![York BP 036 Technical Manual Download Page 16](http://html1.mh-extra.com/html/york/bp-036/bp-036_technical-manual_3658898016.webp)
255027-YTG-B-0507
16
Unitary Products Group
TABLE 9:
SUPPLY AIR BLOWER PERFORMANCE (BP036 BELT DRIVE) - BOTTOM DUCT APPLICATION
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
1
0.2
0.3
0.4
0.5
0.6
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
800
-
-
-
-
-
-
-
-
-
749
384
0.41
791
422
0.45
900
-
-
-
-
-
-
720
364
0.39
764
404
0.43
806
443
0.47
1000
-
-
-
690
346
0.37
739
388
0.42
783
429
0.46
824
467
0.50
1100
657
334
0.36
711
376
0.40
760
417
0.45
804
458
0.49
845
497
0.53
1200
681
369
0.40
735
410
0.44
784
452
0.49
828
493
0.53
869
532
0.57
1300
707
409
0.44
761
451
0.48
809
493
0.53
854
534
0.57
895
572
0.61
1400
735
456
0.49
789
498
0.53
837
540
0.58
882
581
0.62
923
619
0.66
1500
765
509
0.55
819
550
0.59
867
592
0.64
911
633
0.68
953
672
0.72
1600
796
567
0.61
850
609
0.65
899
651
0.70
943
692
0.74
984
730
0.78
1700
829
631
0.68
883
673
0.72
932
715
0.77
976
756
0.81
1017
794
0.85
1800
863
701
0.75
918
743
0.80
966
785
0.84
1010
826
0.89
1051
864
0.93
1900
899
776
0.83
953
818
0.88
1001
860
0.92
1045
901
0.97
1087
939
1.01
2000
936
857
0.92
990
899
0.96
1038
941
1.01
1082
981
1.05
-
-
-
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
1
0.7
0.8
0.9
1.0
1.1
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
RPM
WATTS
BHP
800
831
456
0.49
871
486
0.52
914
509
0.55
961
525
0.56
1012
532
0.57
900
846
477
0.51
886
507
0.54
929
530
0.57
976
546
0.59
1027
553
0.59
1000
864
502
0.54
905
531
0.57
947
555
0.60
994
571
0.61
1046
578
0.62
1100
885
531
0.57
926
561
0.60
969
584
0.63
1015
600
0.64
1067
607
0.65
1200
909
566
0.61
950
596
0.64
992
619
0.66
1039
635
0.68
1091
642
0.69
1300
935
607
0.65
976
636
0.68
1018
660
0.71
1065
676
0.72
-
-
-
1400
963
654
0.70
1004
683
0.73
1046
707
0.76
1093
722
0.77
-
-
-
1500
993
706
0.76
1033
736
0.79
1076
759
0.81
-
-
-
-
-
-
1600
1024
765
0.82
1065
794
0.85
1108
818
0.88
-
-
-
-
-
-
1700
1057
829
0.89
1098
859
0.92
-
-
-
-
-
-
-
-
-
1800
1091
899
0.96
-
-
-
-
-
-
-
-
-
-
-
-
1900
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
Factory Installed AK74 blower sheave and A39 belt.
AK61 blower sheave and A36 belt - Field installation required.