
C
1465 950 1540 900 ML B
1370 890 1440 845 MH C
1255 815 1320 790 L
B
1330 865 1400 835 ML A
1140 740 1200 725 L
A
1195 780 1260 750 ML C
1025 665 1080 650 L
C