291627-YTG-B-0807
18
Unitary Products Group
TABLE 14: ELECTRICAL DATA
MODEL
DNH
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN.
MAX.
RLA
LRA
030
208/230-3-60
187
253
8.6
55
1.1
2.6
14.5
20
20
.96
75
030
460-3-60
414
504
4.3
27
0.6
1.4
7.4
15
15
.96
75
036
208/230-3-60
187
253
11.4
77
1.1
3.5
18.9
25
25
.96
75
036
460-3-60
414
504
5.7
39
0.6
1.8
9.5
15
15
.96
75
042
208/230-3-60
187
253
13.9
88
1.3
3.5
22.2
30
30
.96
75
042
460-3-60
414
504
6.4
44
0.7
1.8
10.5
15
15
.96
75
048
208/230-3-60
187
253
13.0
93
1.9
4.2
22.4
30
30
.96
75
048
460-3-60
414
504
6.4
46.5
1.0
2.1
11.1
15
15
.96
75
060
208/230-3-60
187
253
19.3
123
1.9
9.4
32.9
45
45
.96
75
060
460-3-60
414
504
10.0
62
1.0
4.7
16.0
20
20
.96
75
1. Utilization range “A” in accordance with ARI Standard 110.
2. Dual element, time delay type.