background image

036-33073-001 Rev. A (0701)

4

Unitary Products Group

ELECTRICAL POWER SUPPLY AND
CONNECTIONS

Before installing the unit, make sure that the voltage and
number of phases on the unit data plate are the same as the
available power supply. A fused disconnect or circuit breaker
must be provided within the sight of anyone working on the
unit. The size of fuses or circuit breaker required is shown on
the unit data label. Fuses must be of the time delay type. The
power supply wiring is to be connected directly to the line
side of compressor contactor as shown on the connection
wiring diagram. A ground wire must be connected to the
ground lug marked GND in the electrical control box. A 7/8-
inch diameter hole is provided in the unit corner post for the
entry of the power wiring.

ROOM THERMOSTAT AND CONTROL
WIRING

Any cooling only 24-volt room thermostat can be used with
these units. It is recommended that the thermostat sub-base
should include a fan switch, so that constant fan operation
can be selected if desired. Three control wires are required
from the unit to the thermostat. It is preferred that the wires
be colored red, yellow, and green. Using these colors simpli-
fies connecting the red, yellow, and green terminals on the
thermostat to the red, yellow, and green terminals on the unit
low voltage terminal strip. Room thermostats can be ordered
as an optional accessory for delivery with the units if desired.

BLOWER PERFORMANCE

All units have blower motors that have three speeds avail-
able, except the 460 and 575-volt units. The motors have
been selected to deliver the nominal air volume against high
external static pressures when necessary. Therefore, it will be
necessary to check the air volume obtained on every installa-
tion and change the motor speed connection accordingly, if
the air volume is too high or too low. The units are factory-
wired with the medium speed winding connected.

Three methods are available to measure the air volume. The
preferred method is to measure the actual cubic feet per
minute of air being circulated, if suitable instruments for doing
this are available. Then if necessary, change the motor speed
to try to get the nominal air volume of 400 CFM per ton of
cooling capacity, within plus or minus 10 percent.

The second method is to measure the difference between the
supply and return air temperatures. The temperature differ-
ence should be in the range of 18°F to 25°F. If it is not, reduce
the motor speed if it is less than 18°F, and increase the motor
speed if it is more than 25°F .

The third method is to measure the external static pressure
obtained, and use the fan perfom1ance table for the unit. The

following performance tables are 230-volt operation. Slightly

lower air volumes will be obtained on 208-volt operation.

1.

At higher evaporator air flows and wet bulb conditions,
condensate carry-over may occur. Adjust airflow down-
ward as necessary.

2.

Values include pressure drop from wet coil and clean fil-
ters.

CONDENSER WATER SUPPLY AND
CONNECTIONS

The cooling water for the condenser may be from the mains,
a cooling tower, or a chilled water system. An automatic
water flow regulating valve is normally required, except if the
inlet water temperature is constant and the flow rate can be
pre-set and turned on and off by some other means, such as
a pump or solenoid valve.

Automatic water flow regulating valves are available as
accessories in either 3/8, 1/2, or 3/4-inch sizes and for maxi-
mum water pressure ratings of 150 PSI or 350 PSI. The fol-
lowing table shows the recommended valve size for each unit
model depending on the temperature of the water supply
available.

TABLE 2: EVAPORATOR BLOWER PERFORMANCE (CFM)

Unit

Model

Blower
Speed

External Static Pressure (in w.g.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

060

High

2200

2120

2040

1980

1880

1780

1660

Med.

2060

2020

1940

1880

1800

1700

1600

Low

1800

1780

1740

1680

1620

1560

-

048

High

1900

1840

1780

1720

1620

1540

1440

Med.

1720

1680

1640

1580

1520

1420

1320

Low

-

1405

1400

1380

1340

-

-

036

High

1420

1370

1310

1250

1180

1110

1020

Med.

1300

1260

1220

1170

1110

1040

960

Low

-

1120

1110

1070

1030

960

-

030

High

1240

1190

1130

1080

1010

930

850

Med.

1050

1030

1000

960

910

840

750

Low

-

9 25

910

880

830

770

-

024

High

1070

1020

970

920

850

770

690

Med.

930

910

880

840

780

710

630

Low

810

805

800

770

730

670

-

018

High

770

730

695

645

590

525

-

Med.

690

660

625

585

5 3 0

-

-

Low

520

500

495

-

-

-

-

012

High

480

455

425

400

365

325

-

Med.

425

410

380

350

315

-

-

Low

350

335

315

-

-

-

-

Summary of Contents for CH012

Page 1: ...CH036A06A1 CU036A06A1 3 CH036A25A1 CU036A25A1 3 CH048A06A1 CU048A06A1 4 CH048A25A1 CU048A25A1 4 CH060A06A1 CU060A06A1 5 CONTENTS INTRODUCTION 3 INSPECTION OF EQUIPMENT 3 SELECTION OF INSTALLATION LOC...

Page 2: ...ARNING CAUTION CONTENTS INTRODUCTION 3 INSPECTION OF EQUIPMENT 3 SELECTION OF INSTALLATION LOCATION 3 CLEARANCES REQUIRED 3 CHECKING THAT THE UNIT IS LEVEL 3 UNIT MOUNTINGS 3 DUCT CONNECTIONS 3 ELECTR...

Page 3: ...possible When deciding where to locate the unit the following require ments must be considered 1 Power wiring to the correct power source for the unit 2 Condenser water supply and return piping 3 Con...

Page 4: ...change the motor speed to try to get the nominal air volume of 400 CFM per ton of cooling capacity within plus or minus 10 percent The second method is to measure the difference between the supply and...

Page 5: ...gulating valve needs to be adjusted to maintain a leaving water temperature between 90 F and 100 F If using a refrigerant discharge pressure gauge adjust the water valve to maintain a condensing press...

Page 6: ...ety lock out it will be necessary to interrupt the power to the control circuit This can be done at the thermostat or at the disconnect MAINTENANCE The air circulating fan motor has bearings that are...

Page 7: ...036 33073 001 Rev A 0701 Unitary Products Group 7 FIGURE 1 W C UNITS 208 230V 3PH 60HZ...

Page 8: ...036 33073 001 Rev A 0701 8 Unitary Products Group FIGURE 2 W C SINGLE PHASE UNITS 208 230V 1PH 60HZ...

Page 9: ...036 33073 001 Rev A 0701 Unitary Products Group 9 FIGURE 3 W C AIR CONDITIONERS ELECTRICAL DATA...

Page 10: ...036 33073 001 Rev A 0701 10 Unitary Products Group FIGURE 4 HORIZONTAL WATER COOLED UNITS DIMENSIONAL DATA...

Page 11: ...036 33073 001 Rev A 0701 Unitary Products Group 11 FIGURE 5 VERTICAL WATER COOLED UNITS DIMENSIONAL DATA...

Page 12: ...ect to change without notice Printed in U S A 036 33073 001 Rev A 0701 Copyright by Unitary Products Group 2000 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7...

Reviews: