Table A: Optional Setting Items for Function Selection
No.
Items
Optional Function
Individual
Setting
Setting
Condition
Contents
Setting
1
b1
Cancellation of Heating
Temperature Compensation
due to Uneven Heat Load
○
00
01
02
03
04
Standard (Set Temp. +7
o
F (+4
o
C))
Removal (Set Temp.)
Set Temp. +3
o
F (+2
o
C) (*1)
Set Temp. +5
o
F (+3
o
C)
Set Temp. +2
o
F (+1
o
C)
2
b2
Circulator Function during
Heating Thermo-OFF
○
00
01
Not Available
Available
3
b3
Not Prepared
-
-
Not Used (Use as 00 conditions)
4
b4
Change of Filter Cleaning Time
○
00
01
02
03
04
Standard 1,200 hrs (Factory-Setting)
100 hrs
1,200 hrs
2,500 hrs
No Indication
5
b5
Fixing of Operation Mode
×
00
01
Standard
Fixed
6
b6
Fixing of Setting Temperature
×
00
01
Standard
Fixed
7
b7
Fixing of Operation as
Exclusive Cooling Unit
×
00
01
Standard
Fixed
8
b8
Automatic COOL/HEAT Operation
×
00
01
Not Available
Available
9
b9
Fixing of Fan Speed
×
00
01
Standard
Fixed
10
bA
Not Prepared
-
-
Not Used
11
bb
Cooling Temperature Compensation
due to Uneven Heat Load
×
00
01
02
Standard (No Compensation)
Set Temp. –2
o
F (–1
o
C)
Set Temp. –3
o
F (–2
o
C)
12
bC
Not Prepared
-
-
Not Used (Use as 00 conditions)
13
bd
Not Prepared
-
-
Not Used (Use as 00 conditions)
14
bE
Not Prepared
-
-
Not Used (Use as 00 conditions)
15
C1
Not Prepared
-
-
Not Used (Use as 00 conditions)
16
C2
Not Prepared
-
-
Not Used
17
C3
Not Prepared
-
-
Not Used
18
C4
Not Prepared
-
-
Not Used
19
C5
Hi Speed
(Except for Hi Speed during Heating
Thermo-OFF)
○
00
01
02
Not Available
Hi Speed 1 (*2)
Hi Speed 2
20
C6
Hi Speed during Heating Thermo-
OFF
○
00
01
Not Available
Available
21
C7
Canceling of Enforced 3 Minutes
Minimum Operation Time of
Compressor
○
00
01
Standard
Cancelation
22
C8
Thermistor of Wired Controller
○
00
01
02
00
01
02
< If Wired Controller Thermistor is Selected
˃
Not Available
Control by Thermistor of Wired Controller
Control by Average Value of Indoor Suction
Thermistor and Thermistor of Wired Controller
< If Remote Sensor is Selected
˃
Control by Average Value of Indoor Suction
Thermistor and Remote Sensor
Control by Remote Sensor
Same as "00"
23
C9
Not Prepared
-
-
Not Used
24
CA
Not Prepared
-
-
Not Used
25
Cb
Selection of Forced Stoppage Logic
○
00
01
Forced Stoppage Input: A Contact
Forced Stoppage Input: B Contact
26
CC
Not Prepared
-
-
Not Used (Use as 00 conditions)
27
Cd
Not Prepared
-
-
Not Used (Use as 00 conditions)
28
CE
Not Prepared
-
-
Not Used (Use as 00 conditions)